Industrial Automation
AXL SE RS485 - Communication module


Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/9e6e964f367bbe4db818e0ffaa606273/-S204x204-FJPG Width: 14.9 mm Height: 62.2 mm Depth: 62 mm |
Notes | Utilization restriction EMC note: EMC: class A product, see manufacturer's declaration in the download area |
Interfaces | SmartÃElement interface Number of interfaces: 1 Connection method: Card edge connector Transmission speed: See system in which you use the SmartÃElement. Start time until ready to operate: < 500 ms RS-485 Number of interfaces: 1 Connection method: Push-in connection Note on the connection method: Use shielded cables. Transmission speed: 1200Ãbps ... 230,400Ãbps (can be parameterized) Transmission physics: Copper Protocols supported: Transparent Termination resistor: 120 é (active, integrated) Data bits: 7 or 8 Stop bits: 1 or 2 Input buffer: 4 kByte Output buffer: 1 kByte |
System properties | Module ID code (hex): none Process data channel: 160 bit Input address area: 20 Byte Output address area: 20 Byte Required parameter data: 10 Byte Required configuration data: 7 Byte |
Product properties | Type: modular Product type: I/O component Product family: Axioline SmartÃElements Mounting position: See the system in which the SmartÃElement is used. Insulation characteristics Overvoltage category: II (IEC 60664-1, ENÃ60664-1) Pollution degree: 2 (IEC 60664-1, ENÃ60664-1) |
Electrical properties | Potentials: Communications power supply of the Smart Elements (U Supply voltage: using card edge connectors Potentials: I/O supply (U Supply voltage: 24 VÃDC (using card edge connectors) Supply voltage range: 19.2 VÃDC ... 30 VÃDC (including all tolerances, including ripple) Current draw: max. 18 mA typ. 10 mA Current consumption: min. 6 mA (without connected peripherals) Power consumption: max. 530 mW min. 144 mW Protective circuit: Surge protection; See the system in which the SmartÃElement is used. Reverse polarity protection; Polarity protection diode Electrical isolation/isolation of the voltage ranges Test voltage: Communications supply / 24 V supply (I/O): 500 VÃAC, 50 Hz, 1 min. Test voltage: Logic supply / RS-485 interface: 500 VÃAC, 50 Hz, 1 min. Test voltage: Communications supply / functional ground: 500 VÃAC, 50 Hz, 1 min. Test voltage: 24 V supply (I/O) / RS-485 interface: 500 VÃAC, 50 Hz, 1 min. Test voltage: 24ÃV supply (I/O) / functional ground: 500 VÃAC, 50 Hz, 1 min. Test voltage: RS-485 interface / functional ground: 500 VÃAC, 50 Hz, 1 min. |
Connection data | Connection technology Connection name: I/O Note on the connection method: Please observe the information provided on conductor cross sections in the ââ¬Ã AxiolineÃSmartÃElementsâ⬠user manual. Conductor connection Connection method: Push-in connection Conductor cross section rigid: 0.25 mm² ... 1.5 mm² Conductor cross section flexible: 0.25 mm² ... 1.5 mm² Conductor cross section AWG: 24 ... 16 Conductor cross section flexible, with ferrule without plastic sleeve: 0.25 mm² ... 1.5 mm² Conductor cross section, flexible, with ferrule, with plastic sleeve: 0.25 mm² ... 1.5 mm² Stripping length: 8 mm I/O Connection method: Push-in connection Note on the connection method: Please observe the information provided on conductor cross sections in the ââ¬Ã AxiolineÃSmartÃElementsâ⬠user manual. Conductor cross section, rigid: 0.25 mm² ... 1.5 mm² Conductor cross section, flexible: 0.25 mm² ... 1.5 mm² Conductor cross section AWG: 24 ... 16 Conductor cross section, flexible, with ferrule, with plastic sleeve: 0.25 mm² ... 1.5 mm² Conductor cross section flexible, with ferrule without plastic sleeve: 0.25 mm² ... 1.5 mm² Stripping length: 8 mm |
Environmental and real-life conditions | Ambient conditions Ambient temperature (operation): -25°C ... 60°C Degree of protection: IP20 Air pressure (operation): 70 kPa ... 106 kPa (up to 3000Ãm above sea level) Air pressure (storage/transport): 70 kPa ... 106 kPa (up to 3000Ãm above sea level) Ambient temperature (storage/transport): -40°C ... 85°C Permissible humidity (operation): 5 % ... 95 % (non-condensing) Permissible humidity (storage/transport): 5 % ... 95 % (non-condensing) |
Standards and regulations | Protection class: III (IEC 61140, ENÃ61140, VDEÃ0140-1) |
Mounting | Mounting type: Smart Element slot Mounting position: See the system in which the SmartÃElement is used. |