Industrial Automation

Mechatronics

Industrial Safety

Panel Components

Sensors and Systems of Vision

Pneumatics

Network Comunications

Automation Cables

Design Software

Access services

Enter your reserved area

Access services

Enter your reserved area

PHOENIX CONTACT 1234308
PHOENIX CONTACT 1234308
PHOENIX CONTACTNot available

PS-EE-2G/1AC/24DC/480W/SC - Power supply unit

Primary-switched power supply unit, ESSENTIAL POWER, Screw connection, DIN rail mounting, input: 1-phase, output: 24 V DC / 20 A, adjustable from 24 V DC ... 28 V DC
Product Code: 1234308
Partner cod.: 1234308
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Description
Download
Tecnichal data
Input dataAC operation
Supply system configuration: TN, TT, IT (PE)
Nominal input voltage range: 100 V AC ... 240 V AC
Input voltage range: 110 V AC ... 240 V AC ±10 % (PN = 480 W)
100 V AC ... 109 V AC -15 % ... +10 % (PN = 400 W)
Typical national grid voltage: 120 V AC
230 V AC
Voltage type of supply voltage: AC
Inrush current: typ. 16 A (at 25 °C)
Inrush current integral (I2t): typ. 0.25 A2s
Frequency range (fN): 50 Hz ... 60 Hz ±10 %
Mains buffering time: typ. 15 ms (120 V AC)
typ. 35 ms (230 V AC)
Current consumption: max. 6 A (480 W)
max. 5 A (400 W)
typ. 5 A (110 V AC (480 W))
typ. 2.3 A (240 V AC (480 W))
typ. 4.5 A (100 V AC (400 W))
typ. 4.3 A (109 V AC (400 W))
Protective circuit: Transient protection; Varistor
Switch-on time: typ. 1 s
Device mains fuse: 10 A internal (device protection), fast-blow
Recommended breaker for input protection: 6 A ... 16 A (Characteristic B, C, D, K or comparable)
Discharge current to PE: < 3.5 mA
Output dataEfficiency: typ. 91 % (120 V AC)
typ. 93 % (230 V AC)
Nominal output voltage: 24 V DC
Setting range of the output voltage (USet): 24 V DC ... 28 V DC (> 24 V DC, constant capacity restricted)
Nominal output current (IN): max. 20 A (PN = 480 W)
max. 16.66 A (PN = 400 W)
Short-circuit-proof: yes
No-load proof: yes
Crest factor: typ. 1,7 (120 V AC)
typ. 1.8 (230 V AC)
Output power (PN): 480 W (240 V AC)
400 W (100 V AC)
Connection in parallel: yes, for increasing power and redundancy with diode
Connection in series: yes, for increased output voltage
Feedback voltage resistance: ≤ 35 V DC
Protection against overvoltage at the output (OVP): ≤ 35 V DC
Residual ripple: typ. 70 mVPP (with nominal values)
Control deviation: < 2 % (change in load, static 10 % ... 90 %)
< 4 % (change in load, dynamic 10 % ... 90 %)
< 0.1 % (change in input voltage ±10 %)
Rise time: < 100 ms (UOut = 10 % ... 90 %)
Minimum no-load power dissipation: < 4 W (120 V AC)
Maximum no-load power dissipation: < 3 W (230 V AC)
Minimum nominal load power dissipation: < 43 W (120 V AC)
Power loss nominal load max.: < 33 W (230 V AC)
Integrated fuse protection: no
Connection dataInput
Position: 1.x
Identification: 1.1 (), 1.2 (L), 1.3 (N)
Conductor connection
Connection method: Screw connection
rigid: 0.75 mm² ... 6 mm²
flexible: 0.75 mm² ... 4 mm²
flexible with ferrule without plastic sleeve: 0.75 mm² ... 4 mm²
flexible with ferrule with plastic sleeve: 0.75 mm² ... 4 mm²
rigid (AWG): 18 ... 10 (Cu)
Stripping length: 8 mm
Tightening torque: 0.5 Nm ... 0.6 Nm
