Industrial Automation
AXL SE RS232 - Communication module
![](https://www.technologybsa.com/wp-content/uploads/2023/08/copia.png)
![](https://www.technologybsa.com/wp-content/uploads/2023/08/copia.png)
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/9e6e964f367bbe4db818e0ffaa606273/-S204x204-FJPG Width: 14.9 mm Height: 62.2 mm Depth: 62 mm |
Interfaces | SmartElement interface Number of interfaces: 1 Connection method: Card edge connector Transmission speed: See system in which you use the SmartElement. Start time until ready to operate: < 500 ms RS-232 Number of interfaces: 1 Connection method: Push-in connection Note on the connection method: Use shielded cables. Connect both ends of the shield. Transmission speed: 100bps ... 230400bps (can be parameterized) Transmission physics: Copper Protocols supported: Transparent Data bits: 7 or 8 Stop bits: 1 or 2 Input buffer: 4 kByte Output buffer: 1 kByte |
System properties | Module ID code (hex): none Process data channel: 160 bit Input address area: 20 Byte Output address area: 20 Byte Required parameter data: 11 Byte Required configuration data: 7 Byte |
Product properties | Type: modular Product type: I/O component Product family: Axioline SmartElements Mounting position: See the system in which the SmartElement is used. Insulation characteristics Overvoltage category: II (IEC 60664-1, EN60664-1) Pollution degree: 2 (IEC 60664-1, EN60664-1) |
Electrical properties | Maximum power dissipation for nominal condition: 174 mW Potentials: Communications power supply of the Smart Elements (U Supply voltage: using card edge connectors Potentials: I/O supply (U Supply voltage: 24 VDC (using card edge connectors) Supply voltage range: 19.2 VDC ... 30 VDC (including all tolerances, including ripple) Current draw: max. 9 mA typ. 7 mA Current consumption: min. 6 mA Power consumption: max. 174 mW min. 154 mW Protective circuit: Surge protection; See the system in which the SmartElement is used. Reverse polarity protection; Polarity protection diode Electrical isolation/isolation of the voltage ranges Test voltage: Communications supply / 24 V supply (I/O): 500 VAC, 50 Hz, 1 min. Test voltage: Logic supply / RS-232 interface: 500 VAC, 50 Hz, 1 min. Test voltage: Communications supply / functional ground: 500 VAC, 50 Hz, 1 min. Test voltage: 24 V supply (I/O) / RS-232 interface: 500 VAC, 50 Hz, 1 min. Test voltage: 24V supply (I/O) / functional ground: 500 VAC, 50 Hz, 1 min. Test voltage: RS-232 interface/functional ground: 500 VAC, 50 Hz, 1 min. |
Connection data | Connection technology Connection name: I/O Note on the connection method: Please observe the information provided on conductor cross sections in the âAxiolineSmartElementsâ user manual. Conductor connection Connection method: Push-in connection Conductor cross section rigid: 0.25 mm² ... 1.5 mm² Conductor cross section flexible: 0.25 mm² ... 1.5 mm² Conductor cross section AWG: 24 ... 16 Conductor cross section flexible, with ferrule without plastic sleeve: 0.25 mm² ... 1.5 mm² Conductor cross section, flexible, with ferrule, with plastic sleeve: 0.25 mm² ... 1.5 mm² Stripping length: 8 mm I/O Connection method: Push-in connection Note on the connection method: Please observe the information provided on conductor cross sections in the âAxiolineSmartElementsâ user manual. Conductor cross section, rigid: 0.25 mm² ... 1.5 mm² Conductor cross section, flexible: 0.25 mm² ... 1.5 mm² Conductor cross section AWG: 24 ... 16 Conductor cross section, flexible, with ferrule, with plastic sleeve: 0.25 mm² ... 1.5 mm² Conductor cross section flexible, with ferrule without plastic sleeve: 0.25 mm² ... 1.5 mm² Stripping length: 8 mm |
Environmental and real-life conditions | Ambient conditions Ambient temperature (operation): -25°C ... 60°C Degree of protection: IP20 Air pressure (operation): 70 kPa ... 106 kPa (up to 3000m above sea level) Air pressure (storage/transport): 70 kPa ... 106 kPa (up to 3000m above sea level) Ambient temperature (storage/transport): -40°C ... 85°C Permissible humidity (operation): 5 % ... 95 % (non-condensing) Permissible humidity (storage/transport): 5 % ... 95 % (non-condensing) |
Standards and regulations | Protection class: III (IEC 61140, EN61140, VDE0140-1) |
Mounting | Mounting type: Smart Element slot Mounting position: See the system in which the SmartElement is used. |
ECLASS | ECLASS-11.0: 27242608 ECLASS-12.0: 27242608 ECLASS-13.0: 27242608 |
ETIM | ETIM 9.0: EC001604 |
UNSPSC | UNSPSC 21.0: 32151600 |
Description other products