Industrial Automation
Product properties | Product type: Single relay Mechanical service life: 5x 106 cycles |
Electrical properties | Service life electrical: see diagram Maximum power dissipation for nominal condition: 0.43 W Test voltage (Winding/contact): 5 kV AC (50Hz, 1min., winding/contact) Test voltage (Contact/contact): 5 kV AC (50Hz, 1min., contact/contact) Test voltage (Changeover contact/changeover contact): 5 kV AC (Changeover contact/changeover contact) |
Input data | Coil side Nominal input voltage UN: 110 VDC Input voltage range: 88 VDC ... 242 VDC (20°C) Drive and function: monostable Drive (polarity): non-polarized Typical input current at UN: 3.6 mA Typical response time: 9 ms Typical release time: 6 ms |
Output data | Switching Contact switching type: 2 changeover contacts Type of switch contact: Single contact Contact material: AgNi Maximum switching voltage: 250 V AC/DC Minimum switching voltage: 12 V (at 10 mA) Limiting continuous current: 8 A Maximum inrush current: 16 A (20ms) Min. switching current: 10 mA (at 12 V) Interrupting rating (ohmic load) max.: 2000 VA (for 250 V AC) Motor load according to UL 508: 1/4HP, 120VAC (N/O contact) 1/2HP, 240VAC (N/O contact) |
Connection data | Connection method: Plug / solder connection |
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/31d12b5fa5e40549afb72472815e1a9f/-S204x204-FJPG Width: 12.7 mm Height: 29 mm Depth: 25 mm |
Environmental and real-life conditions | Ambient conditions Ambient temperature (operation): -40°C ... 70°C Ambient temperature (storage/transport): -40°C ... 85°C |
Approvals | Corrosive gas test Identification: ISA-S71.04. G3 Harsh Group EN60068-2-60 |
Standards and regulations | Standards/regulations: EN61810-1 VDE0435-201 EN50178 |
Description other products