PHOENIX CONTACT 1038842
PHOENIX CONTACTNot available

BLT-SKT-230-A - Type 3 surge protection device

Type 3 surge protection for permanent installation on ground contact sockets. Circuit with thermal monitoring, acoustic fault warning.
Product Code: 1038842
Partner cod.: 1038842
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Description
Download
Tecnichal data
Product propertiesIEC power supply system: TN-S
TT
Type: Socket mounting module
Product type: Device protection
Product family: BLOCKTRAB
Number of positions: 2
Surge protection fault message: Acoustic
Insulation characteristics
Overvoltage category: III
Pollution degree: 2
IEC test classification: III
T3
EN type: T3
Number of ports: One
Connection dataConnection method: Single wires
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/5b88fabae477bd4f85b5c2d125a42993/-S204x204-FJPG
Width: 53 mm
Height: 53 mm
Depth: 32 mm
Material specificationsFlammability rating according to UL 94: V-0
CTI value of material: 600
Insulating material: PA 6.6-FR
Material group: I
Housing material: PA 6.6-FR
Protective circuitMode of protection: L-N
L-PE
N-PE
Direction of action: 1L-N & N-PE
Nominal voltage UN: 230VAC(TN-S)
230VAC(TT - only in use with RCD)
Nominal frequency fN: 50 Hz (60Hz)
Maximum continuous voltage UC: 255 VAC
Residual current IPE: ≤ 5 µA
Reference test voltage UREF: 255 VAC
Maximum discharge current Imax (8/20) µs: 4 kA
Combination wave UOC: 6 kV
Voltage protection level Up: ≤ 1.5 kV
TOV behavior at UT (L-N): 440 VAC (5s / withstand mode)
440 VAC (120min / withstand mode)
TOV behavior at UT (L-PE): 440 VAC (5s / withstand mode)
440 VAC (120min / withstand mode)
1455 VAC (200ms / safe failure mode)
TOV behavior at UT (N-PE): 1200 VAC (200ms / safe failure mode)
Response time tA (L-N): ≤ 25 ns
Response time tA (L-PE): ≤ 100 ns
Response time tA (N-PE): ≤ 100 ns
Max. required back-up fuse: 16 A (MCB B)
Short-circuit current rating ISCCR: 1 kA AC
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20 (Installed)
Ambient temperature (operation): -20°C ... 70°C
Ambient temperature (storage/transport): -20°C ... 70°C
Altitude: ≤ 2000 m (amsl)
Permissible humidity (operation): 5 % ... 95 %
Standards and regulationsStandards/specifications: IEC 61643-11
Note: 2011
EN 61643-11
Standards/specifications: EN61643-11
Note: 2012
MountingMounting type: in device sockets of insulating material with standard ground contact sockets
Technical Specs
ECLASSECLASS-11.0: 27130806
ECLASS-13.0: 27171203
ETIMETIM 9.0: EC000942
UNSPSCUNSPSC 21.0: 39121600
Description
Type 3 surge protection for permanent installation on ground contact sockets. Circuit with thermal monitoring, acoustic fault warning.
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Flyer_00001.pdf

Flyer_00002.pdf

Manufacturer_declaration_01076.pdf

Manufacturer_declaration_02058.pdf

Manufacturer_declaration_05980.pdf

Package_slip_00230.pdf

Technical_drawing_06238.pdf