Industrial Automation

Mechatronics

Industrial Safety

Panel Components

Sensors and Systems of Vision

Pneumatics

Network Comunications

Automation Cables

Design Software

Access services

Enter your reserved area

Access services

Enter your reserved area

PHOENIX CONTACT 2700974
PHOENIX CONTACTNot available

ILC 151 ETH - Controller

The Inline controller offers the option of communicating via PROFINET and Modbus/TCP. Programming is carried out using PC Worx Express or PC Worx (IEC 61131-3).
Product Code: 2700974
Partner cod.: 2700974
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Download
Tecnichal data
NotesUtilization restriction
CCCex note: Use in potentially explosive areas is not permitted in China.
Product propertiesType: modular
Product type: Controller
Product family: Inline-Controller
Display
Diagnostics display: No
System propertiesProcessor: Altera Nios II 64 MHz
Retentive data storage: 8 kByte (NVRAM)
IEC 61131 runtime system
Program memory: 256 kByte
Data storage system: 256 kByte
Number of control tasks: 8
INTERBUS-Master
Amount of process data: max. 4096 bit (INTERBUS)
Number of supported devices: max. 128
Number of local bus devices that can be connected: max. 63 (observe current consumption)
Number of devices with parameter channel: max. 16
Number of supported branch terminals with remote bus branch: max. 3
Modbus/TCP-Client
Amount of process data: max. 16384 bit (internal Modbus /TCP client)
Number of Modbus/TCP clients: max. 8 later than FW 4.42
PROFINET
Device function: PROFINET device
Specification: 2.2
Device ID: 007Ehex / 126dez
Vendor ID: 00B0hex / 176dez
Function
Diagnostics display: No
Controller redundancy: No
Safety function: No
Functionality
Programming languages supported: Instruction list (IL)
Symbolic flowchart (SFC)
Ladder diagram (LD)
Function block diagram (FBD)
Structured text (ST)
System requirements
Engineering tool: PC Worx
PC Worx Express
Configuration tool: Config+ Version 1.01 or later
Diagnostics tool: DIAG+
Runtime system: eCLR
Application interface: OPC
Electrical propertiesTransmission medium: Copper
Real-time clock
Realtime clock: Yes
Description realtime clock: integrated (rechargeable battery buffered)
Potentials: 24 V supply U
Supply voltage: 24 VDC -15% / +20% (in accordance with EN61131-2)
Supply voltage range: 19.2 VDC ... 30 VDC
Current draw: 80 mA (without connected I/O terminal blocks)
Potentials: 7.5 V communications power U
Supply voltage: 7.5 VDC ±5%
Potentials: 24V analog supply U
Supply voltage: 24 VDC -15% / +20%
Supply voltage range: 19.2 VDC ... 30 VDC (including all tolerances, including ripple)
Potentials: 24 V main supply U
Supply voltage: 24 VDC -15% / +20% (in accordance with EN61131-2)
Supply voltage range: 19.2 VDC ... 30 VDC (including all tolerances, including ripple)
Current draw: max. 8 ADC
6 mA (without sensors)
Potentials: 24 V segment supply U
Supply voltage: 24 VDC -15% / +20% (in accordance with EN61131-2)
Supply voltage range: 19.2 VDC ... 30 VDC (including all tolerances, including ripple)
Current draw: max. 8 ADC
10 mA (without actuators)
Input dataDigital
Input name: Digital inputs
Description of the input: EN 61131-2 type 1 NPN/PNP
Number of inputs: 8
Cable length: max. 30 m
Connection method: Inline potential distributor
Connection technology: 2-, 3-, 4-conductor
Input voltage range: -0.5 V ... 30 V
Input voltage range "0" signal: -0.5 V ... 5 V
Input voltage range "1" signal: 15 V ... 30 V
Nominal input current at UIN: typ. 7 mA
max. 15 mA
Input filter time: typ. 5 ms (Signal change 01)
typ. 5 ms ()
Output dataDigital
Output name: Digital outputs
Connection method: Spring-cage connection
Connection technology: 2-, 3-, 4-conductor
Number of outputs: 4
Maximum output current per channel: 500 mA
Maximum output current per module / terminal block: 2 A
Nominal load, lamp: 12 W
