Industrial Automation
AXL SE UTH4 EF - Temperature module


Dimensions | Dimensional drawing: https://caas.production.phoenixcontact.coremedia.cloud/caas/v1/stable/media/22530/full/b250?format=jpg Width: 14.9 mm Height: 62.2 mm Depth: 62 mm |
Notes | Utilization restriction EMC note: EMC: class A product, see manufacturer's declaration in the download area |
Interfaces | SmartÃElement interface Number of interfaces: 1 Connection method: Card edge connector Transmission speed: See system in which you use the SmartÃElement. Start time until ready to operate: < 500 ms |
System properties | Module ID code (hex): none Process data channel: 80 bit Input address area: 10 Byte Output address area: 10 Byte Required parameter data: 21 Byte Required configuration data: 6 Byte |
Input data | Analog Input name: Analog inputs Description of the input: Inputs for thermocouples or linear voltage Number of inputs: 4 (Inputs for thermocouples or linear voltage) Connection method: Push-in connection Connection technology: 2-conductor (shielded, twisted pair) Sensor types that can be used (TC): B, C, E, J, K, L, N, R, S, T, U, W, HK, mV input Measured value representation: 16 bits (15 bits + sign bit) Input filter time: 40 ms 60 ms 100 ms 120 ms (adjustable) Protective circuit: Surge protection Transient protection Analogââ¬Ã¢¹ Input name: External cold junction (can also be used as an additional Pt 100 sensor input) Number of inputs: 1 Connection method: Push-in connection Connection technology: 4-conductor Sensor types (RTD) that can be used: Pt 100 Input filter time: 120 ms |
Product properties | Type: modular Product type: I/O component Product family: Axioline SmartÃElements Mounting position: See the system in which the SmartÃElement is used. Insulation characteristics Overvoltage category: II (IEC 60664-1, ENÃ60664-1) Pollution degree: 2 (IEC 60664-1, ENÃ60664-1) |
Electrical properties | Potentials: Communications power supply of the Smart Elements (U Supply voltage: using card edge connectors Potentials: I/O supply (U Supply voltage: 24 VÃDC (using card edge connectors) Supply voltage range: 19.2 VÃDC ... 30 VÃDC (including all tolerances, including ripple) Current draw: max. 28 mA typ. 22 mA Current consumption: min. 16 mA (without connected peripherals) Power consumption: max. 0.67 W min. 0.38 W (without connected peripherals) Protective circuit: Surge protection; See the system in which the SmartÃElement is used. Reverse polarity protection; Polarity protection diode Electrical isolation/isolation of the voltage ranges Test voltage: Communications supply / 24 V supply (I/O): 500 VÃAC, 50 Hz, 1 min. Test voltage: Communications supply / functional ground: 500 VÃAC, 50 Hz, 1 min. Test voltage: 24ÃV supply (I/O) / functional ground: 500 VÃAC, 50 Hz, 1 min. |
Connection data | Connection technology Connection name: I/O Note on the connection method: Please observe the information provided on conductor cross sections in the ââ¬Ã AxiolineÃSmartÃElementsâ⬠user manual. Conductor connection Connection method: Push-in connection Conductor cross section rigid: 0.25 mm² ... 1.5 mm² Conductor cross section flexible: 0.25 mm² ... 1.5 mm² Conductor cross section AWG: 24 ... 16 Conductor cross section flexible, with ferrule without plastic sleeve: 0.25 mm² ... 1.5 mm² Conductor cross section, flexible, with ferrule, with plastic sleeve: 0.25 mm² ... 1.5 mm² Stripping length: 8 mm I/O Connection method: Push-in connection Note on the connection method: Please observe the information provided on conductor cross sections in the ââ¬Ã AxiolineÃSmartÃElementsâ⬠user manual. Conductor cross section, rigid: 0.25 mm² ... 1.5 mm² Conductor cross section, flexible: 0.25 mm² ... 1.5 mm² Conductor cross section AWG: 24 ... 16 Conductor cross section, flexible, with ferrule, with plastic sleeve: 0.25 mm² ... 1.5 mm² Conductor cross section flexible, with ferrule without plastic sleeve: 0.25 mm² ... 1.5 mm² Stripping length: 8 mm |
Environmental and real-life conditions | Ambient conditions Ambient temperature (operation): -25°C ... 60°C Degree of protection: IP20 Air pressure (operation): 70 kPa ... 106 kPa (up to 3000Ãm above sea level) Air pressure (storage/transport): 70 kPa ... 106 kPa (up to 3000Ãm above sea level) Ambient temperature (storage/transport): -40°C ... 85°C Permissible humidity (operation): 5 % ... 95 % (non-condensing) Permissible humidity (storage/transport): 5 % ... 95 % (non-condensing) |
Standards and regulations | Protection class: III (IEC 61140, ENÃ61140, VDEÃ0140-1) |
Mounting | Mounting type: Smart Element slot Mounting position: See the system in which the SmartÃElement is used. |