Industrial Automation
Notes | Utilization restriction CCCex note: Use in potentially explosive areas is not permitted in China. |
Product properties | Product type: Coupling relay Product family: PSRmini Application: Safe switch off High demand Low demand Ex Relay type: Electromechanical relay with force-guided contacts in accordance with IEC/ENÃ61810-3 Times Typical response time: < 100 ms (with Us when controlled via A1) Typical release time: < 200 ms (with Us when controlled via A1) Recovery time: < 500 ms |
Electrical properties | Maximum power dissipation for nominal condition: 5.7 W (at IL²Ã=Ã72ÃA²) Nominal operating mode: 100% operating factor Air clearances and creepage distances between the power circuits Rated insulation voltage: 250 VÃAC Rated surge voltage/insulation: Basic insulation 4ÃkV between all current paths and housing Safe isolation, reinforced insulation 2.5ÃkV between (93/94) and (31/32, 24V/GND) Safe isolation, reinforced insulation 6ÃkV: between (A1/A2) and (13/14) and (31/32, 24V/GND) between (A1/A2) and (93/94) between (13/14) and (93/94) Supply Designation: A1/A2 Rated control circuit supply voltage US: 24 V AC/DC ... 230 V AC/DC -15Ã%Ã...Ã+10Ã% Rated control supply current IS: 75 mA (24ÃVÃDC) 34 mA (48ÃVÃDC) 97 mA (42ÃVÃAC) 28 mA (120ÃVÃAC) 16 mA (230 V AC) Power consumption at US: 1.8 W (with DC) 2.1 W (with AC) Apparent power: typ. 4.1 VA Inrush current: typ. 16 A (ÃâtÃ<Ã100Ãõs at Us) < 5 mA (at terminal blocks 24V/GND at UD) Filter time: 10 ms (24 V DC, A1 in the event of voltage dips at Us ) max. 1.5 ms (at A1-A2; test pulse width; at 24ÃVÃDC) 7.5 ms (at A1-A2; test pulse rate; at 24ÃVÃDC) Test pulse rateÃ=Ã5ÃxÃTest pulse width Protective circuit: Surge protection; Varistor 275 V Supplyââ¬Ã¢¹ Designation: 24V/GND Diagnostic supply voltage UD: 24 VÃDC -15Ã% / +10Ã% Input current at UD: < 5 mA (at terminal blocks 24V/GND at UD) Protective circuit: Surge protection; 33 V suppressor diode Reverse polarity protection |
Output data | Relay: Enabling current path Output description: safety-related N/O contacts Number of outputs: 2 (undelayed) Contact switching type: 2 enabling current paths Contact material: AgSnO2 Switching voltage: min. 12 V AC/DC max. 250 V AC/DC (13/14, observe the load curve) max. 60 V AC/DC (93/94, observe the load curve) Switching capacity: min. 60 mW Inrush current: min. 3 mA max. 6 A Switching capacity (360/h cycles): 4 A (24ÃV (DC13)) 5 A (230 V (AC 15)) Limiting continuous current: 6 A (observe derating) Sq. Total current: 72 A2 (observe derating) Switching frequency: max. 1 Hz Mechanical service life: 10x 106 cycles Output fuse: 6 A gL/gG 4 A gL/gG (for low-demand applications) Relay: Confirmation current path Output description: Safety-related N/C contacts Number of outputs: 1 (undelayed) Contact switching type: 1 confirmation current path Contact material: AgCuNi, + Au Switching voltage: min. 3.3 V AC/DC max. 26.4 VÃDC Switching capacity: min. 3.3 mW Inrush current: min. 1 mA max. 100 mA Limiting continuous current: 100 mA Output fuse: 150 mA fast blow |
Connection data | Connection technology pluggable: yes Conductor connection Connection method: Screw connection Conductor cross section rigid: 0.2 mm² ... 2.5 mm² Conductor cross section flexible: 0.2 mm² ... 2.5 mm² Conductor cross-section AWG: 24 ... 12 Stripping length: 7 mm Screw thread: M3 |
Signaling | Status display: 1 x green LED, 1 x yellow LED Operating voltage display: 1 x yellow LED |
Dimensions | Width: 17.5 mm Height: 112.2 mm Depth: 114.5 mm |
Material specifications | Housing material: Polyamide |
Characteristics | Safety data Stop category: 0 Safety data: ENÃ50156-2 Safety Integrity Level (SIL): 3 (Reference IEC 61508) Safety data: IEC 61508 - High demand Safety Integrity Level (SIL): 3 (<Ã15%Ãof the overall SIL) Safety data: IEC 61508 - Low demand Safety Integrity Level (SIL): 3 (<Ã15%Ãof the overall SIL) |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Min. degree of protection of inst. location: IP54 Ambient temperature (operation): -40°C ... 70°C (observe derating) Ambient temperature (storage/transport): -40°C ... 85°C Maximum altitude: ââ°¤ 2000 m (Above sea level) Max. permissible humidity (storage/transport): 75 % (on average, 85% infrequently, non-condensing) Max. permissible relative humidity (operation): 75 % (on average, 85% infrequently, non-condensing) Shock: 15g Vibration (operation): 10ÃHzÃ...Ã150ÃHz, 2g |
Approvals | ATEX Identification: ïÃÃIIÃ3GÃÃExÃecÃnCÃIICÃT4ÃGc Certificate: ULÃ22ÃATEXÃ2912X IECEx Identification: ExÃecÃnCÃIICÃT4ÃGc Certificate: IECExÃULÃ22.0037X UL, USA/Canada Identification: cULus Certificate: E140324 UL Ex, USA / Canada Identification: Class I, Zone 2, AEx nA nC IIC T4 / Ex nA nC IIC Gc T4 X Class I, Div. 2, Groups A, B, C, D, T4 Certificate: E360692 CE Identification: CE-compliant Environmental simulation test Identification: G3 Certificate: ISA-S71.04 CCCÃ/ÃChina-Ex Identification: Ex ec nC IIC T4 Gc Certificate: 2022122304115695 |
Standards and regulations | Air clearances and creepage distances between the power circuits Standards/regulations: ENÃ60664-1, ENÃ60079-7, ENÃ60079-15 |
Mounting | Mounting type: DIN rail mounting Assembly instructions: See derating curve Mounting position: vertical or horizontal Connection method: Screw connection |