Industrial Automation
IB IL PB MA-PAC - Communication module


Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/61847ea072ac2f4a94bf2299909bd975/-S204x204-FJPG Width: 48.8 mm Height: 119.8 mm Depth: 71.5 mm |
Interfaces | Inline local bus Connection method: Bus base module Transmission speed: 500 kbps / 2 Mbps PROFIBUS DP V0 master/slave Connection method: 9-pos. D-SUB socket Transmission speed: 9.6 kbps ... 12 Mbps No. of channels: 1 |
System properties | Module ID code (dec.): 221 ID code (hex): DD Length code (hex): 0C Length code (dec): 12 Process data channel: 24 Byte Input address area: 24 Byte (Default) Output address area: 24 Byte (Default) Register length: 32 Byte |
Product properties | Type: modular Product type: I/O component Product family: Inline |
Electrical properties | Maximum power dissipation for nominal condition: 6.72 W Power dissipation: Module Potentials: Communications power (U Supply voltage: 7.5 VÃDC (via voltage jumper) Current draw: max. 280 mA typ. 98 mA |
Connection data | Connection technology Connection name: PROFIBUS DP PROFIBUS DP Connection method: 9-pos. D-SUB socket Stripping length: 8 mm |
Environmental and real-life conditions | Ambient conditions Ambient temperature (operation): -25°C ... 55°C Degree of protection: IP20 Air pressure (operation): 70 kPa ... 106 kPa (up to 3000Ãm above sea level) Air pressure (storage/transport): 70 kPa ... 106 kPa (up to 3000Ãm above sea level) Ambient temperature (storage/transport): -25°C ... 85°C Permissible humidity (operation): 10 % ... 95 % (according to DINÃENÃ61131-2) Permissible humidity (storage/transport): 10 % ... 95 % (according to DINÃENÃ61131-2) |
Standards and regulations | Protection class: III (IEC 61140, ENÃ61140, VDEÃ0140-1) |
Mounting | Mounting type: DIN rail mounting |