Industrial Automation

Mechatronics

Industrial Safety

Panel Components

Sensors and Systems of Vision

Pneumatics

Network Comunications

Automation Cables

Design Software

Access services

Enter your reserved area

Access services

Enter your reserved area

PHOENIX CONTACT 2297109
PHOENIX CONTACTNot available

ELR W3- 24DC/500AC- 2I-BR - Hybrid motor starter

Hybrid motor starter for reversing 3~AC motors up to 550VAC, with 24VDC input, 2.4A output current, adjustable overload shutdown, and limited phase failure detection
Product Code: 2297109
Partner cod.: 2297109
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Download
Tecnichal data
Product propertiesProduct type: Hybrid motor starters
Product family: CONTACTRON
Operating mode: 100% operating factor
Electrical propertiesNumber of phases: 3
Motor starter type: Reversing starter
Switching frequency: ≤ 2 Hz (Load-dependent)
Maximum power dissipation: 3.3 W
Minimum power dissipation: 1.1 W
Supply
Rated control circuit supply voltage US: 24 VDC
Control supply voltage range: 19.2 VDC ... 30 VDC
Rated control supply current IS: 40 mA
Protective circuit: Surge protection
Reverse polarity protection
Insulation characteristics
Rated insulation voltage: 500 V
Rated surge voltage: 6 kV
Overvoltage category: III
Degree of pollution: 2
Insulation characteristics between the control input and control supply voltage, and auxiliary circuit to the main circuit: Safe isolation (IEC 60947-1) at operating voltage ≤ 300 V AC
Basic insulation (IEC 60947-1) at operating voltage 300VAC...500VAC
Safe isolation (IEC 60947-1) in the auxiliary circuit ≤ 300 V AC
Input dataControl
Input name: Control input right/left
Rated actuating voltage UC: 24 VDC
Triggering voltage range: 19.2 VDC ... 30 VDC
Rated actuating current IC: 5 mA (Input type 1)
Switching threshold: 9.6 V (“0” signal)
19.2 V (“1” signal)
Typical response time: < 35 ms
Typical turn-off time: < 40 ms
Protective circuit: Reverse polarity protection
Output dataAC output
Rated operating voltage Ue: 500 VAC
Operating voltage range: 42 VAC ... 550 VAC
Rated operating current Ie: 2.4 A (AC-51)
2.4 A (AC-53a)
Mains frequency: 50/60 Hz
Load current range: 180 mA ... 2.4 A (see to derating)
Trigger characteristic in acc. with IEC 60947-4-2: Class 10A
Cooling time: 20 min. (for auto reset)
Leakage current: 0 mA
Protective circuit: Surge protection
Acknowledge output
Note: Confirmation 01: floating changeover contact
Contact switching type: 1changeover contact
Switching capacity in accordance with IEC 60947-5-1: 3 A (230 V, AC15)
2 A (24V, DC13)
Connection dataControl circuits
Connection method: Screw connection
Stripping length: 8 mm
Screw thread: M3
Conductor cross section rigid: 0.2 mm² ... 2.5 mm²
Conductor cross section flexible: 0.2 mm² ... 2.5 mm²
Conductor cross section AWG: 24 ... 14
Tightening torque: 0.5 Nm ... 0.6 Nm
5 lbf-in. ... 7 lbf-in.
Load circuit
Connection method: Screw connection
Stripping length: 8 mm
Screw thread: M3
Conductor cross section rigid: 0.2 mm² ... 2.5 mm²
Conductor cross section flexible: 0.2 mm² ... 2.5 mm²
Conductor cross section AWG: 24 ... 14
Tightening torque: 0.5 Nm ... 0.6 Nm
5 lbf-in. ... 7 lbf-in.
SignalingStatus display: Yellow LED
Operating voltage display: Green LED
Error indication: Red LED
DimensionsWidth: 22.5 mm
Height: 107 mm
Depth: 114 mm
Material specificationsFlammability rating according to UL 94: V0 (Housing)
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -25°C ... 70°C (observe derating)
Ambient temperature (storage/transport): -40°C ... 80°C
Altitude: ≤ 2000 m
ApprovalsUKCA
Certificate: UKCA-compliant
Standards and regulationsStandards/regulations
Standards/regulations: IEC 60947-1
MountingMounting type: DIN rail mounting
Assembly instructions: can be aligned with spacing: see derating
Mounting position: Vertical (horizontal DIN rail)
Technical Specs
ECLASSECLASS-11.0: 27370905
ECLASS-12.0: 27370905
ECLASS-13.0: 27370905
ETIMETIM 8.0: EC001037
UNSPSCUNSPSC 21.0: 25173900
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Application_note_00061.pdf

Data_sheet_03057.pdf

Manufacturer_declaration_00609.pdf

Manufacturer_declaration_01876.pdf

Manufacturer_declaration_14086.pdf

Package_slip_00974.pdf

Technical_drawing_37002.pdf