PHOENIX CONTACT 1111664
PHOENIX CONTACT 1111664
PHOENIX CONTACTNot available

TRIO-PS67/1AC/24DC/10/IPD - Power supply unit

Primary-switched power supply unit TRIO POWER, IPD panel feed-through with Push-in spring connection, Wall mounting, input:1-phase, output: 24 VDC / 10 A
Product Code: 1111664
Partner cod.: 1111664
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Download
Tecnichal data
Input dataAC operation
Supply system configuration: Star network (TN, TT, IT (PE))
Nominal input voltage range: 100 VAC ... 240 VAC
Input voltage range: 100 VAC ... 240 VAC ±10%
Switch-on voltage: > 75 VAC
Shut-down voltage: < 70 VAC
Electric strength, max.: ≤ 300 VAC 15 s
Typical national grid voltage: 120 VAC
230 VAC
Voltage type of supply voltage: AC/DC
Inrush current: ≤ 25 A (typical)
Inrush current integral (I2t): < 0.5 A2s
Inrush current limitation: typ. 25 A (after 1ms)
AC frequency range: 50 Hz ... 60 Hz ±10%
Frequency range (fN): 50 Hz ... 60 Hz ±10%
Mains buffering time: > 15 ms (120VAC)
> 15 ms (230 V AC)
Current consumption: 2.8 A (100VAC)
1.2 A (240VAC)
Nominal power consumption: 285 VA
Protective circuit: Transient surge protection; Varistor
Power factor (cos phi): > 0.93
Switch-on time: < 1 s
Input fuse: 6.3 A (internal (device protection))
Recommended breaker for input protection: 6 A ... 16 A (US/CAN: branch circuit protection <20A) (Characteristic B, C, D, K or comparable)
Discharge current to PE: < 3.5 mA
DC operation
Nominal input voltage range: 110 VDC ... 250 VDC
Input voltage range: 110 VDC ... 250 VDC ±10%
Switch-on voltage: ≥ 95 VDC
Shut-down voltage: < 95 VDC
Voltage type of supply voltage: AC/DC
Mains buffering time: > 15 ms (230 V AC)
Current consumption: 2.4 A (110VDC)
1.1 A (250VDC)
Output dataEfficiency: typ. 91 % (120VAC)
typ. 93 % (230 V AC)
Nominal output voltage: 24 VDC ±1%
Nominal output current (IN): 10 A
Dynamic Boost (IDyn.Boost): 15 A (5 s)
Derating: > 60°C ... 70°C (2.5%/K)
Feedback voltage resistance: ≤ 35 VDC
Protection against overvoltage at the output (OVP): ≤ 30 VDC
Control deviation: < 1 % (change in load, static 10 % ... 90 %)
< 3 % (Dynamic load change 10 % ... 90 %, 10 Hz)
< 0.1 % (change in input voltage ±10 %)
Residual ripple: ≤ 10 mVPP
Short-circuit-proof: yes
No-load proof: yes
Output power: 240 W
360 W
Maximum no-load power dissipation: < 10 W (120VAC)
< 6 W (230 V AC)
Power loss nominal load max.: < 22 W (120VAC)
< 17 W (230 V AC)
Rise time: ≤ 12 ms (UOUT (10 % ... 90 %))
Connection in parallel: yes, for redundancy and increased capacity
Connection in series: yes
Signal: DC OK
Maximum switching voltage: 30 V AC/DC
Continuous load current: 100 mA
Signal relay 13/14
Default: closed
Digital: 30 VAC 30 VDC 100 mA
Connection dataInput
Connection method: IPD panel feed-through with Push-in spring connection
Conductor cross section, rigid min.: 0.5 mm²
Conductor cross section, rigid max.: 2.5 mm²
Conductor cross section flexible min.: 0.5 mm²
Conductor cross section flexible max.: 2.5 mm²
Single conductor/terminal point, stranded, with ferrule, min.: 0.5 mm²
Single conductor/terminal point, stranded, with ferrule, max.: 2.5 mm²
Conductor cross section AWG max.: 14
Color-coded: gray
Type of locking: Clip locking
Number of positions: 3
Output
Connection method: IPD panel feed-through with Push-in spring connection
Conductor cross section, rigid min.: 0.5 mm²
Conductor cross section, rigid max.: 2.5 mm²
Conductor cross section flexible min.: 0.5 mm²
Conductor cross section flexible max.: 2.5 mm²
Single conductor/terminal point, stranded, with ferrule, min.: 0.5 mm²
Single conductor/terminal point, stranded, with ferrule, max.: 2.5 mm²
Conductor cross section AWG max.: 14
Color-coded: black
Type of locking: Clip locking
Number of positions: 3
SignalingTypes of signaling: LED
Floating signal contact
Status display: 2 x green LEDs
Signal output: LED status indicator
Signalization designation: AC OK
Status display: LED
Color: green
AC OK: ACIn>0.55xACN (ACN=90VAC)
Signal output: LED status indicator​
Signalization designation: DC OK
Status display: LED
Color: green
DC OK: UOUT > 0.9 x UN (UN = 24VDC)
Electrical propertiesNumber of phases: 1.00
Insulation voltage input/output: 3 kV AC (type test)
1.5 kV AC (routine test)
Product propertiesProduct type: Power supply
Product family: TRIO POWER
MTBF (IEC 61709, SN 29500): > 1200000 h (25°C)
> 700000 h (40°C)
> 300000 h (60°C)
Insulation characteristics
Protection class: I
Degree of pollution: 3
DimensionsItem dimensions
Width: 136 mm
Height: 292 mm
Depth: 53 mm
Drill hole
Diameter: 5.6 mm
Installation dimensions
Installation distance right/left: 20 mm / 20 mm
Installation distance top/bottom: 50 mm / 100 mm
MountingMounting type: Wall mounting
Assembly instructions: Alignable: 20mm horizontally, 50mm vertically above, 100mm vertically below
