Industrial Automation
QUINT-HP-UPS/120AC/2.5KVA/PT - Uninterruptible power supply


Notes | General Note on the battery: For proper operation of the UPS, at least 2 QUINT-HP-BAT/PB/48DC/7.0AH/PT (1133819) battery modules are required. For longer buffer times, multiples of 2 battery modules must always be connected to the UPS (2, 4, 6, 8, or 10). A maximum of 10 batteries can be connected to a single UPS. |
Input data | Input voltage: 100 V AC -10 % / +20 % 110 V AC -10 % / +20 % 120 V AC -10 % / +15 % 130 V AC -15 % / +10 % Voltage type of supply voltage: AC Frequency range (fN): 47.5 Hz ... 52.5 Hz 57 Hz ... 63 Hz Bypass fuse: 40 A T 250 V Permissible backup fuse: 40 A (Listed breaker) Current consumption: nom. 24 A (100 V AC) nom. 23.3 A (110 V AC) nom. 24 A (120 V AC) nom. 23.4 A (130 V AC) max. 34.4 A (100 V AC) max. 31.2 A (110 V AC) max. 35.4 A (120 V AC) max. 34.6 A (130 V AC) Rated short-time current carrying capacity Icw: 6 kA |
Output data | Classification according to IEC 62040-3: VFI-SS-111 Efficiency: > 94 % (100% load, battery charged) > 90 % (100% load, battery charged) Apparent power: 2500 VA Real power: 2250 W Power factor (cos phi): 0.9 Crest factor: 2.5 Switch-over time: 0 ms Connection in parallel: yes max. 3 Connection in series: no Overload capability Mains operation: 120 % ... 150 % (20 s / 5 s, then switch to bypass operation) Overload capability Battery operation: 120 % ... 150 % (20 s / 5 s, then shutdown) Overload capability Bypass mode: 120 % ... 150 % (for a sustained period / 20 s, then shutdown) Rated short-time current carrying capacity Icw: 6 kA Mains operation Output voltage: 100 V AC ñ2 % 110 V AC ñ2 % 120 V AC ñ2 % 130 V AC ñ2 % Form of output voltage: Pure sine Output current: nom. 20 A (100 V AC) nom. 18.2 A (110 V AC) nom. 20.8 A (120 V AC) nom. 19.2 A (130 V AC) Maximum no-load power dissipation: 9 W Power loss nominal load max.: < 120 W (100% load, battery charged) Nominal output frequency: 50 Hz 60 Hz ñ0.5 % (Output frequency tolerance) Electronic current limitation: > 2 x Output: Current nom. (> 200 ms) Battery operation Maximum no-load power dissipation: 9 W Power loss nominal load max.: 250 W (100% load, battery charged) Nominal output frequency: 50 Hz 60 Hz ñ0.5 % (Output frequency tolerance) Total harmonic distortion factor (THD): < 3 % (linear load) < 8 % (non-linear load) Electronic current limitation: > 2 x Output: Current nom. (> 200 ms) |
Energy storage | Input Input voltage: 48 V DC max. 60 V DC Input current: max. 40 A Nominal capacity range: 7 Ah ... 200 Ah Charging current: max. 10 A Output Short-circuit current: 650 A (< 1,5 ms) General Connection in parallel: yes max. 5 (per battery string) Connection in series: no IQ-Technology: yes Permissible backup fuse: 40 A Temperature sensor: yes |
