QUINT-HP-UPS/120AC/2.5KVA/PT - Uninterruptible power supply

QUINT AC UPS, IQ Technology, Wall mounting, input: 120 V AC, output: 120 V AC / 2500 VA. At least 2x 1133819 are required for operation.
Product Code: 1136813
Partner cod.: 1136813
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Description
Tecnichal data
NotesGeneral
Note on the battery: For proper operation of the UPS, at least 2 QUINT-HP-BAT/PB/48DC/7.0AH/PT (1133819) battery modules are required.
For longer buffer times, multiples of 2 battery modules must always be connected to the UPS (2, 4, 6, 8, or 10).
A maximum of 10 batteries can be connected to a single UPS.
Input dataInput voltage: 100 V AC -10 % / +20 %
110 V AC -10 % / +20 %
120 V AC -10 % / +15 %
130 V AC -15 % / +10 %
Voltage type of supply voltage: AC
Frequency range (fN): 47.5 Hz ... 52.5 Hz
57 Hz ... 63 Hz
Bypass fuse: 40 A T 250 V
Permissible backup fuse: 40 A (Listed breaker)
Current consumption: nom. 24 A (100 V AC)
nom. 23.3 A (110 V AC)
nom. 24 A (120 V AC)
nom. 23.4 A (130 V AC)
max. 34.4 A (100 V AC)
max. 31.2 A (110 V AC)
max. 35.4 A (120 V AC)
max. 34.6 A (130 V AC)
Rated short-time current carrying capacity Icw: 6 kA
Output dataClassification according to IEC 62040-3: VFI-SS-111
Efficiency: > 94 % (100% load, battery charged)
> 90 % (100% load, battery charged)
Apparent power: 2500 VA
Real power: 2250 W
Power factor (cos phi): 0.9
Crest factor: 2.5
Switch-over time: 0 ms
Connection in parallel: yes
max. 3
Connection in series: no
Overload capability Mains operation: 120 % ... 150 % (20 s / 5 s, then switch to bypass operation)
Overload capability Battery operation: 120 % ... 150 % (20 s / 5 s, then shutdown)
Overload capability Bypass mode: 120 % ... 150 % (for a sustained period / 20 s, then shutdown)
Rated short-time current carrying capacity Icw: 6 kA
Mains operation
Output voltage: 100 V AC ±2 %
110 V AC ±2 %
120 V AC ±2 %
130 V AC ±2 %
Form of output voltage: Pure sine
Output current: nom. 20 A (100 V AC)
nom. 18.2 A (110 V AC)
nom. 20.8 A (120 V AC)
nom. 19.2 A (130 V AC)
Maximum no-load power dissipation: 9 W
Power loss nominal load max.: < 120 W (100% load, battery charged)
Nominal output frequency: 50 Hz
60 Hz
±0.5 % (Output frequency tolerance)
Electronic current limitation: > 2 x Output: Current nom. (> 200 ms)
Battery operation
Maximum no-load power dissipation: 9 W
Power loss nominal load max.: 250 W (100% load, battery charged)
Nominal output frequency: 50 Hz
60 Hz
±0.5 % (Output frequency tolerance)
Total harmonic distortion factor (THD): < 3 % (linear load)
< 8 % (non-linear load)
Electronic current limitation: > 2 x Output: Current nom. (> 200 ms)
Energy storageInput
Input voltage: 48 V DC
max. 60 V DC
Input current: max. 40 A
Nominal capacity range: 7 Ah ... 200 Ah
Charging current: max. 10 A
Output
Short-circuit current: 650 A (< 1,5 ms)
General
Connection in parallel: yes
max. 5 (per battery string)
Connection in series: no
IQ-Technology: yes
Permissible backup fuse: 40 A
Temperature sensor: yes
Connection dataInput
Position: 1.x
Identification: 1.1 (L), 1.2 (N), 1.3 ()
Connection technology
Position marking: 1.1 (L), 1.2 (N), 1.3 ()
Conductor connection
Connection method: Push-in connection
