PHOENIX CONTACT 2320254
PHOENIX CONTACT 2320254
PHOENIX CONTACTAvailable

QUINT-UPS/ 24DC/ 24DC/ 5/1.3AH - Uninterruptible power supply

Uninterruptible energy supply with IQ technology and integrated energy storage for DIN rail mounting, input 24VDC, output: 24VDC / 5A, energy storage: lead AGM 1.2Ah, incl. mounted UTA 107/30 universal DIN rail adapter
Product Code: 2320254
Partner cod.: 2320254
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Download
Tecnichal data
Input dataDC operation
Input voltage: 24 VDC
Input voltage range: 18 VDC ... 30 VDC
Input voltage range DC: 18 VDC ... 30 VDC
Voltage type of supply voltage: DC
Buffer period: 50 min. (1A)
5 min. (5A)
Current consumption: 9.3 A (24VDC)
9.7 mA
1.7 A
7 A
Fixed backup threshold: ≤ 22.6 VDC
Output dataEfficiency: > 97.1 % (Mains operation, with charged energy storage)
97.31 %
Nominal output voltage: 24 VDC
Output voltage range: 18 VDC ... 30 VDC
Nominal output current (IN): 5 A (0°C...40°C)
Output current limit: > 7.5 A (Battery operation)
Bridging time: 360 s
Derating: 60°C ... 70°C (2.5%/K)
Output power: 120 W
Power dissipation: 2.5 W (Mains operation)
2.7 W (Mains operation)
1.9 W (Mains operation)
3.3 W (Battery operation)
3.3 W (Battery operation)
4.1 W (Battery operation)
Output fuse: 1x 15 A
Connection in parallel: 2
Connection in series: No
Mains operation
Nominal output voltage: 24 VDC
Output voltage range: 18 VDC ... 30 VDC (UOUT = UIN - 0,1 V DC)
Nominal output current (IN): 5 A (0°C...40°C)
POWER BOOST (IBoost): 7.5 A (0°C...40°C)
Selective Fuse Breaking (ISFB): 30 A (0°C...40°C)
Duration: 12 ms (SFB technology)
Battery operation
Nominal output voltage: 24 VDC
Output voltage range: 19.2 VDC ... 27.6 VDC (UOUT = UBAT - 0,5 V DC)
Nominal output current (IN): 5 A (0°C...40°C)
POWER BOOST (IBoost): 7.5 A (0°C...40°C)
Selective Fuse Breaking (ISFB): 32.5 A (0°C...40°C)
Duration: 15 ms (SFB technology)
Signal: Alarm
Output description: Relay
Output voltage: ≤ 30 V AC/DC
Continuous load current: ≤ 100 mA
Signal: Battery charge
Output description: Relay
Output voltage: ≤ 30 V AC/DC
Continuous load current: ≤ 100 mA
Signal: Battery mode
Output description: Relay
Output voltage: ≤ 30 V AC/DC
Continuous load current: ≤ 100 mA
Signal
Continuous load current: ≤ 200 mA
Energy storageNominal voltage UN: 24 VDC
End-of-charge voltage: 24 VDC ... 29 VDC (temperature compensated)
Charging current: 0.36 A
Nominal capacity: 1.2 Ah
Buffer period: 50 min. (1A)
5 min. (5A)
Latest startup date (battery only): 3 Months (0°C ... 20°C)
1 Months (30°C ... 40°C)
Latest startup (battery only) - range: 1 Months ... 3 Months (20°C...30°C)
Battery technology: VRLA-AGM
Memory medium: VRLA-AGM Battery 1.2Ah
Accumulator type: 2x BBBattery BP1.2-12FR (from UPS V/C-level05)
Disposal: Used batteries must not be thrown away with household waste, they should instead be disposed of in accordance with applicable national regulations.
IQ technology: Yes
Temperature sensor: yes
Network management: Yes
Connection dataInput
Connection method: Screw connection
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 2.5 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 2.5 mm²
Conductor cross section AWG min.: 20
Conductor cross section AWG max.: 12
Stripping length: 7 mm
Screw thread: M4
Tightening torque, min: 0.5 Nm
Tightening torque max: 0.6 Nm
Output
Connection method: Screw connection
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 2.5 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 2.5 mm²
Conductor cross section AWG min.: 20
Conductor cross section AWG max.: 12
Stripping length: 7 mm
Screw thread: M4
Tightening torque, min: 0.5 Nm
Tightening torque max: 0.6 Nm
Signal
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 2.5 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 2.5 mm²
Conductor cross section AWG min.: 24
Conductor cross section AWG max.: 12
Screw thread: M4
Tightening torque, min: 0.5 Nm
Tightening torque max: 0.6 Nm
InterfacesInterface: IFS (Interface system data port)
SignalingTypes of signaling: LED
Relay contact
Interface/software
Signal output
Signalization designation: Power In OK
Status display: LED
Note on status display: Static to
Signal output: Switching output
Signalization designation: Alarm
Status display: LED
Note on status display: Static to
Color: red
Signal output: Switching output​
Signalization designation: Battery charge
