Product properties | Product type: Panel feed-through terminal block Product family: PLW 16 Number of positions: 3 Pitch: 10 mm Number of connections: 6 Number of rows: 1 Number of potentials: 3 Solder pins per potential: 1 Insulation characteristics Overvoltage category: III Degree of pollution: 3 |
Electrical properties | Nominal current IN: 41 A Nominal voltage UN: 1000 V Degree of pollution: 3 Rated voltage (III/3): 1000 V Rated surge voltage (III/3): 8 kV Rated voltage (III/2): 1000 V Rated surge voltage (III/2): 8 kV Rated voltage (II/2): 1000 V Rated surge voltage (II/2): 6 kV |
Connection data | Connection technology Connector system: PLW 16-6 Nominal cross section: 16 mm² Conductor connection exterior Connection method: Push-lock connection Connection direction of the conductor to plug-in direction: 0° Conductor cross section rigid: 2.5 mm² ... 10 mm² Single-conductor/terminal point multi-stranded: 2.5 mm² ... 16 mm² Conductor cross section flexible: 2.5 mm² ... 25 mm² Conductor cross section flexible, with ferrule without plastic sleeve: 2.5 mm² ... 16 mm² Conductor cross section, flexible, with ferrule, with plastic sleeve: 2.5 mm² ... 16 mm² Stripping length: 18 mm Conductor connection interior Connection method: Push-in spring connection Connection direction of the conductor to plug-in direction: 35° Conductor cross section flexible, with ferrule without plastic sleeve: 1.5 mm² ... 6 mm² Conductor cross section, flexible, with ferrule, with plastic sleeve: 1.5 mm² ... 6 mm² Stripping length: 15 mm |
Mounting | Plate thickness: 19.26 mm |
Material specifications | Material data - contact Note: WEEE/RoHS-compliant, free of whiskers according to IEC 60068-2-82/JEDEC JESD 201 Contact material: Cu alloy Surface characteristics: tin-plated Material data - housing Color (Housing): gray (7042) Insulating material: PA Insulating material group: I CTI according to IEC 60112: 600 Flammability rating according to UL 94: V0 Glow wire flammability index GWFI according to EN60695-2-12: 850 Glow wire ignition temperature GWIT according to EN60695-2-13: 775 Temperature for the ball pressure test according to EN60695-10-2: 125°C Material data â actuating element Insulating material: PBT GF Insulating material group: IIIa CTI according to IEC 60112: 275 Flammability rating according to UL 94: V0 |
Notes | Safety note Safety note: ⢠WARNING: Only electrically qualified personnel may install and operate the product. They must observe the following safety notes. The qualified personnel must be familiar with the basics of electrical engineering. They must be able to recognize and prevent danger. The relevant symbol on the packaging indicates that only personnel familiar with electrical engineering are allowed to install and operate the product. ⢠The installation notes/Design In documents online on the download page at phoenixcontact.com/products must be observed for this product. ⢠The cable entry funnel is not safe to touch. Never connect or disconnect the terminal when it is energized. Take appropriate steps to ensure touch protection. ï· There is no electrical contact to the housing. Make sure that protective grounding is provided for green/yellow color variants and articles marked with PE. |
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/e840d33717330747ad0c7b5d4b264f71/-S204x204-FJPG Pitch: 10 mm Width [w]: 54.4 mm External dimensions Width [w]: 54.4 mm Height [h1]: 43 mm Length [l1]: 25.7 mm Internal dimensions Width [w]: 54.4 mm Height [h2]: 42.8 mm Length [l2]: 20.27 mm |
Electrical tests | Air clearances and creepage distances | 1. Insulation coordination Specification: IEC 60947-1:2007-06 + A1:2010-12 Insulating material group: I Comparative tracking index (IEC 60112): CTI 600 Rated insulation voltage (III/3): 1000 V Rated surge voltage (III/3): 8 kV minimum clearance value - non-homogenous field (III/3): 8 mm minimum creepage distance (III/3): 12.5 mm Rated insulation voltage (III/2): 1000 V Rated surge voltage (III/2): 8 kV minimum clearance value - non-homogenous field (III/2): 8 mm minimum creepage distance (III/2): 5 mm Rated insulation voltage (II/2): 1000 V Rated surge voltage (II/2): 6 kV minimum clearance value - non-homogenous field (II/2): 5.5 mm minimum creepage distance (II/2): 5 mm |
Environmental and real-life conditions | Ambient conditions Ambient temperature (operation): -40°C ... 100°C (Depending on the current carrying capacity/derating curve) Ambient temperature (storage/transport): -40°C ... 70°C Relative humidity (storage/transport): 30 % ... 70 % Ambient temperature (assembly): -5°C ... 105°C |
Packaging specifications | Type of packaging: packed in cardboard |
ECLASS | ECLASS-11.0: 27141134 ECLASS-13.0: 27141134 ECLASS-12.0: 27141134 |
ETIM | ETIM 9.0: EC001283 |
UNSPSC | UNSPSC 21.0: 39121400 |