Industrial Automation

Mechatronics

Industrial Safety

Panel Components

Sensors and Systems of Vision

Pneumatics

Network Comunications

Automation Cables

Design Software

Access services

Enter your reserved area

Access services

Enter your reserved area

PHOENIX CONTACT 1125985
PHOENIX CONTACT 1125985
PHOENIX CONTACTNot available

PLC-RSC-120UC/21-21/SO46 - Relay Module

PLC-INTERFACE for protection against interference currents/voltages on the control side. Consisting of PLC-BSC-120UC/21-21/SO46 basic terminal block with screw connection and plug-in miniature relay with power contact up to 2x 8A, 2changeover contacts, 120VAC input voltage
Product Code: 1125985
Partner cod.: 1125985
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Description
Download
Tecnichal data
NotesNote on the material
General: Separating plate PLC-ATP must be installed for voltages larger than 250V (L1, L2, L3) between identical terminal blocks in adjacent modules. Potential bridging is then carried out with FBST 8-PLC... or FBST 500....
The PLC-ATP separating plate should be installed for safe isolation between adjacent modules
The PLC-ATP separating plate is required at the start and end of every PLC terminal strip.
The system installer must ensure the touch protection of the product (at voltages > 25 V AC/60 V DC). The product is a built-in device without protection against direct contact.
Product propertiesProduct type: Relay Module
Product family: PLC-INTERFACE
Application: Filter to prevent interference
Operating mode: 100% operating factor
Mechanical service life: 3x 107 cycles
Insulation characteristics
Insulation: Basic insulation
Insulation characteristics: Air clearances and creepage distances between the power circuits
Insulation: Basic insulation
Overvoltage category: III
Pollution degree: 3
Electrical propertiesMaximum power dissipation for nominal condition: 0.84 W
Test voltage (Winding/contact): 4 kVrms (50Hz, 1min., winding/contact)
Air clearances and creepage distances between the power circuits
Rated insulation voltage: 250 VAC
Rated surge voltage: 4 kV (Safe isolation, reinforced insulation, and 6 kV between input circuit and output contact current paths)
Input dataCoil side
Nominal input voltage UN: 120 VAC
110 VDC
Input voltage range: 94.8 VAC ... 168 VAC (20°C)
93.5 VDC ... 168.3 VDC (20°C)
Mains frequency: 50/60 Hz
Drive and function: monostable
Drive (polarity): polarized
Typical input current at UN: 6 mA (50Hz)
7 mA (60Hz)
Typical response time: 7 ms
Typical release time: 10 ms
Typical release voltage: 16 VAC
Coil voltage: 110 VDC
Protective circuit: Bridge rectifier
RC element
Status display: Yellow LED
Output dataSwitching
Contact switching type: 2 changeover contacts
Type of switch contact: Single contact
Contact material: AgNi
Maximum switching voltage: 250 V AC/DC
Minimum switching voltage: 5 V (10mA)
Limiting continuous current: 6 A
Maximum inrush current: 15 A (300ms)
Min. switching current: 10 mA (5 V)
Interrupting rating (ohmic load) max.: 144 W (24VDC)
96 W (48VDC)
60 W (60VDC)
44 W (110VDC)
57 W (220VDC)
1500 VA (250VAC)
Switching capacity min.: 0.12 W
Switching capacity: 2 A (at 24 V, DC13)
0.2 A (at 250 V, DC13)
3 A (at 24 V, AC15)
3 A (at 250 V, AC15)
Connection dataConnection method: Screw connection
Stripping length: 8 mm
Screw thread: M3
Conductor cross section rigid: 0.14 mm² ... 2.5 mm²
Conductor cross section flexible: 0.14 mm² ... 2.5 mm²
0.2 mm² ... 2.5 mm² (Single ferrule)
2x 0.5 mm² ... 1.5 mm² (TWIN ferrule)
Conductor cross section AWG: 26 ... 14
Tightening torque: 0.6 Nm ... 0.8 Nm
DimensionsWidth: 14 mm
Height: 80 mm
Depth: 94 mm
Environmental and real-life conditionsAmbient conditions
Degree of protection (Relay): RT III (Relay)
Degree of protection (Relay base): IP20 (Relay base)
Degree of protection (Installation location): IP54 (Installation location)
Ambient temperature (operation): -40°C ... 55°C
Ambient temperature (storage/transport): -40°C ... 85°C
Altitude: ≤ 2000 m
ApprovalsCE
Certificate: CE-compliant
UKCA
Certificate: UKCA-compliant
Shipbuilding approval
Certificate: TAE0000196
Corrosive gas test
Identification: ISA-S71.04. G3 Harsh Group
EN60068-2-60
DNV GL data
Temperature: D
Humidity: A
Vibration: B/C
EMC: B
Enclosure: Required protection according to the Rules shall be provided upon installation on board
EMC dataLow Voltage Directive: Conformance with Low Voltage Directive
Electromagnetic compatibility: Conformance with EMC directive
Standards and regulationsAir clearances and creepage distances between the power circuits
Standards/regulations: IEC 60947-5-1
MountingMounting type: DIN rail mounting
Assembly instructions: in rows with zero spacing
Mounting position: any
Technical Specs
ECLASSECLASS-11.0: 27371601
ECLASS-12.0: 27371601
ECLASS-13.0: 27371601
ETIMETIM 9.0: EC001437
UNSPSCUNSPSC 21.0: 39122300
Description
PLC-INTERFACE for protection against interference currents/voltages on the control side. Consisting of PLC-BSC-120UC/21-21/SO46 basic terminal block with screw connection and plug-in miniature relay with power contact up to 2x 8 A, 2 changeover contacts, 120 V AC input voltage
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Application_note_00006.pdf

Approvals_00240.pdf

Approvals_01560.pdf

Approvals_01561.pdf

Approvals_01883.pdf

Manufacturer_declaration_03393.pdf

Manufacturer_declaration_03394.pdf

Manufacturer_declaration_03599.pdf

Manufacturer_declaration_06551.pdf

Product_information_00033.pdf

Product_information_00078.pdf

Technical_drawing_09022.pdf