Status display: LED bar graph
Note on status display: dynamic
Color: red/green
Signal output: Switching output​​
Signalization designation: Battery mode
Status display: LED
Note on status display: Static to
Color: yellow
Product propertiesProduct type: DC UPS with integrated energy storage
Product family: QUINTUPS ‒ UPS with integrated energy storage
Disposal: Used batteries must not be thrown away with household waste, they should instead be disposed of in accordance with applicable national regulations.
IQ technology: Yes
MTBF (IEC 61709, SN 29500): > 806000 h (40°C)
Insulation characteristics
Protection class: III
Degree of pollution: 2
Life expectancy (electrolytic capacitors)
Time: 316800 h
DimensionsWidth: 88 mm
Height: 138 mm
Depth: 125 mm
Installation dimensions
Installation distance right/left: 5 mm / 5 mm
Installation distance top/bottom: 50 mm / 50 mm
MountingMounting type: DIN rail mounting
Assembly instructions: alignable: horizontal 5mm, vertical 50mm
Mounting position: horizontal DIN rail NS 35, EN 60715
Material specificationsHousing material: Metal
Steel sheet, zinc-plated
Type of housing: Steel sheet, zinc-plated
Side element version: Galvanized sheet steel, closed
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (storage/transport): -20°C ... 40°C
Ambient temperature (charge): 0°C ... 40°C
Ambient temperature (discharge): -20°C ... 50°C
Climatic class: 3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation): ≤ 95 % (25°C, non-condensing)
Shock: 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation): < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz ... 150 Hz, 2.3g tv = 90 min.
Standards and regulationsRail applications: EN50121-4
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations: EN50178/VDE0160 (PELV)
Standard - Electrical safety: EN60950-1/VDE0805 (SELV)
EN61558-2-17
ApprovalsUL approvals: UL/C-UL Recognized UL60950-1
UL Listed UL508
EMC dataLow Voltage Directive: Conformance with Low Voltage Directive 2014/35/EC
EMC requirements for noise emission: EN61000-6-3
EN61000-6-4
EMC requirements for noise immunity: EN61000-6-1
EN61000-6-2
Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU
Electrostatic discharge
Standards/regulations: EN61000-4-2
Electrostatic discharge​
Contact discharge: 8 kV (Test Level 4)
Discharge in air: 15 kV (Test Level 4)
Comments: Criterion A
Electromagnetic HF field
Standards/regulations: EN61000-4-3
Electromagnetic HF field​
Frequency range: 80 MHz ... 1 GHz
1 GHz ... 2 GHz
2 GHz ... 3 GHz
Test field strength: 20 V/m
10 V/m
3 V/m
Comments: Criterion A
Fast transients (burst)
Standards/regulations: EN61000-4-4
Fast transients (burst)​
Input: 2 kV (Test Level 3 - asymmetrical)
Output: 2 kV (Test Level 3 - asymmetrical)
Signal: 2 kV (Test Level 4 - asymmetrical)
Comments: Criterion A
Surge voltage load (surge)
Standards/regulations: EN61000-4-5
Input: 1 kV (Test Level 2 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
Output: 1 kV (Test Level 2 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
Signal: 1 kV (Test Level 2 - asymmetrical)
Comments: Criterion A
Conducted interference
Standards/regulations: EN61000-4-6
Conducted interference​
I/O/S: asymmetrical
Frequency range: 0.15 MHz ... 80 MHz
Comments: Criterion A
Voltage: 10 V (Test Level 3)
Emitted interference
Standards/regulations: EN61000-6-3
Radio interference voltage in acc. with EN 55011: EN55011 (EN55022) ClassB, area of application: Industry and residential
Emitted radio interference in acc. with EN 55011: EN 55011 (EN 55022) Class B, area of application: Industry and residential
Criteria
Criterion A: Normal operating behavior within the specified limits.
Criterion B: Temporary impairment to operational behavior that is corrected by the device itself.
Technical Specs
ECLASSECLASS-11.0: 27040705
ECLASS-13.0: 27040705
ECLASS-12.0: 27040705
ETIMETIM 9.0: EC000382
UNSPSCUNSPSC 21.0: 39121000
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_00040.pdf

Approvals_00041.pdf

Approvals_00054.pdf

Approvals_00055.pdf

Approvals_00056.pdf

Approvals_00057.pdf

Approvals_01610.pdf

Data_sheet_03112.pdf

Manual_00124.pdf

Manufacturer_declaration_03036.pdf

Manufacturer_declaration_04610.pdf

Manufacturer_declaration_05510.pdf

Manufacturer_declaration_14303.pdf

Package_slip_02099.pdf

Technical_drawing_37397.pdf

Various_00039.pdf

Various_00047.pdf

Various_00006.pdf