Industrial Automation

Mechatronics

Industrial Safety

Panel Components

Sensors and Systems of Vision

Pneumatics

Network Comunications

Automation Cables

Design Software

Access services

Enter your reserved area

Access services

Enter your reserved area

PHOENIX CONTACT 1104545
PHOENIX CONTACT 1104545
PHOENIX CONTACTNot available

AXL F MA MBUS 1H - Communication module

AxiolineF, M-Bus master, interface M-Bus, for the connection of M-Bus devices, transmission speed in the local bus:100 Mbps, degree of protection:IP20, including bus base module and AxiolineF connectors
Product Code: 1104545
Partner cod.: 1104545
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Download
Tecnichal data
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/70f8cf974520554e81de80f4005f2af3/-S204x204-FJPG
Width: 35 mm
Height: 126.1 mm
Depth: 54 mm
Note on dimensions: The depth applies when a TH35-7.5 DIN rail is used (in accordance with EN60715).
InterfacesOutput buffer: 1 kByte
Data bits: 8
Input buffer: 1 kByte
Stop bits: 1
AxiolineFlocal bus
Number of interfaces: 2
Connection method: Bus base module
Transmission speed: 100 Mbps
M-Bus
Connection method: Push-in connection
Transmission speed: 300bps ... 38,400bps (can be parameterized)
Transmission physics: Copper
System propertiesModule
Input address area: 20 Byte
Output address area: 20 Byte
Required parameter data: 1 Byte
Required configuration data: 7 Byte
Product propertiesType: block modular
Product type: I/O component
Product family: AxiolineF
Mounting position: any (no temperature derating)
Scope of delivery: including bus base module and AxiolineF connectors
Insulation characteristics
Overvoltage category: II (IEC 60664-1, EN60664-1)
Pollution degree: 2 (IEC 60664-1, EN60664-1)
Electrical propertiesPotentials: AxiolineF local bus supply (U
Supply voltage: 5 VDC (via bus base module)
Current draw: max. 75 mA
Power consumption: max. 350 mW
Potentials: Feed-in of supply voltage (U
Supply voltage: 24 VDC
Supply voltage range: 19.2 VDC ... 30 VDC (including all tolerances, including ripple)
Current draw: max. 410 mA
Power consumption: max. 6 W (depending on the number of devices (for unit loads, see the table below “Additional data”) on the M-Bus, of which20% is internal losses)
Protective circuit: Surge protection; electronic (35 V, 0.5 s)
Reverse polarity protection; parallel diode; with external 5A fuse
Electrical isolation/isolation of the voltage ranges
Test voltage: 5V supply of the local bus (UBus) / 24V supply (I/Os): 500 VAC, 50 Hz, 1 min.
Test voltage: 5V supply (logic) / M-Bus: 500 VAC, 50 Hz, 1 min.
Test voltage: 5V supply of the local bus (UBus) / functional ground: 500 VAC, 50 Hz, 1 min.
Test voltage: 24V supply (I/O) / M-Bus: 500 VAC, 50 Hz, 1 min.
Test voltage: 24V supply (I/O) / functional ground: 500 VAC, 50 Hz, 1 min.
Test voltage: M-Bus/functional ground: 500 VAC, 50 Hz, 1 min.
Connection dataConnection technology
Connection name: AxiolineF connector
Note on the connection method: Please observe the information provided on conductor cross sections in the “AxiolineF: system and installation” user manual.
Conductor connection
Connection method: Push-in connection
Conductor cross section rigid: 0.2 mm² ... 1.5 mm²
Conductor cross section flexible: 0.2 mm² ... 1.5 mm²
Conductor cross section AWG: 24 ... 16
Stripping length: 8 mm
AxiolineF connector
Connection method: Push-in connection
Note on the connection method: Please observe the information provided on conductor cross sections in the “AxiolineF: system and installation” user manual.
Conductor cross section, rigid: 0.2 mm² ... 1.5 mm²
Conductor cross section, flexible: 0.2 mm² ... 1.5 mm²
Conductor cross section AWG: 24 ... 16
Stripping length: 8 mm
Environmental and real-life conditionsAmbient conditions
Ambient temperature (operation): -25°C ... 60°C
Degree of protection: IP20
Air pressure (operation): 70 kPa ... 106 kPa (up to 3000m above sea level)
Air pressure (storage/transport): 70 kPa ... 106 kPa (up to 3000m above sea level)
Ambient temperature (storage/transport): -40°C ... 85°C
Permissible humidity (operation): 5 % ... 95 % (non-condensing)
Permissible humidity (storage/transport): 5 % ... 95 % (non-condensing)
Standards and regulationsProtection class: III (IEC 61140, EN61140, VDE0140-1)
MountingMounting type: DIN rail mounting
Mounting position: any (no temperature derating)
Technical Specs
ECLASSECLASS-11.0: 27242608
ECLASS-12.0: 27242608
ECLASS-13.0: 27242608
ETIMETIM 9.0: EC001604
UNSPSCUNSPSC 21.0: 32151600
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_01758.pdf

Data_sheet_00631.pdf

Manufacturer_declaration_01372.pdf

Manufacturer_declaration_02320.pdf

Manufacturer_declaration_05480.pdf

Manufacturer_declaration_06413.pdf

Package_slip_00750.pdf

Technical_drawing_08500.pdf