PHOENIX CONTACT 1151618
PHOENIX CONTACT 1151618
PHOENIX CONTACTNot available

ELR H51-IES-24DC500AC-3-IFS - Hybrid motor starter

Hybrid motor starter; functions: start motor, reverse motor, motor protection, emergency stop, network capable, short-circuit protection; input: 24 VDC; output: 3~, 500 VAC, 3 A; connection method: screw and Push-in connection; connection to the Interface system
Product Code: 1151618
Partner cod.: 1151618
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Download
Tecnichal data
Product propertiesProduct type: Hybrid motor starters
Product family: CONTACTRON
Operating mode: 100% operating factor
Insulation characteristics: Standards/regulations
Pollution degree: 2
Electrical propertiesNumber of phases: 3
Motor starter type: Reversing starter
Maximum power dissipation for nominal condition: 2.5 W
Switching frequency: ≤ 2 Hz (Load-dependent)
Maximum power dissipation: 4.1 W
Minimum power dissipation: 0.88 W
Coordination type: 1
Supply
Rated control circuit supply voltage US: 24 VDC
Control supply voltage range: 19.2 VDC ... 30 VDC
Rated control supply current IS: 60 mA
Protective circuit: Surge protection
Reverse polarity protection; Parallel polarity protection diode
Insulation characteristics
Rated insulation voltage: 550 V
Rated surge voltage: 6 kV
Overvoltage category: III
Degree of pollution: 2
Insulation characteristics between control input voltage and control supply voltage to main circuit: Safe isolation (IEC 60947-1)
Emergency tripping
Operate threshold: > 33 A
Response time: < 0.5 s
Input dataControl
Input name: Enable input
Note: The enable input is compatible with signals with blanking (semiconductor output signals with test pulse with max. 3ms duration),
unblanking pulses of max. 4ms are tolerated without adversely affecting the safety function.
Rated actuating voltage UC: 24 VDC
Triggering voltage range: 19.2 VDC ... 30 VDC
Rated actuating current IC: 7 mA
Switching threshold: 9.6 V (“0” signal)
19.2 V (“1” signal)
Switching level: < 5 VDC (For EMERGENCY STOP)
Typical turn-off time: < 30 ms
Protective circuit: Reverse polarity protection
Output dataAC output
Rated operating voltage Ue: 500 VAC
Operating voltage range: 42 VAC ... 550 VAC
Rated operating current Ie: 3 A (AC-51)
3 A (AC-53a)
Mains frequency: 50/60 Hz
Load current range: 180 mA ... 3 A (see to derating)
Trigger characteristic in acc. with IEC 60947-4-2: Class 10
Cooling time: 20 min. (for auto reset)
Leakage current: 0 mA
Protective circuit: Surge protection; Varistor
Connection dataControl circuits
Connection method: Push-in connection
Stripping length: 10 mm
Conductor cross section rigid: 0.2 mm² ... 2.5 mm²
Conductor cross section flexible: 0.2 mm² ... 2.5 mm²
Conductor cross section AWG: 24 ... 14
Load circuit
Connection method: Screw connection
Stripping length: 8 mm
Screw thread: M3
Conductor cross section rigid: 0.2 mm² ... 2.5 mm²
Conductor cross section flexible: 0.2 mm² ... 2.5 mm²
Conductor cross section AWG: 24 ... 14
Tightening torque: 0.5 Nm ... 0.6 Nm
5 lbf-in. ... 7 lbf-in.
SignalingStatus display: Yellow LED
Operating voltage display: Green LED
Error indication: Red LED
DimensionsWidth: 22.5 mm
Height: 160 mm
Depth: 114.5 mm
Material specificationsFlammability rating according to UL 94: V0 (Housing)
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -5°C ... 60°C (observe derating)
Ambient temperature (storage/transport): -40°C ... 80°C
Altitude: ≤ 2000 m
ApprovalsUKCA
Certificate: UKCA-compliant
Category (ISO13849)
Identification: ≤3
Note: Safe shutdown
UL approval
Certificate: NLDX.E228652
NRNT.E172140
Safety Integrity Level (SIL, IEC 61508)
Identification: ≤3
Note: Safe shutdown
Performance Level (ISO13849)
Identification: e
Note: Safe shutdown
UL data
SCCR: 100 kA (480 V AC (fuse: 30 A class CC/30 A class J (high fault)))
5 kA (480 V AC (fuse: 20 A RK5 (standard fault)))
FLA: 3 A (480VAC)
Group installation: 20 A (class RK5, SCCR 5kA (480 V AC), #24 - 14 AWG max. solid and stranded)
30 A (class CC or J, SCCR 100kA (480 V AC), #24 - 14 AWG max, solid and stranded)
Category code: NLDX / NRNT
Horsepower ratings: 0.5 hp (120VAC/208VAC)
1.5 hp (277VAC/480VAC)
Standards and regulationsStandards/regulations
Standards/regulations: IEC 60947-1
EN60947-4-2
IEC 61508
ISO13849-1
MountingAssembly instructions: alignable, for spacing see derating
Mounting position: vertical (horizontal DIN rail, motor output below)
Technical Specs
ECLASSECLASS-11.0: 27370905
ECLASS-13.0: 27370905
ECLASS-12.0: 27370905
ETIMETIM 9.0: EC001037
UNSPSCUNSPSC 21.0: 25173900
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_00051.pdf

Approvals_00052.pdf

Data_sheet_00857.pdf

Manual_00005.pdf

Manufacturer_declaration_01404.pdf

Manufacturer_declaration_02295.pdf

Manufacturer_declaration_06604.pdf

Package_slip_00967.pdf

Technical_drawing_09440.pdf