With protective coating: No
Material specificationsFlammability rating according to UL94 (housing / terminal blocks): V0
Housing material: Metal
Type of housing: Aluminum (AlMg3)
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP67
Ambient temperature (operation): -25°C ... 70°C (Derating>60°C: 2.5%/K)
Ambient temperature (storage/transport): -40°C ... 85°C
Ambient temperature (start-up type tested): -40°C
Maximum altitude: ≤ 4000 m (>2000m, Derating: 10%/1000m)
Climatic class: 4K26 (EN60721-3-4)
Max. permissible relative humidity (operation): ≤ 100 % (at 25°C, non-condensing)
Permissible humidity (operation): ≤ 100 % (at 25°C, non-condensing)
Shock: 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation): < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz ... 150 Hz, 4g, 90 min.
Standards and regulationsOvervoltage category
EN 61010-1: III(≤2000m)
II(≤4000m)
Electrical safety
Standard designation: Electrical safety
Standards/specifications: IEC 61010-1
Protective extra-low voltage
Standard designation: Protective extra-low voltage
Standards/specifications: IEC 61010-1 (SELV)
IEC 61010-2-201 (PELV)
Safe isolation
Standard designation: Safe isolation
Standards/specifications: IEC 61558-2-16
Low-voltage power supplies, DC output
Standard designation: Low-voltage power supplies, DC output
Standards/specifications: EN61204-3
Safety requirements for electrical equipment for measurement, control, and laboratory use
Standard designation: Safety requirements for electrical equipment for measurement, control, and laboratory use
Standards/specifications: IEC 61010-1
Limit values for harmonic currents
Standard designation: Limit values for harmonic currents
Standards/specifications: EN61000-3-2
Degrees of protection provided by enclosures (IP code)
Standard designation: Degrees of protection provided by enclosures (IP code)
Standards/specifications: EN/IEC 60529
ApprovalsUL
Identification: UL/C-UL Listed UL61010-1
UL​
Identification: UL/C-UL Listed UL61010-2-201
EMC dataLow Voltage Directive: Conformance with Low Voltage Directive 2014/35/EC
Interference emission: Interference emission in accordance with EN61000-6-3 (residential and commercial) and EN61000-6-4 (industrial)
Noise immunity: Immunity in accordance with EN61000-6-1 (residential), EN61000-6-2 (industrial)
Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU
Conducted noise emission: EN55016
EN61000-6-3 (Class B)
Noise emission: EN 55011 (EN 55022)
EN55016
EN61000-6-3 (Class B)
Harmonic currents
Standards/regulations: EN61000-3-2
EN61000-3-2 (Class A)
Electrostatic discharge
Standards/regulations: EN61000-4-2
Electrostatic discharge​
Contact discharge: 6 kV (Test Level 3)
Comments: Criterion A
Electromagnetic HF field
Standards/regulations: EN61000-4-3
Electromagnetic HF field​
Frequency range: 80 MHz ... 1 GHz
1 GHz ... 2 GHz
2 GHz ... 6 GHz
Test field strength: 10 V/m (Test Level 3)
Comments: Criterion A
Fast transients (burst)
Standards/regulations: EN61000-4-4
Fast transients (burst)​
Input: 4 kV (Test Level 3 - asymmetrical)
Output: 2 kV (Test Level 3 - asymmetrical)
Signal: 2 kV (Test Level 3 - asymmetrical)
Comments: Criterion A
Surge voltage load (surge)
Standards/regulations: EN61000-4-5
Input: 2 kV (Test Level 4 - symmetrical)
4 kV (Test Level 4 - asymmetrical)
Output: 1 kV (Test Level 3 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
Signal: 1 kV (Test Level 2 - asymmetrical)
Comments: Criterion A
Conducted interference
Standards/regulations: EN61000-4-6
Conducted interference​
Input/Output: asymmetrical
Frequency range: 0.15 MHz ... 80 MHz
Comments: Criterion A
Voltage: 10 V (Test Level 3)
Voltage dips
Standards/regulations: EN61000-4-11
Voltage: 230 VAC
Frequency: 50 Hz
Voltage dip: 70 %
40 %
0 %
Number of periods: 25 periods
10 periods
1 period
Comments: Criterion A
Emitted interference
Standards/regulations: EN61000-6-3
Radio interference voltage in acc. with EN 55011: EN55011 (EN55022) ClassB, area of application: Industry and residential
Emitted radio interference in acc. with EN 55011: EN 55011 (EN 55022) Class B, area of application: Industry and residential
Criteria
Criterion A: Normal operating behavior within the specified limits.
Criterion B: Temporary impairment to operational behavior that is corrected by the device itself.
Criterion C: Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements.
Technical Specs
ECLASSECLASS-11.0: 27040701
ECLASS-12.0: 27040701
ECLASS-13.0: 27040701
ETIMETIM 9.0: EC002540
UNSPSCUNSPSC 21.0: 39121000
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_00720.pdf

Data_sheet_00737.pdf

Manufacturer_declaration_03185.pdf

Manufacturer_declaration_04504.pdf

Manufacturer_declaration_06503.pdf

Package_slip_02465.pdf

Technical_drawing_08771.pdf

Various_00006.pdf