AXL SE FSDO4/2 2A - Safety module


Dimensions | Dimensional drawing: https://caas.phoenixcontact.com/caas/v1/stable/media/22794/full/b1500?format=jpg Width: 14.9 mm Height: 62.2 mm Depth: 62 mm |
Notes | Note on application Note on application: Only for industrial use |
Interfaces | FSoE Number of interfaces: 1 Connection method: Card edge connector Transmission speed: See system in which you use the Smart Element. |
System properties | Module Input address area: 6 Byte (FSoE) Output address area: 6 Byte (FSoE) Required configuration data: 5 Byte |
Output data | Digital: Output name: Safe digital outputs Output description: EN 61131-2 Connection method: Push-in connection Connection technology: 2-conductor Number of outputs: 2 (2-channel assignment) 4 (1-channel assignment) Protective circuit: Short-circuit protection, overload protection of the outputs; electronic Output voltage: 24 V DC Output current: max. 2 A (per output) Maximum output current per channel: 2 A Maximum output current per module: 4 A Nominal output voltage: 24 V DC Load min.: 1.5 ké (at nominal voltage) Output voltage when switched off: < 5 V Output current when switched off: < 2 mA Nominal load, inductive: 48 VA (1 H; 12 é; at nominal voltage) Nominal load, ohmic: 48 W (12 é, at nominal voltage) Switching frequency: 1 Hz (0.2 Hz at > 1 A) Reverse voltage resistance to short pulses: no Behavior with overload: Switch-off of the relevant output, restart upon acknowledgment Behavior with inductive overload: Output can be destroyed |
Product properties | Product type: I/O component Product family: Axioline Smart Elements Application: Functional safety FSoE Type: modular Mounting position: any Operating mode: FSoE Insulation characteristics Overvoltage category: II (IEC 60664-1) Pollution degree: 2 (EN 60664-1) |
Electrical properties | Potentials Protection: external fusing via the system in which the Smart Element is used Protective circuit: Surge protection of the supply voltage; electronic (35 V, 0.5 s) Polarity reversal protection of the supply voltage; via the system in which the Smart Element is used Potentials: Axioline F local bus supply (U Supply voltage: 5 V DC (via bus base module) Current draw: max. 120 mA (at UBus 5 V DC) typ. 93 mA (at UBus 5 V DC) Potentials: Communications power supply of the Smart Elements (U Supply voltage: using card edge connectors Potentials: I/O supply (U Supply voltage: 24 V DC (using card edge connectors) Supply voltage range: 19.2 V DC ... 30 V DC (including all tolerances, including ripple) Current draw: max. 30 mA ((Supply from UP with 30 V DC, all outputs set, without supply to the actuators)) typ. 25 mA ((Supply from UP with 24 V DC, all outputs set, without supply to the actuators)) Power consumption: min. 403 mW |
Connection data | Connection technology Connection name: I/O Note on the connection method: Note the specification in the section Conductor cross sections, and stripping and insertion lengths. Conductor connection Connection method: Push-in connection Conductor cross section rigid: 0.25 mm² ... 1.5 mm² Conductor cross section flexible: 0.25 mm² ... 1.5 mm² Conductor cross section AWG: 24 ... 16 Conductor cross section flexible, with ferrule without plastic sleeve: 0.25 mm² ... 1.5 mm² Conductor cross section, flexible, with ferrule, with plastic sleeve: 0.25 mm² ... 1.5 mm² Stripping length: 8 mm I/O Connection method: Push-in connection Note on the connection method: Note the specification in the section Conductor cross sections, and stripping and insertion lengths. Conductor cross section, rigid: 0.25 mm² ... 1.5 mm² Conductor cross section, flexible: 0.25 mm² ... 1.5 mm² Conductor cross section AWG: 24 ... 16 Conductor cross section, flexible, with ferrule, with plastic sleeve: 0.25 mm² ... 1.5 mm² Conductor cross section flexible, with ferrule without plastic sleeve: 0.25 mm² ... 1.5 mm² Stripping length: 8 mm |
Environmental and real-life conditions | Ambient conditions Ambient temperature (operation): -25 °C ... 60 °C Degree of protection: IP20 Degree of protection at installation location: min. IP54 Air pressure (operation): 70 kPa ... 108 kPa Air pressure (storage/transport): 66 kPa ... 108 kPa Ambient temperature (storage/transport): -40 °C ... 85 °C Permissible humidity (operation): 5 % ... 95 % (non-condensing) Permissible humidity (storage/transport): 5 % ... 95 % (non-condensing) |
Standards and regulations | Protection class: III (IEC 61140, EN 61140, VDE 0140-1) Air clearances and creepage distances Air clearances and creepage distances: IEC 60664-1 |
Mounting | Mounting type: Smart Element slot Mounting position: any |