PHOENIX CONTACT 1009831
PHOENIX CONTACTNot available

PSR-MC38-2NO-1DO-24DC-SC - Safety relays

Safety relay for emergency stop, safety doors and light grids up to SIL3, Cat.4, PLe, 1- or 2-channel operation, automatic or manual, monitored start, 2 enabling current paths, 1 signal output, TBUS interface, US=24VDC, pluggable screw terminal block
Product Code: 1009831
Partner cod.: 1009831
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Description
Download
Tecnichal data
Product propertiesProduct type: Safety relays
Product family: PSRmini
Application: Emergency stop
Safety door
Light grid
Solenoid switch
Transponder
Relay type: Electromechanical relay with force-guided contacts in accordance with IEC/EN61810-3
Times
Typical response time: 200 ms (automatic start)
30 ms (manual, monitored start)
Typ. starting time with Us: 200 ms (when controlled via A1)
Typical release time: 25 ms (when actuation is via the sensor circuit)
60 ms (when controlled via A1)
Restart time: < 1 s (Boot time)
Recovery time: < 500 ms
Electrical propertiesMaximum power dissipation for nominal condition: 16.6 W (at US=26.4V, IL²=72A²)
Nominal operating mode: 100% operating factor
Air clearances and creepage distances between the power circuits
Rated insulation voltage: 250 V
Rated surge voltage/insulation: Safe isolation, reinforced insulation 6 kV between input circuit and enabling current path (13/14) and enabling current path (23/24)
Basic insulation 4 kV between all current paths and housing
Supply
Designation: A1/A2
Rated control circuit supply voltage US: 20.4 VDC ... 26.4 VDC
24 VDC -15% / +10% (provide external protection)
Rated control supply current IS: typ. 75 mA
Power consumption at US: typ. 1.8 W
Inrush current: < 4 A (Δt=3ms at Us)
Filter time: 20 ms (at A1 in the event of voltage dips at Us)
Protective circuit: Serial protection against polarity reversal; Suppressor diode
Input dataDigital: Sensor circuit (S10, S12, S13, S22)
Description of the input: safety-related sensor inputs
Number of inputs: 4
Input voltage range "1" signal: 20.4 VDC ... 26.4 VDC
Inrush current: < 40 mA (typ. with US at S10)
< 300 mA (typ. with US at S12, Δt=150ms)
< 3 mA (Typically with US at S13)
> -300 mA (Typically with US at S22, Δt=150ms)
Filter time: 2 ms (At S10, S12, S13; test pulse width of low test pulses)
1 s (At S10, S12, S13; test pulse rate of low test pulses)
No brightness test pulses / high test pulses permitted.
Concurrence: ∞
Max. permissible overall conductor resistance: 50 Ω
Protective circuit: Suppressor diode
Current consumption: 40 mA (typ. with US at S10)
45 mA (Typically with US at S12)
3 mA (Typically with US at S13)
-35 mA (Typically with US at S22, Δt=150ms)
Digital: Start circuit (Y1, S34, S35)
Description of the input: non-safety-related
Number of inputs: 3
Input voltage range "1" signal: 20.4 VDC ... 26.4 VDC
Inrush current: < 60 mA (Typically with US at Y1, Δt=150ms)
< 270 mA (Typically with US at S34, Δt=15ms)
< 80 mA (Typically with US at S35, Δt=25ms)
Filter time: No darkness test pulses / low test pulses permitted. No brightness test pulses / high test pulses permitted.
Max. permissible overall conductor resistance: 50 Ω
Protective circuit: Suppressor diode
Current consumption: typ. 10 mA (Typically with US at Y1)
typ. 34 µA (Typically with US at S35)
Output dataRelay: Enabling current path (13/14, 23/24)
Output description: safety-related N/O contacts
2 NO contacts each in series, without delay, floating
Number of outputs: 2 (undelayed)
Contact switching type: 2 enabling current paths
Contact material: AgSnO2
Switching voltage: min. 10 V AC/DC
max. 250 V AC/DC (Observe the load curve)
Switching capacity: min. 100 mW
Inrush current: min. 10 mA
max. 6 A
Switching capacity in accordance with IEC 60947-5-1: 5 A (24V (DC13))
5 A (250V (AC15))
Limiting continuous current: 6 A
Sq. Total current: 72 A2 (observe derating)
Switching frequency: max. 0.5 Hz
Mechanical service life: 10x 106 cycles
Output fuse: 10 A gL/gG
4 A gL/gG (for low-demand applications)
Signal: Y30
Output description: PNP
non-safety-related
Number of outputs: 1
Voltage: approx. 23.9 VDC (Us-0.1V)
Current: max. 100 mA
Maximum inrush current: 500 mA (Δt=1ms at Us)
Protective circuit: Suppressor diode
Connection dataConnection technology
pluggable: yes
Conductor connection
Connection method: Screw connection
Conductor cross section rigid: 0.2 mm² ... 2.5 mm²
Conductor cross section flexible: 0.2 mm² ... 2.5 mm²
Conductor cross-section AWG: 24 ... 12
Stripping length: 7 mm
Screw thread: M3
Tightening torque: 0.5 Nm ... 0.6 Nm
SignalingStatus display: 4 x green LEDs
Operating voltage display: 1 x green LED
DimensionsWidth: 22.5 mm
Height: 112.2 mm
Depth: 114.5 mm
Material specificationsHousing material: Polyamide
CharacteristicsSafety data
Stop category: 0
Safety data: ENISO13849
Category: 4 (5ADC13; 5AAC15; 8760switching cycles/year)
Performance level (PL): e
Safety data: IEC 61508 - High demand
Safety Integrity Level (SIL): 3
Safety data: IEC 61508 - Low demand
Safety Integrity Level (SIL): 3
Safety data: ENIEC 62061
Safety Integrity Level (SIL): 3
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Min. degree of protection of inst. location: IP54
Ambient temperature (operation): -20°C ... 55°C (observe derating)
Ambient temperature (storage/transport): -40°C ... 70°C
Maximum altitude: ≤ 2000 m (Above sea level)
Max. permissible humidity (storage/transport): 75 % (on average, 85% infrequently, non-condensing)
Max. permissible relative humidity (operation): 75 % (on average, 85% infrequently, non-condensing)
Shock: 15g
Vibration (operation): 10Hz...150Hz, 2g
ApprovalsCE
Identification: CE-compliant
Standards and regulationsAir clearances and creepage distances between the power circuits
Standards/regulations: IEC 60664-1
MountingMounting type: DIN rail mounting
Assembly instructions: See derating curve
Mounting position: vertical or horizontal
Connection method: Screw connection
Technical Specs
ECLASSECLASS-11.0: 27371819
ECLASS-12.0: 27371819
ECLASS-13.0: 27371819
ETIMETIM 9.0: EC001449
UNSPSCUNSPSC 21.0: 39122200
Description
Safety relay for emergency stop, safety doors and light grids up to SILCL 3, Cat. 4, PL e, 1- or 2-channel operation, automatic or manual, monitored start, 2 enabling current paths, 1 signal output, TBUS interface, US = 24 V DC, pluggable screw terminal block
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_00922.pdf

Approvals_00923.pdf

Approvals_01216.pdf

Approvals_01217.pdf

Certification_00207.pdf

Data_sheet_00064.pdf

Manufacturer_declaration_00795.pdf

Manufacturer_declaration_01644.pdf

Manufacturer_declaration_05474.pdf

Manufacturer_declaration_05843.pdf

Package_slip_01973.pdf

Technical_drawing_05253.pdf