Industrial Automation
Notes | General: Terminal block for aluminum and copper conductors (AL-CU) Generalâ Note: We recommend using ferrules when using flexible donductor. |
Product properties | Product type: Feed-through terminal block Number of positions: 1 Number of connections: 2 Number of rows: 1 Potentials: 1 Insulation characteristics Overvoltage category: III Degree of pollution: 3 |
Electrical properties | Rated surge voltage: 8 kV Maximum power dissipation for nominal condition: 7.54 W |
Connection data | Nominal cross section: 95 mm² Aluminum conductor Screw thread: M14 Note: Screws with hexagonal socket The following values apply to aluminum conductors The values for aluminum conductors relate to rigid and multi-stranded conductors in accordance with EN60228. Application notes on connecting aluminum conductors can be found in the download area. Tightening torque: 20 Nm Stripping length: 27 mm Connection in acc. with standard: IEC 61238-1 Conductor cross section rigid: 16 mm² ... 95 mm² Cross section AWG: 4 ... 4/0 (converted acc. to IEC) Nominal current: 220 A Maximum load current: 220 A (with 95mm² conductor cross section â test current in accordance with IEC 61238-1) Nominal voltage: 1000 V Nominal cross section: 95 mm² Copper conductor Note: The following values apply to copper wires Flexible conductors, class5, in accordance with EN60228. Tightening torque: 20 Nm Stripping length: 27 mm Connection in acc. with standard: IEC 60947-7-1 Conductor cross section rigid: 16 mm² ... 95 mm² Cross section AWG: 4 ... 4/0 (converted acc. to IEC) Conductor cross section flexible: 50 mm² ... 70 mm² Conductor cross-section flexible (ferrule without plastic sleeve): 16 mm² ... 70 mm² Flexible conductor cross section (ferrule with plastic sleeve): 16 mm² ... 70 mm² 2 conductors with same cross section, flexible: 16 mm² ... 35 mm² Nominal current: 232 A Maximum load current: 232 A (with 95 mm² conductor cross section) Nominal voltage: 1000 V Nominal cross section: 95 mm² |
Dimensions | Width: 25.1 mm Height: 93.6 mm Depth: 58 mm Depth on NS35/7,5: 58 mm Depth on NS35/15: 65.5 mm Hole diameter: 2.75 mm |
Material specifications | Color: green Flammability rating according to UL 94: V0 Insulating material group: II Insulating material: PA Relative insulation material temperature index (Elec., UL 746 B): 400°C |
Electrical tests | Surge voltage test Test voltage setpoint: 8 kV Result: Test passed Temperature-rise test Requirement temperature-rise test: Increase in temperature â¤45K Result: Test passed Short-time withstand current 95 mm²: 11.4 kA Power-frequency withstand voltage Test voltage setpoint: 2.2 kV Result: Test passed |
Mechanical properties | Mechanical data Open side panel: No |
Mechanical tests | Mechanical strength Result: Test passed Attachment on the carrier DIN rail/fixing support: NS35 Test force setpoint: 15 N Result: Test passed Test for conductor damage and slackening Rotation speed: 10rpm Revolutions: 135 Conductor cross section/weight: 16 mm² / 2.9 kg 95 mm²/14 kg Result: Test passed |
Environmental and real-life conditions | Needle-flame test Time of exposure: 10 s Result: Test passed Oscillation/broadband noise Specification: DINEN50155 (VDE0115-200):2018-05 Spectrum: Service life test category2, bogie-mounted Frequency: f1 = 5 Hz to f2 = 250 Hz ASD level: 6.12 (m/s²)²/Hz Acceleration: 3.12g Test duration per axis: 5 h Test directions: X-, Y- and Z-axis Result: Test passed Shocks Pulse shape: Half-sine Acceleration: 30g Shock duration: 18ms Number of shocks per direction: 3 Test directions: X-, Y- and Z-axis (pos. and neg.) |
Standards and regulations | Connection in acc. with standard: IEC 61238-1 IEC 60947-7-1 |
Mounting | Mounting type: NS35/15 NS 35/7,5 |