Connection data | Input Position: 1.x Identification: 1.1 (L), 1.2 (N), 1.3 (ï⬵) Connection technology Position marking: 1.1 (L), 1.2 (N), 1.3 (ï⬵) Conductor connection Connection method: Push-in connection rigid: 4 mm² ... 6 mm² flexible: 4 mm² ... 6 mm² flexible with ferrule without plastic sleeve: 4 mm² flexible with ferrule with plastic sleeve: 4 mm² rigid (AWG): 10 Stripping length: 10 mm Output Position: 2.x Identification: 2.1 (L), 2.2 (N), 2.3 (ï⬵) Connection technologyââ¬Ã¢¹ Position marking: 2.1 (L), 2.2 (N), 2.3 (ï⬵) Conductor connectionââ¬Ã¢¹ Connection method: Push-in connection rigid: 4 mm² ... 6 mm² flexible: 4 mm² ... 6 mm² flexible with ferrule without plastic sleeve: 4 mm² flexible with ferrule with plastic sleeve: 4 mm² rigid (AWG): 10 Stripping length: 10 mm Outputââ¬Ã¢¹ Position: 2.x Identification: 2.4 (L'), 2.5 (N), 2.6 (ï⬵) Connection technologyââ¬Ã¢¹Ã¢Ã¢¬Ã¢¹ Position marking: 2.4 (L'), 2.5 (N), 2.6 (ï⬵) Conductor connectionââ¬Ã¢¹Ã¢Ã¢¬Ã¢¹ Connection method: Push-in connection rigid: 4 mm² ... 6 mm² flexible: 4 mm² ... 6 mm² flexible with ferrule without plastic sleeve: 4 mm² flexible with ferrule with plastic sleeve: 4 mm² rigid (AWG): 10 Stripping length: 15 mm Battery Position: 4.x Identification: 4.1, 4.2; 4.3, 4.4 Connection technologyââ¬Ã¢¹Ã¢Ã¢¬Ã¢¹Ã¢Ã¢¬Ã¢¹ Position marking: 4.1 (+), 4.2 (-), 4.3 (+), 4.4 (-) Conductor connectionââ¬Ã¢¹Ã¢Ã¢¬Ã¢¹Ã¢Ã¢¬Ã¢¹ Connection method: Push-in connection rigid: 6 mm² ... 16 mm² flexible: 6 mm² ... 16 mm² flexible with ferrule without plastic sleeve: 6 mm² ... 16 mm² flexible with ferrule with plastic sleeve: 6 mm² ... 16 mm² rigid (AWG): 8 ... 6 Stripping length: 18 mm Signal Position: 3.x Identification: 3.1 ... 3.9 Connection technologyââ¬Ã¢¹Ã¢Ã¢¬Ã¢¹Ã¢Ã¢¬Ã¢¹Ã¢Ã¢¬Ã¢¹ Position marking: 3.1 (Alarm), 3.2 (Bat.-Mode), 3.3 (Power Good), 3.4 (Ready), 3.5 (P>Pn), 3.6 (Service Required), 3.7 (Bat.-Start), 3.8 (Remote), 3.9 (SGnd) Conductor connectionââ¬Ã¢¹Ã¢Ã¢¬Ã¢¹Ã¢Ã¢¬Ã¢¹Ã¢Ã¢¬Ã¢¹ Connection method: Push-in connection rigid: 0.2 mm² ... 4 mm² flexible: 0.2 mm² ... 4 mm² flexible with ferrule without plastic sleeve: 0.2 mm² ... 2.5 mm² flexible with ferrule with plastic sleeve: 0.2 mm² ... 2.5 mm² rigid (AWG): 24 ... 12 Stripping length: 10 mm |
Interfaces | Interface: Battery module communication interface Parallel operation communication interface Number of interfaces: 1 2 Connection method: RJ45 Position: 5.x Locking: Locking clip Transmission physics: Twisted-Pair 4x2 |
Signaling | Signal input Bat.-Start Low signal: Connection to SGnd with < 2.7 ké High signal: Open (> 200 ké between Bat.-Start and SGnd) Signal input Remote Low signal: Connection to SGnd with < 2.7 ké High signal: Open (> 35 ké between Remote and SGnd) Signal output Alarm Position: 3.x Signalization designation: Alarm Position marking: 3.1 (Alarm) Switching output: Transistor output, active Output voltage: 24 V Continuous load current: ââ°¤ 20 mA Signal output Battery Mode Position: 3.x Signalization designation: Bat.-Mode Position marking: 3.2 (Bat.