Industrial Automation
Input data | AC operation Nominal input voltage range: 3x 400 VAC ... 500 VAC Input voltage range: 3x 320 VAC ... 575 VAC 2x 360 VAC ... 575 VAC 450 VDC ... 800 VDC Voltage type of supply voltage: AC/DC Inrush current: < 20 A (typical) Inrush current integral (I2t): < 3.2 A2s AC frequency range: 45 Hz ... 65 Hz Frequency range DC: 0 Hz Mains buffering time: typ. 28 ms (400VAC) typ. 43 ms (500 VAC) Current consumption: 3x 1.6 A (400VAC) 3x 1.3 A (500 VAC) 0.9 A (600 VDC) Nominal power consumption: 783 VA Protective circuit: Transient surge protection; Varistor, gas-filled surge arrester Typical response time: < 0.16 s Permissible backup fuse: B6 B10 B16 Permissible DC backup fuse: DC: Connect a suitable fuse upstream Recommended breaker for input protection: 6 A ... 16 A (AC: Characteristics B, C, D, K) Discharge current to PE: < 3.5 mA |
Output data | Efficiency: > 93 % (at 400 V AC and nominal values) Nominal output voltage: 24 VDC ±1% Setting range of the output voltage (USet): 18 VDC ... 29.5 VDC (> 24 VDC, constant capacity restricted) Nominal output current (IN): 20 A (-25°C...60°C, UOUT =24VDC) POWER BOOST (IBoost): 26 A (-25°C...40°C permanent, UOUT = 24VDC ) Selective Fuse Breaking (ISFB): 120 A (12ms) Magnetic circuit breaker tripping: B2 / B4 / B6 / B10 / B16 / C2 / C4 / C6 Derating: 60°C ... 70°C (2.5%/K) Feedback voltage resistance: max. 32 VDC Protection against overvoltage at the output (OVP): < 32 VDC Control deviation: < 1 % (change in load, static 10 % ... 90 %) < 3 % (change in load, dynamic 10 % ... 90 %) < 0.1 % (change in input voltage ±10 %) Residual ripple: < 40 mVPP (with nominal values) Output power: 480 W Peak switching voltages nominal load: < 40 mVPP (at nominal values, 20 MHz) Maximum no-load power dissipation: 11 W Power loss nominal load max.: 40 W Rise time: < 0.05 s (UOUT (10 % ... 90 %)) Connection in parallel: yes, for redundancy and increased capacity Connection in series: yes Signal: DC OK active Output description: UOUT > 0.9 x UN: High signal Switching voltage range: 18 V ... 24 V Output voltage: + 24 VDC Maximum inrush current: ⤠20 mA (short-circuit-proof) Continuous load current: ⤠20 mA Signal: DC OK floating Output description: Relay contact, UOUT > 0.9 x UN: Contact closed Maximum switching voltage: 30 V AC/DC 24 VDC Maximum inrush current: 0.5 A 1 A Continuous load current: ⤠1 A Signal: POWER BOOST, active Output description: IOUT < IN: High signal Switching voltage range: 18 V ... 24 V Output voltage: + 24 VDC Maximum inrush current: ⤠20 mA (short-circuit-proof) Continuous load current: ⤠20 mA |
Connection data | Input Connection method: Screw connection Conductor cross section, rigid min.: 0.2 mm² Conductor cross section, rigid max.: 6 mm² Conductor cross section flexible min.: 0.2 mm² Conductor cross section flexible max.: 4 mm² Conductor cross section AWG min.: 18 Conductor cross section AWG max.: 10 Stripping length: 7 mm Screw thread: M4 Tightening torque, min: 0.5 Nm Tightening torque max: 0.6 Nm Output Connection method: Screw connection Conductor cross section, rigid min.: 0.2 mm² Conductor cross section, rigid max.: 6 mm² Conductor cross section flexible min.: 0.2 mm² Conductor cross section flexible max.: 4 mm² Conductor cross section AWG min.: 12 Conductor cross section AWG max.: 10 Stripping length: 7 mm Screw thread: M4 Tightening torque, min: 0.5 Nm Tightening torque max: 0.6 Nm Signal Conductor cross section, rigid min.: 0.2 mm² Conductor cross section, rigid max.: 6 mm² Conductor cross section flexible min.: 0.2 mm² Conductor cross section flexible max.: 4 mm² Conductor cross section AWG min.: 18 Conductor cross section AWG max.: 10 Screw thread: M4 Tightening torque, min: 0.5 Nm Tightening torque max: 0.6 Nm |
Signaling | Types of signaling: LED Active switching output Relay contact Signal output: DC OK active Status display: UOUT > 0.9 x UN: "DC OK" LED green Note on status display: UOUT < 0.9 x UN: Flashing "DC OK" LED LED flashing Color: green Signal output: DC OK floating Status display: UOUT > 0.9 x UN: "DC OK" LED green Note on status display: UOUT < 0.9 x UN: Flashing "DC OK" LED LED flashing Color: green Signal output: POWER BOOST, active Status display: IOUT > IN: LED "BOOST" yellow Color: yellow |
Electrical properties | Number of phases: 3.00 Insulation voltage input/output: 4 kV AC (type test) 2 kV AC (routine test) Insulation voltage output / PE: 500 VDC (routine test) Insulation voltage input / PE: 3.5 kV AC (type test) 2 kV AC (routine test) |