rigid: 4 mm² ... 6 mm²
flexible: 4 mm² ... 6 mm²
flexible with ferrule without plastic sleeve: 4 mm²
flexible with ferrule with plastic sleeve: 4 mm²
rigid (AWG): 10
Stripping length: 10 mm
Output
Position: 2.x
Identification: 2.1 (L), 2.2 (N), 2.3 ()
Connection technologyâۉ€¹
Position marking: 2.1 (L), 2.2 (N), 2.3 ()
Conductor connectionâۉ€¹
Connection method: Push-in connection
rigid: 4 mm² ... 6 mm²
flexible: 4 mm² ... 6 mm²
flexible with ferrule without plastic sleeve: 4 mm²
flexible with ferrule with plastic sleeve: 4 mm²
rigid (AWG): 10
Stripping length: 10 mm
Outputâۉ€¹
Position: 2.x
Identification: 2.4 (L'), 2.5 (N), 2.6 ()
Connection technologyâۉ€¹Ãƒ¢Ã¢‚¬Ã¢€¹
Position marking: 2.4 (L'), 2.5 (N), 2.6 ()
Conductor connectionâۉ€¹Ãƒ¢Ã¢‚¬Ã¢€¹
Connection method: Push-in connection
rigid: 4 mm² ... 6 mm²
flexible: 4 mm² ... 6 mm²
flexible with ferrule without plastic sleeve: 4 mm²
flexible with ferrule with plastic sleeve: 4 mm²
rigid (AWG): 10
Stripping length: 15 mm
Battery
Position: 4.x
Identification: 4.1, 4.2; 4.3, 4.4
Connection technologyâۉ€¹Ãƒ¢Ã¢‚¬Ã¢€¹Ãƒ¢Ã¢‚¬Ã¢€¹
Position marking: 4.1 (+), 4.2 (-), 4.3 (+), 4.4 (-)
Conductor connectionâۉ€¹Ãƒ¢Ã¢‚¬Ã¢€¹Ãƒ¢Ã¢‚¬Ã¢€¹
Connection method: Push-in connection
rigid: 6 mm² ... 16 mm²
flexible: 6 mm² ... 16 mm²
flexible with ferrule without plastic sleeve: 6 mm² ... 16 mm²
flexible with ferrule with plastic sleeve: 6 mm² ... 16 mm²
rigid (AWG): 8 ... 6
Stripping length: 18 mm
Signal
Position: 3.x
Identification: 3.1 ... 3.9
Connection technologyâۉ€¹Ãƒ¢Ã¢‚¬Ã¢€¹Ãƒ¢Ã¢‚¬Ã¢€¹Ãƒ¢Ã¢‚¬Ã¢€¹
Position marking: 3.1 (Alarm), 3.2 (Bat.-Mode), 3.3 (Power Good), 3.4 (Ready), 3.5 (P>Pn), 3.6 (Service Required), 3.7 (Bat.-Start), 3.8 (Remote), 3.9 (SGnd)
Conductor connectionâۉ€¹Ãƒ¢Ã¢‚¬Ã¢€¹Ãƒ¢Ã¢‚¬Ã¢€¹Ãƒ¢Ã¢‚¬Ã¢€¹
Connection method: Push-in connection
rigid: 0.2 mm² ... 4 mm²
flexible: 0.2 mm² ... 4 mm²
flexible with ferrule without plastic sleeve: 0.2 mm² ... 2.5 mm²
flexible with ferrule with plastic sleeve: 0.2 mm² ... 2.5 mm²
rigid (AWG): 24 ... 12
Stripping length: 10 mm
InterfacesInterface: Battery module communication interface
Parallel operation communication interface
Number of interfaces: 1
2
Connection method: RJ45
Position: 5.x
Locking: Locking clip
Transmission physics: Twisted-Pair 4x2
SignalingSignal input Bat.-Start
Low signal: Connection to SGnd with < 2.7 kΩ
High signal: Open (> 200 kΩ between Bat.-Start and SGnd)
Signal input Remote
Low signal: Connection to SGnd with < 2.7 kΩ
High signal: Open (> 35 kΩ between Remote and SGnd)
Signal output Alarm
Position: 3.x
Signalization designation: Alarm
Position marking: 3.1 (Alarm)
Switching output: Transistor output, active
Output voltage: 24 V
Continuous load current: ≤ 20 mA
Signal output Battery Mode
Position: 3.x
Signalization designation: Bat.-Mode
Position marking: 3.2 (Bat.-Mode)
Switching output: Transistor output, active
Output voltage: 24 V
Continuous load current: ≤ 20 mA
Signal output Power Good
Position: 3.x
Signalization designation: Power Good
Position marking: 3.3 (Power Good)
Switching output: Transistor output, active
Output voltage: 24 V
Continuous load current: ≤ 20 mA
Signal output Ready
Position: 3.x
Signalization designation: Ready
