Industrial Automation

Mechatronics

Industrial Safety

Panel Components

Sensors and Systems of Vision

Pneumatics

Network Comunications

Automation Cables

Design Software

Access services

Enter your reserved area

Access services

Enter your reserved area

PHOENIX CONTACT 1079389
PHOENIX CONTACTNot available

PLC-RPT-230AC/21-21/SO46/HI - Relay Module

PLC-INTERFACE consisting of PLC-BSC.../21-21/SO46/HI basic terminal block with Push-in connection and plug-in miniature relay with power contact, 2 changeover contacts, nominal input voltage of 230VAC, with defined activation and deactivation thresholds
Product Code: 1079389
Partner cod.: 1079389
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Description
Download
Tecnichal data
Product propertiesProduct type: Relay Module
Product family: PLC-INTERFACE
Application: Filter to prevent interference
Operating mode: 100% operating factor
Mechanical service life: 3x 107 cycles
Insulation characteristics
Insulation: Basic insulation
Safe isolation, reinforced insulation, and 6 kV between input circuit and output contact current paths
Insulation characteristics: Air clearances and creepage distances between the power circuits
Insulation: Basic insulation
Safe isolation, reinforced insulation, and 6 kV between input circuit and output contact current paths
Overvoltage category: III
Pollution degree: 2
Electrical propertiesMaximum power dissipation for nominal condition: 1.04 W
Test voltage (Winding/contact): 4 kV AC (50Hz, 1min., winding/contact)
Test voltage (Changeover contact/changeover contact): 2.5 kV AC (50Hz, 1min., changeover contact/changeover contact)
Air clearances and creepage distances between the power circuits
Rated surge voltage: 4 kV
Input dataCoil side
Nominal input voltage UN: 230 VAC
Input voltage range: 190 VAC ... 264 VAC (20°C)
Switch-on threshold: 190 VAC
Switch-off threshold: 170 VAC
Drive and function: monostable
Drive (polarity): polarized
Typical input current at UN: 14 mA (50Hz)
Input power dissipation for UN: 3 VA
Typical response time: 10 ms
Typical release time: 8 ms
Coil voltage: 110 VDC
Protective circuit: Bridge rectifier
Input circuit: RC element with threshold value switch
Operating voltage display: Yellow LED
Output dataSwitching
Contact switching type: 2 changeover contacts
Type of switch contact: Single contact
Contact material: AgNi
Maximum switching voltage: 250 V AC/DC (The separating plate PLC-ATP should be installed for voltages larger than 250 V (L1, L2, L3) between identical terminal blocks in adjacent modules. Potential bridging is then carried out with FBST 8-PLC... or ...FBST 500...)
Minimum switching voltage: 5 V AC/DC (10mA)
Limiting continuous current: 6 A
Maximum inrush current: 15 A (300ms)
Min. switching current: 10 mA (5V)
Interrupting rating (ohmic load) max.: 140 W (at 24 V DC)
85 W (at 48 V DC)
60 W (at 60 V DC)
44 W (at 110 V DC)
57 W (at 220 V DC)
1500 VA (for 250 V AC)
Switching capacity: 2 A (at 24 V, DC13)
0.2 A (at 250 V, DC13)
3 A (at 24 V, AC15)
3 A (at 120 V, AC15)
3 A (at 250 V, AC15)
Connection dataConnection method: Push-in connection
Stripping length: 10 mm
Conductor cross section rigid: 0.14 mm² ... 2.5 mm²
Conductor cross section flexible: 0.14 mm² ... 2.5 mm²
0.2 mm² ... 2.5 mm² (Single ferrule)
2x 0.5 mm² ... 1 mm² (TWIN ferrule)
Conductor cross section AWG: 26 ... 14
DimensionsWidth: 14 mm
Height: 80 mm
Depth: 94 mm
Material specificationsFlammability rating according to UL 94: V0 (Housing)
Environmental and real-life conditionsAmbient conditions
Degree of protection (Relay): RT III (Relay)
Degree of protection (Relay base): IP20 (Relay base)
Degree of protection (Installation location): ≥ IP54 (Installation location)
Ambient temperature (operation): -40°C ... 50°C
Ambient temperature (storage/transport): -40°C ... 85°C
Altitude: ≤ 2000 m
ApprovalsCE
Certificate: CE-compliant
UKCA
Certificate: UKCA-compliant
Shipbuilding approval
Certificate: TAE0000196
Corrosive gas test
Identification: ISA-S71.04. G3 Harsh Group
EN60068-2-60
DNV GL data
Temperature: D
Humidity: A
Vibration: B/C
EMC: B
Enclosure: Required protection according to the Rules shall be provided upon installation on board
EMC dataLow Voltage Directive: Conformance with Low Voltage Directive
Electromagnetic compatibility: Conformance with EMC directive
Standards and regulationsAir clearances and creepage distances between the power circuits
Standards/regulations: IEC 60947-5-1
MountingMounting type: DIN rail mounting
Assembly instructions: in rows with zero spacing
Mounting position: any
Technical Specs
ECLASSECLASS-11.0: 27371601
ECLASS-12.0: 27371601
ECLASS-13.0: 27371601
ETIMETIM 9.0: EC001437
UNSPSCUNSPSC 21.0: 39122300
Description
PLC-INTERFACE consisting of PLC-BSC.../21-21/SO46/HI basic terminal block with Push-in connection and plug-in miniature relay with power contact, 2 changeover contacts, nominal input voltage of 230 V AC, with defined activation and deactivation thresholds
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Application_note_00006.pdf

Approvals_00240.pdf

Approvals_01560.pdf

Approvals_01561.pdf

Approvals_01883.pdf

Manufacturer_declaration_03393.pdf

Manufacturer_declaration_03394.pdf

Manufacturer_declaration_03599.pdf

Manufacturer_declaration_06224.pdf

Package_slip_01742.pdf

Product_information_00033.pdf

Product_information_00044.pdf

Technical_drawing_07744.pdf