FA MCR-HT-1TS-I-OLP - Head-mounted transducer

Output loop-powered head transmitter for transmitting RTD and TC sensor signals, as well as from resistance and voltage sensors via 4mA...20mA. HART, Standard configuration, Screw connection
Product Code: 1145210
Partner cod.: 1145210
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Download
Tecnichal data
Product propertiesProduct type: Temperature transmitter
Product family: Field Analog
No. of channels: 1
Configuration: Software
HART
Insulation characteristics
Overvoltage category: II
Pollution degree: 2
Electrical propertiesNo. of channels: 1
Step response (0–99%): 1 s (TC)
1 s (RTD)
Electrical isolation Input/output
Test voltage: 2 kV AC (50Hz, 60s)
Supply
Supply voltage range: loop-powered, no external supply necessary
10 VDC ... 36 VDC (Standard)
Input dataMeasurement
Number of inputs: 1
Input voltage range: -20 mV ... 100 mV (Minimum measuring span: 5mV)
Sensor types (RTD) that can be used: Pt, Ni, Cu sensors: 2, 3, 4-wire
Sensor types that can be used (TC): A, B, C, D, E, J, K, L, N, R, S, T, U
Temperature measuring range: -250°C ... 2500°C (Range depending on the sensor type)
≥ 10 K (RTD)
≥ 50 K (TC)
Linear resistance measuring range: 10 Ω ... 2000 Ω (Minimum measuring span: 10Ω)
Output dataSignal: Current
Current output signal: 4 mA ... 20 mA (HART)
20 mA ... 4 mA (HART)
Max. current output signal: 23 mA
Load: (UL - 10V) / 0.023A
HART coding: FSK ± 0.5mA
HART version: 7
Transmission speed: 1200 Baud
Mains frequency filter: 50/60 Hz
Communication resistance: ≥ 250 Ω
Switch-on delay:  7 s (HART)
 7 s (Measured value)
Connection dataConnection method: Screw connection
Stripping length: 8 mm
Screw thread: M3
Conductor cross section rigid: 0.2 mm² ... 2.5 mm²
Conductor cross section flexible: 0.2 mm² ... 2.5 mm²
Conductor cross section AWG: 24 ... 14
Tightening torque: 0.5 Nm
Ex dataEx installation (EPL): Gc
Div.2
InterfacesData communication (bypass)
Protocols supported: HART
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP00 (upon installation in field housing IP66/67, NEMA 4X)
Ambient temperature (operation): -40°C ... 85°C
Ambient temperature (storage/transport): -50°C ... 100°C
Altitude: ≤ 4000 m (Above sea level)
Climatic class: C1
Permissible humidity (operation): 5 % ... 95 % (condensation permitted)
ApprovalsCE
Certificate: CE-compliant
ATEX
Identification:  II 3 G Ex ec IIC T6
Certificate: PxCIF20ATEX1145192U
CSA
Identification: Ex ec IIC T6...T4
MountingMounting type: Installation
DIN rail mounting
Assembly instructions: Installation in connecting head B in accordance with DINEN50446
Technical Specs
ECLASSECLASS-11.0: 27210129
ECLASS-12.0: 27210129
ECLASS-13.0: 27210129
ETIMETIM 9.0: EC002919