Position marking: 3.4 (Ready)
Switching output: Transistor output, active
Output voltage: 24 V
Continuous load current: ≤ 20 mA
Signal output P > P
Position: 3.x
Signalization designation: P>Pn
Position marking: 3.5 (P>Pn)
Switching output: Transistor output, active
Output voltage: 24 V
Continuous load current: ≤ 20 mA
Signal output Service Required
Position: 3.x
Signalization designation: Service Required
Position marking: 3.6 (Service Required)
Switching output: Transistor output, active
Output voltage: 24 V
Continuous load current: ≤ 20 mA
Signal ground SGnd
Function: Signal ground
Reference potential: For signal inputs and signal outputs
Product propertiesProduct type: AC UPS
Product family: QUINT AC UPS
Data management status
Article revision: 01
Insulation characteristics
Protection class: I
Overvoltage category: II
Pollution degree: 3
DimensionsItem dimensions
Width: 188 mm
Height: 240 mm
Depth: 143 mm
Drill hole
Diameter: 5.5 mm
Installation dimensions
Installation distance right/left: 0 mm / 0 mm
Installation distance top/bottom: 50 mm / 50 mm
MountingMounting type: Wall mounting
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -25 °C ... 60 °C (> 50 °C: 2,5 % / K)
Ambient temperature (storage/transport): -40 °C ... 85 °C
Maximum altitude: ≤ 4000 m (> 1000 m: 3 % / 1000 m)
Max. permissible relative humidity (operation): ≤ 95 %
Shock: 30g in each direction, according to IEC 60068-2-27
Vibration (operation): 5 Hz ... 100 Hz, 0.7g (EN 60068-2-6)
ApprovalsUL
Identification: UL/C-UL Recognized UL 1778
EMC dataElectromagnetic compatibility: Conformance with EMC Directive 2014/30/EU
Low Voltage Directive: Conformance with Low Voltage Directive 2014/35/EC
Interference emission: Noise emission
Noise immunity: Immunity
Conducted noise emission: EN 62040-02 (Class C2)
Electrostatic discharge
Standards/regulations: EN 61000-4-2
Electrostatic dischargeâۉ€¹
Contact discharge: ± 6 kV
Discharge in air: ± 8 kV
Comments: Criterion A
Electromagnetic HF field
Standards/regulations: EN 61000-4-3
Electromagnetic HF fieldâۉ€¹
Frequency range: 80 MHz ... 6 GHz
Test field strength: 10 V/m
Comments: Criterion A
Fast transients (burst)
Standards/regulations: EN 61000-4-4
Fast transients (burst)âۉ€¹
Input: ± 2 kV
Output: ± 2 kV
Signal: ± 2 kV
± 2 kV (Communication parallel operation, battery module)
Comments: Criterion A
Surge voltage load (surge)
Standards/regulations: EN 61000-4-5
Surge voltage load (surge)âۉ€¹
Signal: 1 kV (asymmetrical)
Comments: Criterion B
Input/Output: ± 1 kV (symmetrical)
± 2 kV (asymmetrical)
Conducted interference
Standards/regulations: EN 61000-4-6
Conducted interferenceâۉ€¹
Frequency range: 0.15 MHz ... 80 MHz
Signal: 10 V (asymmetrical)
Comments: Criterion A
Power frequency magnetic field
Standards/regulations: EN 61000-4-8
Frequency: 60 Hz
Signal: 30 A/m
Comments: Criterion A
Harmonic and interharmonic components
Standards/regulations: EN 61000-4-13
Harmonic and interharmonic componentsâۉ€¹
Comments: Criterion A
Criteria
Criterion A: Normal operating behavior within the specified limits.
Criterion B: Temporary impairment to operational behavior that is corrected by the device itself.
Description
QUINT-HP-UPS/120AC/2.5KVA/PT Gruppo cont.