Nominal load, ohmic: 12 W
Connection dataInline connector
Connection method: Spring-cage connection
Conductor cross section, rigid: 0.08 mm² ... 1.5 mm²
Conductor cross section, flexible: 0.08 mm² ... 1.5 mm²
Conductor cross section AWG: 28 ... 16
InterfacesWeb server: yes
null
Bus system: RJ45
Number of interfaces: 1
Connection method: RJ45 jack
Transmission speed: 10/100 Mbps
No. of channels: 1
INTERBUS local bus (master)
Number of interfaces: 1
Connection method: Inline data jumper
Transmission speed: 500 kBaud / 2 MBaud (can be switched)
Parameterization/operation/diagnostics
Bus system: RS-232
Number of interfaces: 1
Connection method: 6-pos. MINI DIN socket (PS/2)
Transmission speed: max. 115.2 kbps
Transmission physics: Copper
No. of channels: 1
DimensionsWidth: 80 mm
Height: 119.8 mm
Depth: 71.5 mm
Material specificationsColor: green
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -25°C ... 55°C
Ambient temperature (storage/transport): -25°C ... 85°C
Permissible humidity (operation): 10 % ... 95 % (according to DINEN61131-2)
Permissible humidity (storage/transport): 10 % ... 95 % (according to DINEN61131-2)
Shock: 25g, Criterion 1, according to IEC 60068-2-27
Vibration (operation): 5g
Air pressure (operation): 70 kPa ... 106 kPa (up to 3000m above sea level)
Air pressure (storage/transport): 70 kPa ... 106 kPa (up to 3000m above sea level)
Resistance to gases that may endanger the functions, in acc. with DIN 40046-36, DIN 40046-37: Sulfur dioxide (SO2) 10 ±0.3 ppm (test duration: 10 days), hydrogen sulfide (H2S) 1 ±0.3 ppm (test duration: 4 days), both at 25°C and with 75% humidity
EMC dataConformance with EMC directives: Immunity test in accordance with EN61000-6-2/IEC 61000-6-2 Electrostatic discharge (ESD)EN61000-4-2/IEC 61000-4-2 Criterion B, 6 kV contact discharge, 8 kV air discharge
Immunity test in accordance with EN61000-6-2/IEC 61000-6-2 Electromagnetic fieldsEN61000-4-3/IEC 61000-4-3 Criterion A, Field intensity: 10 V/m
Immunity test in accordance with EN61000-6-2/IEC 61000-6-2 Fast transients (burst)EN61000-4-4/IEC 61000-4-4 Criterion A, all interfaces 1 kVCriterion B, all interfaces 2 kV
Immunity test in accordance with EN61000-6-2/IEC 61000-6-2 Transient overvoltage (surge)EN61000-4-5/IEC 61000-4-5 Criterion B, supply lines DC: 0.5 kV/0.5 kV (symmetrical/asymmetrical), fieldbus cable shield 1 kV
Immunity test in accordance with EN61000-6-2/IEC 61000-6-2 Conducted interferenceEN61000-4-6/IEC 61000-4-6 Criterion A, Test voltage 10 V
Noise emission test in accordance with EN61000-6-4/IEC 61000-6-4 EN55011 ClassA
Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU
MountingMounting type: DIN rail mounting
Technical Specs
ECLASSECLASS-11.0: 27242207
ECLASS-12.0: 27242207
ECLASS-13.0: 27242207
ETIMETIM 9.0: EC000236
UNSPSCUNSPSC 21.0: 32151700
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Application_note_00082.pdf

Application_note_00189.pdf

Application_note_00108.pdf

Application_note_00132.pdf

Application_note_00109.pdf

Application_note_00051.pdf

Application_note_00101.pdf

Approvals_00156.pdf

Approvals_01165.pdf

Approvals_01166.pdf

Approvals_01202.pdf

Approvals_01479.pdf

Approvals_01497.pdf

Approvals_01554.pdf

Approvals_01895.pdf

Function_blocks_00003.pdf

Function_blocks_00002.pdf

Function_blocks_00005.pdf

Function_blocks_00004.pdf

Manual_00162.pdf

Manual_00146.pdf

Manual_00161.pdf

Manual_00085.pdf

Manufacturer_declaration_01037.pdf

Manufacturer_declaration_01038.pdf

Manufacturer_declaration_01502.pdf

Manufacturer_declaration_01503.pdf

Manufacturer_declaration_05551.pdf

Manufacturer_declaration_14513.pdf

Package_slip_01467.pdf

Package_slip_01468.pdf

Package_slip_02500.pdf

Package_slip_02501.pdf

Package_slip_02502.pdf

Product_information_00033.pdf

Product_information_00274.pdf

Technical_drawing_37658.pdf