5 lbf-in. ... 7 lbf-in.
Drive form screw head: Slotted L
Output
Position: 2.x
Identification: 2.1, 2.2 (+), 2.3, 2.4 (-)
Conductor connectionâۉ€¹
Connection method: Screw connection
rigid: 2.5 mm² ... 6 mm²
flexible: 2.5 mm² ... 4 mm²
flexible with ferrule without plastic sleeve: 2.5 mm² ... 4 mm²
flexible with ferrule with plastic sleeve: 2.5 mm² ... 4 mm²
rigid (AWG): 14 ... 10 (Cu)
Stripping length: 6.5 mm
Tightening torque: 0.5 Nm ... 0.6 Nm
5 lbf-in. ... 7 lbf-in.
Drive form screw head: Slotted L
SignalingLED signaling
Types of signaling: LED DC OK âۉ€œ signal state operation (UN = 24 V DC, IOut = IN)
Function: Visual operating state display
Color: green
LED off: Supply voltage input AC not present (Off)
LED on (green), DC OK: UOUT > 11 V (On (green), DC OK)
Electrical propertiesNumber of phases: 1.00
Insulation voltage input/output: 4 kV AC (type test)
3 kV AC (routine test)
Insulation voltage input / PE: 3.5 kV AC (type test)
2.4 kV AC (routine test)
Product propertiesProduct type: Power supply
Product family: ESSENTIAL POWER
MTBF (Telcordia SR-332): > 860000 h (25 °C)
> 640000 h (40 °C)
> 570000 h (45 °C)
Data management status
Article revision: 02
Insulation characteristics
Protection class: I
Degree of pollution: 2
Life expectancy (electrolytic capacitors)
Current: 20 A
Temperature: 40 °C
Time: 25000 h
Additional text: 120 V AC
Life expectancy (electrolytic capacitors)âۉ€¹
Current: 20 A
Temperature: 30 °C
Time: 50000 h
Additional text: 120 V AC
Life expectancy (electrolytic capacitors)âۉ€¹Ãƒ¢Ã¢‚¬Ã¢€¹
Current: 20 A
Temperature: 40 °C
Time: 37000 h
Additional text: 230 V AC
Life expectancy (electrolytic capacitors)âۉ€¹Ãƒ¢Ã¢‚¬Ã¢€¹Ãƒ¢Ã¢‚¬Ã¢€¹
Current: 20 A
Temperature: 30 °C
Time: 74000 h
Additional text: 230 V AC
DimensionsItem dimensions
Width: 86 mm
Height: 124 mm
Depth: 125 mm
Installation dimensions
Installation distance right/left: 10 mm / 10 mm
Installation distance top/bottom: 30 mm / 30 mm
MountingMounting type: DIN rail mounting
Assembly note: alignable: 0 mm horizontally, 30 mm vertically
Mounting position: horizontal DIN rail NS 35, EN 60715
With protective coating: no
Material specificationsHousing material: Metal
Aluminum (AlMg3) / sheet steel, zinc-plated
Hood version: Stainless steel
Side element version: Aluminum
Foot latch material: Sheet steel, zinc-plated
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -20 °C ... 70 °C (Derating >45 °C: 2.5%/K)
Ambient temperature (storage/transport): -40 °C ... 85 °C
Maximum altitude: ≤ 3000 m (> 2000 m, Derating: 10 %/1000 m)
Climatic class: 3K22 (in accordance with EN 60721-3-3)
Max. permissible relative humidity (operation): ≤ 95 % (at 25 °C, non-condensing)
Shock (operation): 15 ms, 15g, per spatial direction (IEC 60068-2-27)
Vibration (operation): 10 Hz ... 50 Hz, amplitude ±0.2 mm
50 Hz ... 150 Hz, 2.3g, 90 min.
Temp code: T4 (-20...+70 °C; >45 °C, Derating: 2,5 %/K)
Standards and regulationsOvervoltage category
EN 61010-1: II (≤ 3000 m)
Electrical safety
Standard designation: Electrical safety
Standards/specifications: IEC 61010-2-201 (SELV)
Safety for measurement, control, and laboratory equipment
