Industrial Automation
Notes | Utilization restriction EMC note: EMC: class A product, see manufacturer's declaration in the download area |
Product properties | Product type: Temperature transmitter Product family: MACX Analog Application: Temperature No. of channels: 1 Type: Signal conditioners with SIL functional safety Configuration: Software Insulation characteristics: GBStandard Overvoltage category: II Pollution degree: 2 |
Electrical properties | Alignment span: ± 5 % Alignment zero: ± 5 % No. of channels: 1 Electrical isolation: 3-way isolation Electrical isolation between input and output: yes Step response (0â99%): 1 s ⤠1.7 s Temperature coefficient, typical: 0.01 %/K Transmission error, typical: 0.1 % (e.g. for Pt 100, 300 K span, 4 ... 20 mA) Electrical isolation Input/output/power supply Rated insulation voltage: 300 Vrms Test voltage: 2.5 kV AC (50Hz, 60s) Insulation: Safe isolation in accordance with IEC/EN61010-1 Electrical isolation Input/output Electrical isolation: 375 V (Peak value in accordance with IEC/EN 60079-11) Electrical isolation Input/power supply Electrical isolation: 375 V (Peak value in accordance with IEC/EN 60079-11) Supply Nominal supply voltage: 24 VDC Supply voltage range: 19.2 VDC ... 30 VDC (24VDC, -20%...+25%) Power dissipation: ⤠0.76 W Power consumption: ⤠1 W |
Input data | Signal Number of inputs: 1 Measurement Sensor types (RTD) that can be used: Pt, Ni, Cu sensors: 2, 3, 4-wire Temperature measuring range: -200°C ... 850°C (Range depending on the sensor type) ⥠50 K Linear resistance measuring range: 0 é ... 50 ké Potentiometer resistance range: 0 é ... 50 ké Max. permissible overall conductor resistance: 50 é (Per cable) Sensor input current: 10 µA ... 210 µA (Up to 2x 210µA with 3-conductor technology) |
Output data | Signal: Current Number of outputs: 1 Configurable/programmable: Yes Current output signal: 0 mA ... 20 mA 4 mA ... 20 mA (SIL) Max. current output signal: ⥠21 mA Load/output load current output: ⤠600 é Output ripple (current): < 15 µAPP < 10 µArms Behavior in the event of a sensor error: As per NE 43 or can be freely defined |
Connection data | Connection method: Screw connection Stripping length: 7 mm Screw thread: M3 Conductor cross section rigid: 0.2 mm² ... 2.5 mm² Conductor cross section flexible: 0.2 mm² ... 2.5 mm² Conductor cross section AWG: 24 ... 14 Tightening torque: 0.5 Nm ... 0.6 Nm Test socket Max. diameter: 2 mm |
Ex data | Ex installation (EPL): Gc Div.2 |
Signaling | Status display: Green LED (supply voltage) Red LED, flashing 2.4Hz (cable error, sensor error on input or output, ERR) Red LED, flashing 1.2Hz (service operation, ERR) Red LED, permanently on (module error, ERR) |
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/d4485e18fd60154ba93005f91a55c68d/-S204x204-FJPG Width: 12.5 mm Height: 112.5 mm Depth: 113.7 mm Depth NS35/7,5: 114.5 mm (Snapped onto DIN rail NS35/7,5 in accordance with EN60715) |
Material specifications | Flammability rating according to UL 94: V0 (Housing) Housing material: PA 6.6-FR |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -40°C ... 70°C (Any mounting position) Ambient temperature (storage/transport): -40°C ... 80°C Permissible humidity (operation): 5 % ... 95 % (non-condensing) Altitude range (⤠2000 m) Altitude: ⤠2000 m (The technical data refers to altitudes â¤2000m above mean sea level. For altitudes >2000m above mean sea level, refer to the data sheet.) Ambient temperature (operation): -40°C ... 70°C Test voltage: 2.5 kV Rated insulation voltage: 300 Vrms Altitude range (⤠3000 m) Height range: > 2000 m ... 3000 m Ambient temperature (operation): -40°C ... 63°C Test voltage: 2.25 kV Rated insulation voltage: 150 Vrms Altitude range (⤠4000 m) Height range: > 3000 m ... 4000 m Ambient temperature (operation): -40°C ... 56°C Test voltage: 2 kV Rated insulation voltage: 150 Vrms Altitude range (⤠5000 m) Height range: > 4000 m ... 5000 m Ambient temperature (operation): -40°C ... 49°C Test voltage: 1.75 kV Rated insulation voltage: 150 Vrms |
Approvals | CE Certificate: CE-compliant Note: and EN61326 ATEX Identification: ï II 3 G Ex ec ic IIC T4 Gc Certificate: PxCIF19ATEX1050192X UKCAEx(UKEX) Identification: ï II 3 G Ex ec ic IIC T4 Gc Certificate: CML 22UKEX3531X IECEx Identification: Ex ec ic IIC T4 Gc Certificate: IECEx IBE 19.0001 X CCC/China-Ex Identification: Ex nA ic IIC T4 Gc Certificate: NEPSIGYJ20.1305X UL, USA/Canada Identification: UL 61010 Listed Class I, Div. 2, Groups A, B, C, D T4 Class I, Zone 2, Group IIC T4 Shipbuilding approval Certificate: DNV GL TAA00000AG Safety Integrity Level (SIL, IEC 61508) Identification: 2 EACEx Identification: ï 2Ex ec ic IIC T4 Gc Certificate: BY/112 02.01 TP012 103.01 00082 DNV GL data Temperature: B Humidity: B Vibration: A EMC: B Enclosure: Required protection according to the Rules shall be provided upon installation on board |
EMC data | Noise immunity: EN 61000-6-2 Note: When being exposed to interference, there may be minimal deviations. Electromagnetic compatibility: Conformance with EMC directive Noise emission: EN 61000-6-4 Electromagnetic HF field Designation: Electromagnetic RF field Standards/regulations: EN61000-4-3 Typical deviation from the measuring range final value: 1 % Fast transients (burst) Designation: Fast transients (burst) Standards/regulations: EN61000-4-4 Typical deviation from the measuring range final value: 1 % Conducted interference Designation: Conducted interferences Standards/regulations: EN61000-4-6 Typical deviation from the measuring range final value: 1 % |
Standards and regulations | Electrical isolation: 3-way isolation GBStandard Standards/regulations: GB3836.1 GB3836.4 GB3836.8 |
Mounting | Mounting type: DIN rail mounting |
ECLASS | ECLASS-11.0: 27210129 ECLASS-12.0: 27210129 ECLASS-13.0: 27210129 |
ETIM | ETIM 8.0: EC002919 |
UNSPSC | UNSPSC 21.0: 41112100 |