Industrial Automation
AXC F XT SPLC 1000 - PLC extension module


Dimensions | Width: 45 mm Height: 126.93 mm Depth: 75 mm Note on dimensions: The depth applies when a THÃ35-7.5 DIN rail is used (in accordance with ENÃ60715). External dimensions Width / Height / Depth: 45 mm / 126.93 mm / 75 mm (The depth applies when a THÃ35-7.5 DIN rail is used (in accordance with ENÃ60715).) |
Notes | General: If the SPLC-1000 is operated with AXCÃFÃ2152, the AXC BSÃL 2 bus base module must be used. |
Interfaces | Web server: No |
System properties | Processor: Armî Cortexî-M4, 180 MHz (CPU1) Armî Cortexî-M4, 100 MHz (CPU2) Function Diagnostics display: No Controller redundancy: No Safety function: yes System requirements Engineering tool: PLCnext Engineer |
Product properties | Type: modular Product type: I/O component Product family: PLCnext Control Extension Insulation characteristics Protection class: III (IEC 61140, ENÃ61140, VDEÃ0140-1) Display Diagnostics display: No |
Electrical properties | Supply Supply voltage: 24 VÃDC Supply voltage range: 19.2 VÃDC ... 30 VÃDC (including all tolerances, including ripple) Max. current consumption: 100 mA Typical current consumption: 80 mA Potentials: Supply of the logic voltage U Supply voltage: 24 VÃDC Supply voltage range: 19.2 VÃDC ... 30 VÃDC (including all tolerances, including ripple) Current draw: max. 100 mA typ. 80 mA Protective circuit: Reverse polarity protection; Polarity protection diode Transient protection; Suppressor diode |
Connection data | Connection technology Connection name: AxiolineÃF connector Conductor connection Connection method: Push-in connection Conductor cross section rigid: 0.2 mm² ... 1.5 mm² Conductor cross section flexible: 0.2 mm² ... 1.5 mm² Conductor cross section AWG: 24 ... 16 Stripping length: 8 mm AxiolineÃF connector Connection method: Push-in connection Conductor cross section, rigid: 0.2 mm² ... 1.5 mm² Conductor cross section, flexible: 0.2 mm² ... 1.5 mm² Conductor cross section AWG: 24 ... 16 Stripping length: 8 mm |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -25°C ... 60°C up to 2000Ãm above mean sea level -25°C ... 55°C up to 3000Ãm above mean sea level -25°C ... 50°C up to 4000Ãm above mean sea level Ambient temperature (storage/transport): -40°C ... 85°C Permissible humidity (operation): 5 % ... 95 % (according to DINÃENÃ61131-2) Permissible humidity (storage/transport): 5 % ... 95 % (according to DINÃENÃ61131-2) Shock (operation): 30g (in accordance with ENÃ60068-2-27/IEC 60068-2-27) Shock (storage/transport): 30g (in accordance with ENÃ60068-2-27/IEC 60068-2-27) Vibration (operation): 5g (in accordance with ENÃ60068-2-6/IEC 60068-2-6) Vibration (storage/transport): 5g (in accordance with ENÃ60068-2-6/IEC 60068-2-6) Air pressure (operation): 70 kPa ... 106 kPa (up to 3000Ãm above sea level) Air pressure (storage/transport): 58 kPa ... 106 kPa (up to 4500Ãm above mean sea level) Resistance to gases that may endanger the functions, in acc. with DIN 40046-36, DIN 40046-37: Use of the device in these ambient conditions is prohibited. |
Approvals | ATEX Identification: ïà II 3 G Ex ec IIC T4 Gc Certificate: ULÃ21ÃATEXÃ2651X IECEx Identification: Ex ec IIC T4 Gc Certificate: IECExÃULDÃ21.0029X UL Ex, USA / Canada Identification: Class I, Zone 2, AEx ec IIC T4, Ex ec IIC T4 Gc X Class I, Div. 2 Groups A, B, C, D T4 Certificate: E366272 UL, USA/Canada Identification: cULus Certificate: E238705 Industrial Cyber Security Identification: IndustrialÃITÃSecurity, IACSÃComponent Certificate: IITS2Ã029429Ã0027 Note: Configuration: SecurityÃProfileÃactive |
Mounting | Mounting type: DIN rail mounting Connection method: Push-in connection |
Description other products