Industrial Automation
Notes | Utilization restriction EMC note: EMC: class A product, see manufacturer's declaration in the download area |
Product properties | Product type: Device coupler Insulation characteristics Overvoltage category: II Degree of pollution: 2 |
Electrical properties | Supply Supply voltage range: 16 VDC ... 32 VDC (input on trunk line side) Max. current consumption: 50 mA (trunk, no load) 550 mA (maximum trunk current) |
Connection data | Supply Conductor cross section, flexible: 2.50 mm² ... 0.20 mm² Conductor cross section, rigid: 2.50 mm² ... 0.20 mm² Conductor cross section, flexible [AWG]: 24 ... 12 Conductor cross section AWG: 24 ... 12 |
Ex data | Safety data Input voltage Ui: 32 V Inductance Li: 0 µH Capacitance Ci: 0 µF Max. output voltage Uo: 16.7 V Max. output current Io: 250 mA Max. output power Po: 1.05 W Safety-related maximum voltage Um: 253 V IIC: Max. external inductivity Lo / Max. external capacitance Co: / 0.39 µF 0.56 mH IIB: Max. external inductivity Lo / Max. external capacitance Co: / 2.33 µF 2.27 mH |
Interfaces | Signal: FOUNDATION Fieldbus PROFIBUS Data: Foundation Fieldbus and PROFIBUS PA Segment Connection method: Pluggable COMBICON screw connection for each spur No. of channels: 12 Termination resistor: Integrated termination, activated with bridge located in correct terminals Conductor cross section flexible max.: 2.5 mm² Conductor cross section flexible min.: 0.2 mm² Conductor cross section, rigid max.: 2.5 mm² Conductor cross section, rigid min.: 0.2 mm² Conductor cross section AWG max.: 12 Conductor cross section AWG min.: 24 Output nominal voltage: ⤠14 V (each spur) Output current: 35 mA (per spur) |
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/f54716aa18486942b3fc7f2a3380a22d/-S204x204-FJPG Width: 279 mm Height: 142 mm Depth: 66 mm |
Material specifications | Flammability rating according to UL 94: V0 |
Cable/line | Cable impedance: Recommend Type A fieldbus cable |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 IP30 (over trunk connections) Ambient temperature (operation): -40°C ... 80°C Ambient temperature (storage/transport): -40°C ... 85°C Max. permissible relative humidity (operation): < 95 % (non-condensing) Permissible humidity (operation): 95 % (non-condensing) Shock: 15g for 11 ms Vibration (operation): 2g, 10 Hz ... 150 Hz |
Approvals | ATEX Identification: II 2(1) G Ex eb ib mb [ia Ga] IIC T4 Gb II (1D) [Ex ia Da] IIIC FISCO power supply (spur) Certificate: DEMKO 16ATEX 1689X IECEx Identification: Ex eb ib mb [ia Ga] IIC T4 Gb [Ex ia Da] IIIC FISCO power supply (spur) Certificate: IECEx UL 16.0114X UKCAEx(UKEX) Identification: II 2(1) G Ex eb ib mb [ia Ga] IIC T4 Gb II (1D) [Ex ia Da] IIIC FISCO power supply (spur) Certificate: UL21UKEX2210X CCCEx Identification: Ex eb ib mb [ia Ga] IIC T4 Gb [Ex ia Da] IIIC Ex data UL, USA / Canada: Install in Class I, Div. 2, Groups A, B, C, D Entity/FISCO spur to: Class I, Groups A, B, C, D; Class II, Groups E, F, G; Class III; Group IIIC Class I, Zone 1 AEx eb ib mb [ia Ga] IIC T4 Gb [AEx ia Da] IIIC FISCO power supply (spur) Ex eb ib mb [ia Ga] IIC T4 Gb [Ex ia Da] IIIC FISCO power supply (spur) |
Standards and regulations | Standards/regulations Standards/regulations: Ring wave noise immunity in acc. with IEC 61000-4-12 Standards/regulationsâ Standards/regulations: Dry heat in acc. with IEC 61131-2 Standards/regulationsââ Standards/regulations: Damp heat in acc. with IEC 61131-2 Standards/regulationsâââ Standards/regulations: Shock and vibration in acc. with EN 61131-2 and EN 50178 IEC 61158-2 |
Mounting | Mounting type: DIN rail mounting Mounting position: On horizontal and vertical DIN rail NS 35 in acc. with EN 60715 |
ECLASS | ECLASS-11.0: 27242610 ECLASS-12.0: 27242610 ECLASS-13.0: 27242610 |
ETIM | ETIM 9.0: EC001600 |
UNSPSC | UNSPSC 21.0: 32151600 |