Industrial Automation
AXL E IOL DI8 DO4/4 EF M12 6M - Digital module


Dimensions | Dimensional drawing: https://caas.phoenixcontact.com/caas/v1/stable/media/40434/full/b1500?format=jpg Width: 60 mm Height: 184 mm Depth: 30.3 mm |
Notes | Note on application Note on application: Only for industrial use |
Material specifications | Housing material: Zinc die-cast |
Input data | Digital: Input name: Digital inputs Description of the input: EN 61131-2 types 1 and 3 Number of inputs: 8 Cable length: max. 30 m (to the sensor) Connection method: M12 connector (A-coded) Note on the connection method: Push-pull fast connection according to IEC 61076-2-010 or screw connection according to IEC 61076-2-101 Connection technology: 4-conductor Input voltage range "0" signal: -3 V ... 5 V DC Input voltage range "1" signal: 11 V DC ... 30 V DC Nominal input voltage UIN: 24 V DC Nominal input current at UIN: typ. 2.5 mA Input filter time: 1 ms Protective circuit: Reverse polarity protection; yes Short-circuit protection; yes Overload protection; yes IO-Link Number of ports: 1 Connection method: M12 connector (A-coded) Note on the connection method: Push-pull fast connection according to IEC 61076-2-010 or screw connection according to IEC 61076-2-101 Connection technology: 3-conductor Port type: Class A Specification: V1.1.3 Reverse polarity protection: yes Transmission speed: 230.4 kbps (COM3) Cycle Time: 0.6 ms Process data update: 0.6 ms Amount of process data: 3 Byte (Input data) 1 Byte (Output data) |
Output data | Digital: Output name: Digital outputs Connection method: M12 connector (A-coded) Note on the connection method: Push-pull fast connection according to IEC 61076-2-010 or screw connection according to IEC 61076-2-101 Connection technology: 3-conductor Number of outputs: 8 Protective circuit: Overload protection; yes Short-circuit protection; yes Output voltage: 24 V DC Output current: max. 2 A (per output) Nominal output voltage: 24 V DC (from UA1, UA2) Output voltage range: min. UA1 - 1 V ... max. UA1 min. UA2 - 1 V ... max. UA2 Load min.: 10 ké Output voltage when switched off: max. 1 V Output current when switched off: max. 300 õA Nominal load, inductive: 48 VA (1.2 H, 12 é, at nominal voltage, utilization category DC-13) Nominal load, ohmic: 48 W (12 é, at nominal load) Switching frequency: max. 1 per second (with inductive load) Reverse voltage resistance to short pulses: no Behavior with overload: Shutdown with automatic restart Behavior with inductive overload: Output can be destroyed Signal delay: max. 100 õs (when switched on) max. 100 õs (when switched off, with at least 50 mA load current) Overcurrent shut-down: as of 2.2 A Output current with ground connection interrupt when switched off: < 1 mA |
Product properties | Product type: I/O component Product family: Axioline E Type: Stand-Alone Special properties: IO-Link Data management status Article revision: 00 Insulation characteristics Pollution degree: 2 (IEC 60664-1, EN 60664-1) |
Electrical properties | Supply: IO-Link Designation: IO-Link port supply (L+) Nominal voltage for I/O supply: 24 V DC (Provided via the IO-Link interface of the IO-Link master.) Supply voltage range: 18 V DC ... 30 V DC (including all tolerances, including ripple) Nominal current per device: typ. 30 mA Current consumption: max. 800 mA (Device dependent; observe the current of the IO-Link master that is made available via L+.) Protective circuit: Reverse polarity protection; yes Supply: Sensors Designation: Supply of the sensors (from L+) Current consumption: max. 800 mA (per port) max. 800 mA (Device dependent; observe the current of the IO-Link master that is made available via L+.) Supply: Actuators Designation: Supply of actuators (UA1, UA2) Connection method: M12 connector (L-coded) Note on the connection method: Screw connection in accordance with IEC 61076-2-111 Number of positions: 4 Supply voltage: 24 V DC (Nominal voltage) Supply voltage range: 18 V DC ... 30 V DC (including all tolerances, including ripple) Current consumption: max. 8 A (Group UA1) max. 8 A (Group UA2) typ. 35 mA (Group UA1) typ. 35 mA (Group UA2) Protection: max. 8 A (per supply UA1 and UA2) Electrical isolation/isolation of the voltage ranges Test voltage: 24 V supply L+ (IO-Link)/functional ground: 660 V AC, 50 Hz, 1 min. Test voltage: 24 V supply UA1/24 V supply L+ (IO-Link): 660 V AC, 50 Hz, 1 min. Test voltage: 24 V supply UA2/24 V supply L+ (IO-Link): 660 V AC, 50 Hz, 1 min. Test voltage: 24 V supply UA1/functional ground: 660 V AC, 50 Hz, 1 min. Test voltage: 24 V supply UA2/functional ground: 660 V AC, 50 Hz, 1 min. Test voltage: 24 V supply UA1/24 V supply UA2: 660 V AC, 50 Hz, 1 min. |
Connection data | Connection method: M12 connector Tightening torque: 0.4 Nm |
Environmental and real-life conditions | Ambient conditions Ambient temperature (operation): -25 °C ... 70 °C Degree of protection: IP65/IP67/IP69 Air pressure (operation): 70 kPa ... 106 kPa (up to 3000 m above sea level) Air pressure (storage/transport): 70 kPa ... 106 kPa (up to 3000 m above sea level) Ambient temperature (storage/transport): -25 °C ... 85 °C Permissible humidity (operation): 5 % ... 95 % Permissible humidity (storage/transport): 5 % ... 95 % |
Standards and regulations | Protection class: III (IEC 61140, EN 61140, VDE 0140-1) |