PT 10-FSI/C - Fuse modular terminal block


Notes | General Note: The current is determined by the fuse used, the voltage by the fuse or selected light indicator. |
Product properties | Product type: Fuse terminal block Number of connections: 2 Number of rows: 1 Potentials: 1 Insulation characteristics Overvoltage category: III Degree of pollution: 3 |
Electrical properties | Fuse type: Flat Rated surge voltage: 6 kV Maximum power dissipation for nominal condition: 1.82 W Fuse: C |
Connection data | Number of connections per level: 2 Nominal cross section: 10 mm² Note: The current is determined by the fuse used, the voltage by the light indicator. Stripping length: 18 mm ... 20 mm Internal cylindrical gage: A5 Connection in acc. with standard: IEC 60947-7-3 Conductor cross section rigid: 0.5 mm² ... 16 mm² Cross section AWG: 20 ... 6 (converted acc. to IEC) Conductor cross section flexible: 0.5 mm² ... 10 mm² Conductor cross section, flexible [AWG]: 20 ... 8 (converted acc. to IEC) Conductor cross-section flexible (ferrule without plastic sleeve): 0.5 mm² ... 10 mm² Flexible conductor cross section (ferrule with plastic sleeve): 0.5 mm² ... 10 mm² Conductor cross-section flexible (2 conductors with the same cross-section, with TWIN ferrule and plastic sleeve): 0.5 mm² ... 1.5 mm² 2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve: 0.5 mm² ... 4 mm² Nominal current: 25 A Maximum load current: 30 A Nominal voltage: 400 V Connection cross sections directly pluggable Conductor cross section rigid: 1 mm² ... 16 mm² Conductor cross-section flexible (ferrule without plastic sleeve): 1 mm² ... 10 mm² Flexible conductor cross section (ferrule with plastic sleeve): 1 mm² ... 10 mm² |
Dimensions | Width: 10.2 mm Height: 88.9 mm Depth: 49.5 mm Depth on NSÃ35/7,5: 50.5 mm Depth on NSÃ35/15: 58 mm |
Material specifications | Color: black Flammability rating according to UL 94: V0 Insulating material group: I Insulating material: PA Static insulating material application in cold: -60°C Relative insulation material temperature index (Elec., UL 746 B): 130°C Fire protection for rail vehicles (DIN EN 45545-2) R22: HL 1 - HL 3 Fire protection for rail vehicles (DIN EN 45545-2) R23: HL 1 - HL 3 Fire protection for rail vehicles (DIN EN 45545-2) R24: HL 1 - HL 3 Fire protection for rail vehicles (DIN EN 45545-2) R26: HL 1 - HL 3 Surface flammability NFPA 130 (ASTM E 162): passed Specific optical density of smoke NFPA 130 (ASTM E 662): passed Smoke gas toxicity NFPA 130 (SMP 800C): passed |
Mechanical properties | Mechanical data Open side panel: No |
Environmental and real-life conditions | Oscillation/broadband noise Specification: DINÃENÃ50155 (VDEÃ0115-200):2008-03 DINÃENÃ50155 (VDEÃ0115-200):2018-05 Spectrum: Service life test categoryÃ2, bogie-mounted Service life test categoryÃ1, classÃB, body mounted Frequency: f1 = 5 Hz to f2 = 250 Hz f1 = 5 Hz to f2 = 150 Hz ASD level: 6.12 (m/s²)²/Hz 0.964 (m/s²)²/Hz Acceleration: 3.12g 0.58g Test duration per axis: 5 h Test directions: X-, Y- and Z-axis Result: Test passed Shocks Specification: DINÃENÃ50155 (VDEÃ0115-200):2008-03 DINÃENÃ50155 (VDEÃ0115-200):2018-05 Pulse shape: Half-sine Acceleration: 5g Shock duration: 30Ãms Number of shocks per direction: 3 Test directions: X-, Y- and Z-axis (pos. and neg.) Result: Test passed Ambient conditions Ambient temperature (operation): -60°C ... 110°C (Operating temperature range incl. self-heating; for max. short-term operating temperature, see RTI Elec.) Ambient temperature (storage/transport): -25°C ... 60°C (for a short time, not exceeding 24Ãh, -60ðC to +70ðC) Ambient temperature (assembly): -5°C ... 70°C Ambient temperature (actuation): -5°C ... 70°C Permissible humidity (operation): 20 % ... 90 % Permissible humidity (storage/transport): 30 % ... 70 % |
Standards and regulations | Connection in acc. with standard: IEC 60947-7-3 |
Mounting | Mounting type: NS 35/7,5 NSÃ35/15 |