Industrial Automation
RFC 4072R - Controller


Product properties | Type: Stand-Alone Product type: Controller Product family: PLCnext Control Insulation characteristics Protection class: III (IEC 61140, ENÃ61140, VDEÃ0140-1) Pollution degree: 2 (when installed in a control cabinet or housing with IP54 degree of protection or higher) Display Diagnostics display: yes |
System properties | Processor: Intelî Coreâ⢠i5-6300U 2x 2.4 GHz (Standard) Flash memory: 100 Mbyte (internal flash memory) SD card from PhoenixÃContact (for external flash memory, see accessories) Retentive data storage: 2 Mbyte IEC 61131 runtime system Program memory: 16 Mbyte Data storage system: 32 Mbyte PROFINET Device function: PROFINET-Controller Number of supported devices: max. 256 Vendor ID: 00B0hex / 176dez Function Diagnostics display: yes Controller redundancy: yes Safety function: No Functionality Programming languages supported: Instruction list (IL) Symbolic flowchart (SFC) Ladder diagram (LD) Function block diagram (FBD) Structured text (ST) C++ C# Java Python Simulink System requirements Engineering tool: PLCnext Engineer Eclipse Visual Studio MATLABî Simulinkî Application interface: OPCÃUA OPCÃUAÃPub/Sub |
Electrical properties | Power consumption: typ. 25 W (Without fan module) max. 35 W (With fan module) Transmission medium: Copper FO Supply Supply voltage: 24 VÃDC Supply voltage range: 19.2 VÃDC ... 30 VÃDC (including ripple (3.6ÃVPP)) Power supply connection: Via COMBICON, max. conductor cross section 2.5 mm² Real-time clock Realtime clock: integrated (capacitive buffering) Description realtime clock: 1.73 s/day = 20Ãppm at 25ðC Potentials Protective circuit: Surge protection of the supply voltage; electronic Polarity reversal protection of the supply voltage; electronic |
Connection data | COMBICON connector Conductor cross section, rigid: 0.2 mm² ... 2.5 mm² Conductor cross section, flexible: 0.2 mm² ... 2.5 mm² Conductor cross section AWG: 24 ... 12 |
Interfaces | Web server: yes USB Number of interfaces: 1 Connection method: USB type A, socket Ethernet Bus system: RJ45 Number of interfaces: 4 Connection method: RJ45 jack Note on the connection method: Auto negotiation and auto crossing, auto polarity exchange Transmission speed: 10/100/1000 Mbps (LAN 1/LAN 2, half duplex or full duplex) 10/100 Mbps (LAN3.1/LAN3.2 (internally switched), half duplex or full duplex) |
Dimensions | External dimensions Width / Height / Depth: 122 mm / 182 mm / 173 mm (without fan module) 122 mm / 220 mm / 173 mm (With fan module) |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): 0°C ... 60°C up to 2000Ãm above mean sea level (recommended: aboveÃ50°C with fan module) 0°C ... 55°C 2000ÃmÃ...Ã3000Ãm above mean sea level (With fan module only) 0°C ... 50°C 3000ÃmÃ...Ã4000Ãm above mean sea level (With fan module only) Ambient temperature (storage/transport): -25°C ... 70°C Permissible humidity (operation): 10 % ... 95 % (non-condensing) Permissible humidity (storage/transport): 5 % ... 95 % (non-condensing) Shock (operation): 20g (in accordance with ENÃ60068-2-27/IEC 60068-2-27) Vibration (operation): 1g (in accordance with ENÃ60068-2-6/IEC 60068-2-6) Air pressure (operation): 60 kPa ... 108 kPa (up to 4000Ãm above mean sea level) Air pressure (storage/transport): 58 kPa ... 108 kPa (up to 4500Ãm above mean sea level) Resistance to gases that may endanger the functions, in acc. with DIN 40046-36, DIN 40046-37: Use of the device in these ambient conditions is prohibited. |
EMC data | Conformance with EMC directives: Immunity test in accordance with ENÃ61000-6-2/IEC 61000-6-2 Electrostatic discharge (ESD)ENÃ61000-4-2/IEC 61000-4-2 Criterion B, 6 kV contact discharge, 8 kV air discharge Immunity test in accordance with ENÃ61000-6-2/IEC 61000-6-2 Electromagnetic fieldsENÃ61000-4-3/IEC 61000-4-3 Criterion A, Field intensity: 10 V/m Immunity test in accordance with ENÃ61000-6-2/IEC 61000-6-2 Fast transients (burst)ENÃ61000-4-4/IEC 61000-4-4 Criterion B; Supply lines: 2 kV; Signal/data lines: 2 kV Immunity test in accordance with ENÃ61000-6-2/IEC 61000-6-2 Transient overvoltage (surge)ENÃ61000-4-5/IEC 61000-4-5 Criterion B, supply lines: 0.5ÃkV, signal/data cables: 1ÃkV Immunity test in accordance with ENÃ61000-6-2/IEC 61000-6-2 Conducted interferenceENÃ61000-4-6/IEC 61000-4-6 Criterion A, Test voltage 10 V Noise emission test in accordance with ENÃ61000-6-4/IEC 61000-6-4 Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU |
Mounting | Mounting type: DIN rail mounting |