Industrial Automation
Notes | General Note: The product is also suitable for use in photovoltaic systems with max. short-circuit current ISCPV = 15 kA (in accordance with EN 50539-11: 2013). |
Product properties | IEC test classification: PV I / II PV T1 / T2 EN type: T1 / T2 IEC power supply system: DC Type: DIN rail module, one-piece Product type: PV arrester Product family: VALVETRAB MB Installation location: Interior Installation location of the disconnect device: Internal Accessibility: Accessible Connection configuration: Y configuration SPD failure behavior: OCFM (Open-Circuit Failure Mode) Surge protection fault message: optical Insulation characteristics Pollution degree: 2 |
Connection data | Connection method: Screw connection Screw thread: M5 Tightening torque: 3 Nm Stripping length: 16 mm Conductor cross section flexible: 2.5 mm² ... 35 mm² Conductor cross section AWG: 14 ... 2 |
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/f287b5e8e540194fb41b84c8d6131892/-S204x204-FJPG Width: 71.2 mm Height: 120 mm Depth: 65.5 mm (incl. DIN rail 7.5mm) Horizontal pitch: 4 Div. |
Material specifications | Flammability rating according to UL 94: V-0 Insulating material: PA 6.6 PBT Housing material: PA 6.6 |
Mechanical properties | Mechanical data Open side panel: No |
Protective circuit | Mode of protection: (L+) - (L-) (L+) - PE (L-) - PE Direction of action: (L+)-PE & (L-)-PE & (L+)-(L-) Rated load current IL: 50 A Residual current IPE: ⤠100 µA DC ⤠540 µA AC Standby power consumption PC: ⤠150 mVA Nominal discharge current In (8/20) µs: 20 kA Maximum discharge current Imax (8/20) µs: 40 kA Impulse discharge current (10/350)µs, charge: 3.125 As Impulse discharge current (10/350)µs, specific energy: 9.77 kJ/é Impulse discharge current (10/350)µs, peak value limp: 6.25 kA Total discharge current Itotal (8/20)µs: 40 kA Total discharge current Itotal (10/350)µs: 12.5 kA Voltage protection level Up: ⤠4.5 kV Residual voltage Ures: ⤠4.5 kV (at In) ⤠3.3 kV (at 3kA) ⤠3.6 kV (at 6.25 kA) ⤠3.8 kV (at 10 kA) ⤠4.2 kV (at 15 kA) ⤠5.4 kV (at 40 kA) Response time tA: ⤠25 ns PV protective circuit Connection configuration: Y configuration SPD failure behavior: OCFM (Open-Circuit Failure Mode) Protective circuit DC voltage side (DC) Open circuit voltage UOCSTC: ⤠1250 VDC Maximum discharge current Imax (8/20) µs: 40 kA Response time tA: ⤠25 ns Impulse discharge current (10/350)µs, charge: 3.125 As Impulse discharge current (10/350)µs, specific energy: 9.77 kJ/é Impulse discharge current (10/350)µs, peak value limp: 6.25 kA Total discharge current Itotal (8/20)µs: 40 kA Total discharge current Itotal (10/350)µs: 12.5 kA Insulation resistance Riso: > 5 Gé (at 500 V DC) Nominal discharge current In (8/20) µs: 20 kA Rated load current IL: 50 A Continuous operating current ICPV: < 100 µA Maximum continuous operating voltage UCPV: 1500 VDC Short-circuit current rating ISCPV: 2000 A Residual voltage Ures: ⤠4.5 kV (at In) ⤠3.3 kV (at 3kA) ⤠3.6 kV (at 6.25 kA) ⤠3.8 kV (at 10 kA) ⤠4.2 kV (at 15 kA) ⤠5.4 kV (at 40 kA) Residual current IPE: ⤠100 µA DC ⤠540 µA AC Voltage protection level Up: ⤠4.5 kV Standby power consumption PC: ⤠150 mVA |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 (only when all terminal points are used) Ambient temperature (operation): -40°C ... 80°C Ambient temperature (storage/transport): -40°C ... 80°C Altitude: ⤠6000 m (amsl) Permissible humidity (operation): 5 % ... 95 % Shock (operation): 50g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) Vibration (operation): 5g (5 - 500 Hz/2.5 h/X, Y, Z) |
Standards and regulations | Standards/specifications: EN61643-31 IEC 61643-31 Note: 2019 2018 |
Mounting | Mounting type: DIN rail: 35 mm |
ECLASS | ECLASS-11.0: 27130805 ECLASS-13.0: 27171401 |
ETIM | ETIM 9.0: EC000381 |
UNSPSC | UNSPSC 21.0: 39121600 |