Industrial Automation
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/4466fa705ece7847b56185793696fa26/-S204x204-FJPG Width: 80 mm Height: 119.8 mm Depth: 71.5 mm Note on dimensions: Specfications with connectors |
Interfaces | Sercos Number of interfaces: 2 Connection method: RJ45 jack Inline local bus Number of interfaces: 1 Connection method: Inline data jumper Transmission speed: 500 kbps / 2 Mbps (automatic detection, no combined system) Sercosâ Equipment type: Sercos slave |
System properties | System limits Number of supported devices: max. 63 (per station) Number of local bus devices that can be connected: max. 63 Number of devices with parameter channel: max. 16 Number of supported branch terminals with remote bus branch: 0 Module ID code (hex): none |
Input data | Digital Input name: Digital inputs Description of the input: EN 61131-2 type 1 Number of inputs: 8 Connection method: Inline connector Connection technology: 3-conductor Input voltage: 24 VDC Input voltage range "0" signal: -30 VDC ... 5 VDC Input voltage range "1" signal: 15 VDC ... 30 VDC Nominal input voltage UIN: 24 VDC Nominal input current at UIN: typ. 3 mA Typical input current per channel: typ. 3 mA Typical response time: approx. 500 µs Protective circuit: Reverse polarity protection; Suppressor diode |
Output data | Digital Output name: Digital outputs Connection method: Inline connector Connection technology: 3-conductor Number of outputs: 4 Protective circuit: Short-circuit and overload protection; Freewheeling circuit in the output driver Output voltage: 24 VDC -1V (At nominal current) Maximum output current per module: max. 2 A Nominal output voltage: 24 VDC Output voltage when switched off: max. 500 mV Output current when switched off: max. 500 µA (When not loaded, a voltage can be measured even at an output that is not set.) Nominal load, inductive: 12 VA (1.2 H, 48 é) Nominal load, lamp: 12 W Nominal load, ohmic: 12 W Reverse voltage resistance to short pulses: Reverse voltage proof Behavior with overload: Auto restart Behavior with inductive overload: Output can be destroyed Behavior at voltage switch-off: The output follows the power supply without delay Signal delay: < 40 µs (ton, no load) < 50 µs (ton, load = 0.5 A) < 350 µs (toff, no load) < 235 µs (toff, load = 0.5A) Overcurrent shut-down: min. 0.7 A Output current with ground connection interrupt when switched off: max. 25 mA |
Product properties | Type: modular Product type: I/O component Product family: Inline Scope of delivery: including inline connectors, marking fields, and end plate No. of channels: 12 Diagnostics messages: Short-circuit or overload of the digital outputs yes Sensor supply failure yes Failure of the actuator supply yes |
Electrical properties | No. of channels: 12 Maximum power dissipation for nominal condition: 25.2 W Protective circuit: Surge protection, protection against polarity reversal of the supply voltage; 35V suppressor diode Potentials: Bus coupler supply U Supply voltage: 24 VDC (via Inline connector) Supply voltage range: 19.2 VDC ... 30 VDC (including all tolerances, including ripple) Current draw: max. 1 A (with max. number of connected I/O terminal blocks) typ. 60 mA (without connected I/O terminal blocks) Potentials: Communications power (U Supply voltage: 7.5 VDC Potentials: Supply of analog modules (U Supply voltage: 24 VDC Supply voltage range: 19.2 VDC ... 30 VDC (including all tolerances, including ripple) Potentials: Main circuit supply (U Supply voltage: 24 VDC (via Inline connector) Supply voltage range: 19.2 VDC ... 30 VDC (including all tolerances, including ripple) Current draw: max. 8 A min. 3 mA (without connected peripherals) Potentials: Segment circuit supply (U Supply voltage: 24 VDC (via Inline connector) Supply voltage range: 19.2 VDC ... 30 VDC (including all tolerances, including ripple) Current draw: max. 8 A min. 3 mA (without connected peripherals) |
Connection data | Connection technology Connection name: Inline connector Conductor connection Connection method: Spring-cage connection Conductor cross section rigid: 0.08 mm² ... 1.5 mm² Conductor cross section flexible: 0.08 mm² ... 1.5 mm² Conductor cross section AWG: 28 ... 16 Stripping length: 8 mm Inline connector Connection method: Spring-cage connection Conductor cross section, rigid: 0.08 mm² ... 1.5 mm² Conductor cross section, flexible: 0.08 mm² ... 1.5 mm² Conductor cross section AWG: 28 ... 16 Stripping length: 8 mm |
Environmental and real-life conditions | Ambient conditions Ambient temperature (operation): -25°C ... 60°C Degree of protection: IP20 Air pressure (operation): 70 kPa ... 106 kPa (up to 3000m above sea level) Air pressure (storage/transport): 70 kPa ... 106 kPa (up to 3000m above sea level) Ambient temperature (storage/transport): -40°C ... 85°C Permissible humidity (operation): 10 % ... 95 % (non-condensing) Permissible humidity (storage/transport): 10 % ... 95 % (non-condensing) |
Standards and regulations | Protection class: III (IEC 61140, EN61140, VDE0140-1) |
Mounting | Mounting type: DIN rail mounting |
Description other products