Industrial Automation
Notes | General: The necessary requirements for insulation (basic insulation or reinforced insulation) from adjacent modules (in DIN-rail direction) must be realized by applying suitable measures (e.g., partition plates). Ensure that the supply voltage of the device has a common reference potential. For proper use, the specifications of the installation directive (see Downloads) must be observed. For applications or use with third-party products, the specifications, and the safety and warning instructions of the respective third-party manufacturer must also be met. |
Product properties | Product type: Feed-through terminal block Product family: PLC-INTERFACE Insulation characteristics Insulation: Functional insulation Insulation characteristics: Air clearances and creepage distances Insulation: Functional insulation Overvoltage category: III Pollution degree: 2 |
Electrical properties | Operating voltage (AC/DC): 250 V AC/DC Current (per branch): ⤠6 A Current (per connection terminal block with bridge shaft): ⤠6 A Air clearances and creepage distances Rated insulation voltage: 300 V Rated surge voltage: 4 kV |
Connection data | Connection method: Screw connection Stripping length: 8 mm Screw thread: M3 Number of positions: 5 Conductor cross section rigid: 0.2 mm² ... 4 mm² Conductor cross section flexible: 0.2 mm² ... 2.5 mm² Conductor cross section AWG: 24 ... 12 |
Signaling | Status display present: No |
Dimensions | Item dimensions Width: 6.2 mm Height: 80 mm Depth: 94 mm |
Material specifications | Flammability rating according to UL 94: V0 |
Environmental and real-life conditions | Ambient conditions Degree of protection (Module): IP20 Degree of protection (Installation location): ⥠IP54 Ambient temperature (operation): -40°C ... 70°C Ambient temperature (storage/transport): -40°C ... 70°C |
Approvals | CE Certificate: CE-compliant UKCA Certificate: UKCA-compliant Shipbuilding approval Certificate: TAE0000196 DNV GL data Temperature: D Humidity: A Vibration: B/C EMC: B Enclosure: Required protection according to the Rules shall be provided upon installation on board |
EMC data | Low Voltage Directive: Conformance with Low Voltage Directive Electromagnetic compatibility: Conformance with EMC directive |
Standards and regulations | Air clearances and creepage distances Standards/regulations: ENIEC 60664-1 |
Mounting | Mounting type: DIN rail mounting Assembly instructions: in rows with zero spacing Mounting position: any |
ECLASS | ECLASS-11.0: 27371692 ECLASS-12.0: 27371692 ECLASS-13.0: 27371692 |
ETIM | ETIM 9.0: EC002586 |
UNSPSC | UNSPSC 21.0: 39122300 |
Description other products