Industrial Automation
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/9e6e964f367bbe4db818e0ffaa606273/-S204x204-FJPG Width: 14.9 mm Height: 62.2 mm Depth: 62 mm |
Interfaces | SmartElement interface Number of interfaces: 1 Connection method: Card edge connector Transmission speed: See system in which you use the SmartElement. |
System properties | Module Input address area: 5 Byte (PROFIsafe2.6.1) Output address area: 6 Byte (PROFIsafe2.6.1) Required configuration data: 5 Byte |
Output data | Digital Output name: Safe digital outputs Output description: EN61131-2 Connection method: Push-in connection Connection technology: 2-conductor Number of outputs: 2 (2-channel assignment) 4 (1-channel assignment) Protective circuit: Short-circuit protection, overload protection of the outputs; electronic Output voltage: 24 VDC Output current: max. 2 A (per output) Maximum output current per channel: 2 A Maximum output current per module: 4 A Nominal output voltage: 24 VDC Load min.: 1.5 ké (at nominal voltage) Output voltage when switched off: < 5 V Output current when switched off: < 2 mA Nominal load, inductive: 48 VA (1H; 12é; at nominal voltage) Nominal load, ohmic: 48 W (12é, at nominal voltage) Switching frequency: 1 Hz (0.2Hz at >1A) Reverse voltage resistance to short pulses: no Behavior with overload: Switch-off of the relevant output, restart upon acknowledgment Behavior with inductive overload: Output can be destroyed |
Product properties | Type: modular Product type: I/O component Product family: Axioline SmartElements Mounting position: any Application: Functional safety PROFIsafe only for connection to Phoenix Contact or Siemens controller Operating mode: PROFIsafe 2.4, PROFIsafe 2.6.1 Insulation characteristics Overvoltage category: II (IEC 60664-1) Pollution degree: 2 (EN60664-1) |
Electrical properties | Transmission medium: Copper Potentials Protection: external fusing via the system in which the SmartElement is used Protective circuit: Surge protection of the supply voltage; electronic (35 V, 0.5 s) Polarity reversal protection of the supply voltage; via the system in which the SmartElement is used Potentials: AxiolineF local bus supply (U Supply voltage: 5 VDC (via bus base module) Current draw: max. 120 mA (at UBus 5VDC) typ. 93 mA (at UBus 5VDC) Potentials: Communications power supply of the Smart Elements (U Supply voltage: using card edge connectors Potentials: I/O supply (U Supply voltage: 24 VDC (using card edge connectors) Supply voltage range: 19.2 VDC ... 30 VDC (including all tolerances, including ripple) Current draw: max. 30 mA ((Supply from UP with 30VDC, all outputs set, without supply to the actuators)) typ. 25 mA ((Supply from UP with 24VDC, all outputs set, without supply to the actuators)) Current consumption: min. 21 mA ((Supply from UP with 19.2VDC, all outputs set, without supply to the actuators)) Power consumption: max. 900 mW min. 403 mW |
Connection data | Connection technology Connection name: I/O Note on the connection method: Note the specification in the section Conductor cross sections, and stripping and insertion lengths. Conductor connection Connection method: Push-in connection Conductor cross section rigid: 0.25 mm² ... 1.5 mm² Conductor cross section flexible: 0.25 mm² ... 1.5 mm² Conductor cross section AWG: 24 ... 16 Conductor cross section flexible, with ferrule without plastic sleeve: 0.25 mm² ... 1.5 mm² Conductor cross section, flexible, with ferrule, with plastic sleeve: 0.25 mm² ... 1.5 mm² Stripping length: 8 mm I/O Connection method: Push-in connection Note on the connection method: Note the specification in the section Conductor cross sections, and stripping and insertion lengths. Conductor cross section, rigid: 0.25 mm² ... 1.5 mm² Conductor cross section, flexible: 0.25 mm² ... 1.5 mm² Conductor cross section AWG: 24 ... 16 Conductor cross section, flexible, with ferrule, with plastic sleeve: 0.25 mm² ... 1.5 mm² Conductor cross section flexible, with ferrule without plastic sleeve: 0.25 mm² ... 1.5 mm² Stripping length: 8 mm |
Environmental and real-life conditions | Ambient conditions Ambient temperature (operation): -25°C ... 60°C Degree of protection: IP20 Degree of protection at installation location: min. IP54 Air pressure (operation): 70 kPa ... 108 kPa Air pressure (storage/transport): 66 kPa ... 108 kPa Ambient temperature (storage/transport): -40°C ... 85°C Permissible humidity (operation): 5 % ... 95 % (non-condensing) Permissible humidity (storage/transport): 5 % ... 95 % (non-condensing) |
Standards and regulations | Protection class: III (IEC 61140, EN61140, VDE0140-1) Air clearances and creepage distances Air clearances and creepage distances: IEC 60664-1 |
Mounting | Mounting type: Smart Element slot Mounting position: any |
ECLASS | ECLASS-11.0: 27242604 ECLASS-12.0: 27242604 ECLASS-13.0: 27242604 |
ETIM | ETIM 9.0: EC001599 |
UNSPSC | UNSPSC 21.0: 32151600 |
Description other products