Industrial Automation
AXL F AO4 1H - Analog module
![](https://www.technologybsa.com/wp-content/uploads/2023/08/copia.png)
![](https://www.technologybsa.com/wp-content/uploads/2023/08/copia.png)
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/172c7c5767999646b422d3edebda44f8/-S204x204-FJPG Width: 35 mm Height: 126.1 mm Depth: 54 mm Note on dimensions: The depth applies when a TH35-7.5 DIN rail is used (in accordance with EN60715). |
Interfaces | AxiolineFlocal bus Number of interfaces: 2 Connection method: Bus base module Transmission speed: 100 Mbps |
System properties | Module Input address area: 8 Byte Output address area: 8 Byte Required parameter data: 14 Byte Required configuration data: 7 Byte |
Output data | Analog Output name: Analog outputs Connection method: Push-in connection Connection technology: 2-conductor Note regarding the connection technology: shielded, twisted pair Number of outputs: 4 D/A converter resolution: 16 bit Protective circuit: Short-circuit and overload protection; electronic Transient protection; Suppressor diode Data formats: IB IL, S7-compatible Representation of output values: 16 bits (15 bits + sign) Process data update: 140 µs Current output signal: 0 mA ... 20 mA 4 mA ... 20 mA Load/output load current output: ⤠500 é Voltage output signal: 0 V ... 5 V -5 V ... 5 V 0 V ... 10 V -10 V ... 10 V Load/output load voltage output: ⥠1 ké |
Product properties | Type: block modular Product type: I/O component Product family: AxiolineF Mounting position: any (no temperature derating) Scope of delivery: including bus base module and AxiolineF connectors Insulation characteristics Overvoltage category: II (IEC 60664-1, EN60664-1) Pollution degree: 2 (IEC 60664-1, EN60664-1) |
Electrical properties | Potentials Power consumption: typ. 2.04 W (at UBus and UA) max. 3.75 W (at UBus and UA) Potentials: AxiolineF local bus supply (U Supply voltage: 5 VDC (via bus base module) Current draw: max. 150 mA typ. 120 mA Potentials: Supply for analog modules (U Supply voltage: 24 VDC Supply voltage range: 19.2 VDC ... 30 VDC (including all tolerances, including ripple) Current draw: max. 125 mA (4 current channels, 24mA output, 500é load) typ. 60 mA (4 voltage channels, 10 V output) max. 85 mA (4 voltage channels, 10 V output) max. 110 mA (4 current channels, 20mA output, 500é load) Power consumption: max. 3 W (at UA) Protective circuit: Surge protection; electronic (35 V, 0.5 s) Reverse polarity protection; Polarity protection diode Transient protection; Suppressor diode Electrical isolation/isolation of the voltage ranges Test voltage: 5V supply of the local bus (UBus) / 24V supply (I/Os): 500 VAC, 50 Hz, 1 min. Test voltage: 5V supply of the local bus (UBus)/analog outputs: 500 VAC, 50 Hz, 1 min. Test voltage: 5V supply of the local bus (UBus) / functional ground: 500 VAC, 50 Hz, 1 min. Test voltage: 24 V supply (I/O)/analog outputs: 500 VAC, 50 Hz, 1 min. Test voltage: 24V supply (I/O) / functional ground: 500 VAC, 50 Hz, 1 min. Test voltage: Analog outputs/functional ground: 500 VAC, 50 Hz, 1 min. |
Connection data | Connection technology Connection name: AxiolineF connector Note on the connection method: Please observe the information provided on conductor cross sections in the âAxiolineF: system and installationâ user manual. Conductor connection Connection method: Push-in connection Conductor cross section rigid: 0.2 mm² ... 1.5 mm² Conductor cross section flexible: 0.2 mm² ... 1.5 mm² Conductor cross section AWG: 24 ... 16 Stripping length: 8 mm AxiolineF connector Connection method: Push-in connection Note on the connection method: Please observe the information provided on conductor cross sections in the âAxiolineF: system and installationâ user manual. Conductor cross section, rigid: 0.2 mm² ... 1.5 mm² Conductor cross section, flexible: 0.2 mm² ... 1.5 mm² Conductor cross section AWG: 24 ... 16 Stripping length: 8 mm |
Environmental and real-life conditions | Ambient conditions Ambient temperature (operation): -25°C ... 60°C Degree of protection: IP20 Air pressure (operation): 70 kPa ... 106 kPa (up to 3000m above sea level) Air pressure (storage/transport): 70 kPa ... 106 kPa (up to 3000m above sea level) Ambient temperature (storage/transport): -40°C ... 85°C Permissible humidity (operation): 5 % ... 95 % (non-condensing) Permissible humidity (storage/transport): 5 % ... 95 % (non-condensing) |
Standards and regulations | Protection class: III (IEC 61140, EN61140, VDE0140-1) |
Mounting | Mounting type: DIN rail mounting Mounting position: any (no temperature derating) |
ECLASS | ECLASS-11.0: 27242601 ECLASS-12.0: 27242601 ECLASS-13.0: 27242601 |
ETIM | ETIM 9.0: EC001596 |
UNSPSC | UNSPSC 21.0: 32151600 |
Description other products