-Mode) Switching output: Transistor output, active Output voltage: 24 V Continuous load current: ââ°¤ 20 mA Signal output Power Good Position: 3.x Signalization designation: Power Good Position marking: 3.3 (Power Good) Switching output: Transistor output, active Output voltage: 24 V Continuous load current: ââ°¤ 20 mA Signal output Ready Position: 3.x Signalization designation: Ready Position marking: 3.4 (Ready) Switching output: Transistor output, active Output voltage: 24 V Continuous load current: ââ°¤ 20 mA Signal output P > P Position: 3.x Signalization designation: P>Pn Position marking: 3.5 (P>Pn) Switching output: Transistor output, active Output voltage: 24 V Continuous load current: ââ°¤ 20 mA Signal output Service Required Position: 3.x Signalization designation: Service Required Position marking: 3.6 (Service Required) Switching output: Transistor output, active Output voltage: 24 V Continuous load current: ââ°¤ 20 mA Signal ground SGnd Function: Signal ground Reference potential: For signal inputs and signal outputs |
Product properties | Product type: AC UPS Product family: QUINT AC UPS Data management status Article revision: 01 Insulation characteristics Protection class: I Overvoltage category: II Pollution degree: 3 |
Dimensions | Item dimensions Width: 188 mm Height: 240 mm Depth: 143 mm Drill hole Diameter: 5.5 mm Installation dimensions Installation distance right/left: 0 mm / 0 mm Installation distance top/bottom: 50 mm / 50 mm |
Mounting | Mounting type: Wall mounting |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -25 °C ... 60 °C (> 50 °C: 2,5 % / K) Ambient temperature (storage/transport): -40 °C ... 85 °C Maximum altitude: ââ°¤ 4000 m (> 1000 m: 3 % / 1000 m) Max. permissible relative humidity (operation): ââ°¤ 95 % Shock: 30g in each direction, according to IEC 60068-2-27 Vibration (operation): 5 Hz ... 100 Hz, 0.7g (EN 60068-2-6) |
Approvals | UL Identification: UL/C-UL Recognized UL 1778 |
EMC data | Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU Low Voltage Directive: Conformance with Low Voltage Directive 2014/35/EC Interference emission: Noise emission Noise immunity: Immunity Conducted noise emission: EN 62040-02 (Class C2) Electrostatic discharge Standards/regulations: EN 61000-4-2 Electrostatic dischargeââ¬Ã¢¹ Contact discharge: ñ 6 kV Discharge in air: ñ 8 kV Comments: Criterion A Electromagnetic HF field Standards/regulations: EN 61000-4-3 Electromagnetic HF fieldââ¬Ã¢¹ Frequency range: 80 MHz ... 6 GHz Test field strength: 10 V/m Comments: Criterion A Fast transients (burst) Standards/regulations: EN 61000-4-4 Fast transients (burst)ââ¬Ã¢¹ Input: ñ 2 kV Output: ñ 2 kV Signal: ñ 2 kV ñ 2 kV (Communication parallel operation, battery module) Comments: Criterion A Surge voltage load (surge) Standards/regulations: EN 61000-4-5 Surge voltage load (surge)ââ¬Ã¢¹ Signal: 1 kV (asymmetrical) Comments: Criterion B Input/Output: ñ 1 kV (symmetrical) ñ 2 kV (asymmetrical) Conducted interference Standards/regulations: EN 61000-4-6 Conducted interferenceââ¬Ã¢¹ Frequency range: 0.15 MHz ... 80 MHz Signal: 10 V (asymmetrical) Comments: Criterion A Power frequency magnetic field Standards/regulations: EN 61000-4-8 Frequency: 60 Hz Signal: 30 A/m Comments: Criterion A Harmonic and interharmonic components Standards/regulations: EN 61000-4-13 Harmonic and interharmonic componentsââ¬Ã¢¹ Comments: Criterion A Criteria Criterion A: Normal operating behavior within the specified limits. Criterion B: Temporary impairment to operational behavior that is corrected by the device itself. |