Product properties | Product type: Power supply Product family: QUINT POWER MTBF (IEC 61709, SN 29500): > 900000 h (25°C) > 534000 h (40°C) Insulation characteristics Protection class: I Degree of pollution: 2 |
Dimensions | Width: 69 mm Height: 130 mm Depth: 125 mm Installation dimensions Installation distance right/left: 5 mm / 5 mm Installation distance top/bottom: 50 mm / 50 mm Alternative assembly Width: 125 mm Height: 130 mm Depth: 72 mm |
Mounting | Assembly instructions: alignable: PN â¥50%, 5mm horizontally, 15mm next to active components, 50mm vertically alignable: PN <50%, 0mm horizontally, 40mm vertically top, 20 mm vertically bottom Mounting position: horizontal DIN rail NS 35, EN 60715 With protective coating: yes |
Material specifications | Housing material: Metal Steel sheet, zinc-plated Type of housing: Steel sheet, zinc-plated |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -40°C ... 70°C (>60°C Derating: 2,5%/K) Ambient temperature (storage/transport): -40°C ... 85°C Ambient temperature (start-up type tested): -40°C Maximum altitude: 5000 m Climatic class: 3K3 (in acc. with EN 60721) Max. permissible relative humidity (operation): 100 % (at 25°C, non-condensing) Shock: 18 ms, 30g, in each space direction (according to IEC 60068-2-27) Vibration (operation): < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6) 15 Hz ... 150 Hz, 2.3g, 90 min. |
Standards and regulations | Rail applications: EN50121-4 EN50121-3-2 Standard â Limitation of mains harmonic currents: EN61000-3-2 Standard - Electrical safety: IEC 61010-2-201(SELV) Standard - Equipment safety: BG (design tested) Standard â Protection against shock currents, basic requirements for protective separation in electrical equipment: EN50178 Standard â Safety extra-low voltage: IEC 61010-1 (SELV) IEC 61010-2-201 (PELV) Standard - Safe isolation: IEC 61010-2-201 Standard - safety for equipment for measurement, control, and laboratory use: IEC 61010-1 Noxious gas test: ISA-S71.04-1985 G3 Harsh Group A Approval - requirement of the semiconductor industry with regard to mains voltage dips: SEMI F47-0706 Compliance Certificate Overvoltage category EN 62477-1: III |
Approvals | CSA: CAN/CSA-C22.2 No.60950-1-07 CSA-C22.2 No.107.1-01 Shipbuilding approval: DNVGL(EMCB),ABS, LR, RINA, NK, BV UL approvals: UL/C-UL listed UL508 UL/C-UL Recognized UL60950-1 (3-wire + PE, star net) UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location) |
EMC data | Low Voltage Directive: Conformance with Low Voltage Directive 2014/35/EC EMC requirements for noise emission: EN61000-6-3 EN61000-6-4 EMC requirements for noise immunity: EN61000-6-1 EN61000-6-2 Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU Noise emission: EN 55011 (EN 55022) Electrostatic discharge Standards/regulations: EN61000-4-2 Electrostatic dischargeâ Contact discharge: 8 kV (Test Level 4) Discharge in air: 15 kV (Test Level 4) Comments: Criterion A Electromagnetic HF field Standards/regulations: EN61000-4-3 Electromagnetic HF fieldâ Frequency range: 80 MHz ... 1 GHz 1 GHz ... 2 GHz 2 GHz ... 3 GHz Test field strength: 20 V/m (Test Level 3) 10 V/m (Test Level 3) 10 V/m (Test Level 3) Comments: Criterion A Fast transients (burst) Standards/regulations: EN61000-4-4 Fast transients (burst)â Input: 4 kV (Test Level 4 - asymmetrical) Output: 2 kV (Test Level 3 - asymmetrical) Signal: 2 kV (Test Level 4 - asymmetrical) Comments: Criterion B Surge voltage load (surge) Standards/regulations: EN61000-4-5 Input: 3 kV (Test Level 3 - symmetrical) 6 kV (Test Level 4 - asymmetrical) Output: 1 kV (Test Level 2 - symmetrical) 2 kV (Test Level 3 - asymmetrical) Signal: 1 kV (Test Level 2 - asymmetrical) Comments: Criterion A Conducted interference Standards/regulations: EN61000-4-6 Conducted interferenceâ I/O/S: asymmetrical Frequency range: 0.15 MHz ... 80 MHz Comments: Criterion A Voltage: 10 V (Test Level 3) Emitted interference Standards/regulations: EN61000-6-3 Radio interference voltage in acc. with EN 55011: EN55011 (EN55022) ClassB, area of application: Industry and residential Emitted radio interference in acc. with EN 55011: EN 55011 (EN 55022) Class B, area of application: Industry and residential Criteria Criterion A: Normal operating behavior within the specified limits. Criterion B: Temporary impairment to operational behavior that is corrected by the device itself. |
ECLASS | ECLASS-11.0: 27040701 ECLASS-13.0: 27040701 ECLASS-12.0: 27040701 |
ETIM | ETIM 9.0: EC002540 |
UNSPSC | UNSPSC 21.0: 39121000 |
Description other products