Standard designation: Safety for equipment for measurement, control, and laboratory use
Standards/specifications: IEC 61010-1
Protective extra-low voltage
Standard designation: Protective extra-low voltage
Standards/specifications: IEC 61010-1 (SELV)
IEC 61010-2-201 (PELV)
Limitation of harmonic line currents
Standard designation: Limitation of harmonic line currents
Standards/specifications: EN 61000-3-2
Mains voltage dips
Standard designation: Requirement of the semiconductor industry with regard to mains voltage dips
Standards/specifications: SEMI F47 - 0706 (120 V AC)
Safe isolation
Standard designation: Safe isolation
Standards/specifications: IEC 61558-2-16
Note: Transformer
ApprovalsUL
Identification: UL/C-UL Listed UL 61010-1
ULâۉ€¹
Identification: UL/C-UL Listed UL 61010-2-201
CB scheme
Identification: CB scheme (IEC 61010-1, IEC 61010-2-201)
EMC dataElectromagnetic compatibility: Conformance with EMC Directive 2014/30/EU
Low Voltage Directive: Conformance with Low Voltage Directive 2014/35/EC
Interference emission: Interference emission in accordance with EN 61000-6-3 (residential and commercial) and EN 61000-6-4 (industrial)
EMC requirements for noise immunity: EN 61000-6-2
Conducted noise emission: EN 55016
EN 61000-6-3 (Class B)
Noise emission: EN 55016
EN 61000-6-3 (Class B)
Harmonic currents
Standards/regulations: EN 61000-3-2
EN 61000-3-2 (Class A)
Frequency range: 0 kHz ... 2 kHz
Electrostatic discharge
Standards/regulations: EN 61000-4-2
Electrostatic dischargeâۉ€¹
Contact discharge: 6 kV (Test Level 3)
Discharge in air: 8 kV (Test Level 3)
Comments: Criterion A
Electromagnetic HF field
Standards/regulations: EN 61000-4-3
Electromagnetic HF fieldâۉ€¹
Frequency range: 80 MHz ... 1 GHz
1 GHz ... 6 GHz
2 GHz ... 3 GHz
Test field strength: 10 V/m (Test Level 3)
1 V/m (Test Level 3)
Comments: Criterion A
Fast transients (burst)
Standards/regulations: EN 61000-4-4
Fast transients (burst)âۉ€¹
Input: 4 kV (Test Level 4 - asymmetrical)
Output: 2 kV (Test Level 3 - asymmetrical)
Comments: Criterion A
Surge voltage load (surge)
Standards/regulations: EN 61000-4-5
Surge voltage load (surge)âۉ€¹
Input: 1 kV (Test Level 3 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
Output: 0.5 kV (Test Level 2 - symmetrical)
1 kV (Test Level 2 - asymmetrical)
Comments: Criterion B
Conducted interference
Standards/regulations: EN 61000-4-6
Conducted interferenceâۉ€¹
Input/Output: asymmetrical
Frequency range: 0.15 MHz ... 80 MHz
Comments: Criterion A
Voltage: 10 V (Test Level 3)
Voltage dips
Standards/regulations: EN 61000-4-11
Voltage: 230 V AC
Frequency: 50 Hz
Voltage dip: 70 %
40 %
0 %
Number of periods: 25 periods
10 periods
1 period
Comments: Criterion A
Criteria
Criterion A: Normal operating behavior within the specified limits.
Criterion B: Temporary impairment to operational behavior that is corrected by the device itself.
Criterion C: Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements.
Description
PS-EE-2G/1AC/24DC/480W/SC Alimentatore
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_01707.pdf

Data_sheet_01013.pdf

Manufacturer_declaration_04347.pdf

Manufacturer_declaration_05490.pdf

Package_slip_01809.pdf

Technical_drawing_10603.pdf