PHOENIX CONTACT 1256118
PHOENIX CONTACTNot available

VAL-MS 230 P - Type 2 surge protection plug

Type2 surge protection plug with high-capacity varistor for VAL-MS-PSbase element, thermal monitoring, visual fault indication. Version: 230VAC
Product Code: 1256118
Partner cod.: 1256118
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Download
Tecnichal data
Product propertiesIEC test classification: II
T2
EN type: T2
IEC power supply system: TN
TT
Type: DIN rail module, two-section, divisible
Product type: Replacement plug
Product family: VALVETRAB MS
Number of positions: 1
Surge protection fault message: optical
Insulation characteristics
Overvoltage category: III
Pollution degree: 2
Electrical propertiesNominal frequency fN: 50 Hz (60Hz)
Connection dataConnection method: pluggable
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/3e02d9b64ee0a341a2e312513f1ad825/-S204x204-FJPG
Width: 17.5 mm
Height: 52.4 mm
Depth: 55.3 mm
Horizontal pitch: 1 Div.
Material specificationsFlammability rating according to UL 94: V-0
CTI value of material: 600
Insulating material: PA 6.6
Material group: I
Housing material: PA 6.6
Protective circuitMode of protection: L-N
L-PEN
Direction of action: 1L-N/PE
Nominal voltage UN: 240/415VAC (TN)
240/415VAC (TT)
Nominal frequency fN: 50 Hz (60Hz)
Maximum continuous voltage UC: 275 VAC
Residual current IPE: ≤ 0.45 mA
Standby power consumption PC: ≤ 120 mVA
Nominal discharge current In (8/20) µs: 20 kA
Maximum discharge current Imax (8/20) µs: 40 kA
Short-circuit current rating ISCCR: 25 kA
Voltage protection level Up: ≤ 1.35 kV
Residual voltage Ures: ≤ 1.35 kV (at In)
≤ 1.1 kV (at 10 kA)
TOV behavior at UT: 335 VAC (5s / withstand mode)
440 VAC (120min / safe failure mode)
Response time tA: ≤ 25 ns
Max. backup fuse with branch wiring: 125 A (gG)
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -40°C ... 85°C
Ambient temperature (storage/transport): -40°C ... 85°C
Altitude: ≤ 2000 m (amsl)
Permissible humidity (operation): 5 % ... 95 %
Shock (operation): 25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation): 2g (10 ... 500 Hz / 2.5 h / X, Y, Z)
Standards and regulationsStandards/specifications: IEC 61643-11
EN61643-11
Note: 2011
2012
MountingMounting type: on base element
Technical Specs
ECLASSECLASS-11.0: 27130890
ECLASS-13.0: 27171292
ETIMETIM 9.0: EC002496