Industrial Automation
ILC 171 ETH 2TX - Controller


Notes | Utilization restriction CCCex note: Use in potentially explosive areas is not permitted in China. |
Product properties | Type: modular Product type: Controller Product family: Inline-Controller Display Diagnostics display: No |
System properties | Processor: Altera Nios II 64 MHz Clock frequency: 64 MHz Retentive data storage: 48 kByte (NVRAM) IEC 61131 runtime system Program memory: 512 kByte Data storage system: 512 kByte Number of control tasks: 8 INTERBUS-Master Amount of process data: max. 4096 bit (INTERBUS) Number of supported devices: max. 128 Number of local bus devices that can be connected: max. 63 (observe current consumption) Number of devices with parameter channel: max. 24 Number of supported branch terminals with remote bus branch: max. 3 Modbus/TCP-Client Amount of process data: max. 32768 bit (internal Modbus /TCP client) Number of Modbus/TCP clients: max. 16 later than FW 4.42 PROFINET Device function: PROFINET device Specification: 2.2 Device ID: 007Ahex / 122dez Vendor ID: 00B0hex / 176dez Function Diagnostics display: No Controller redundancy: No Safety function: No Functionality Programming languages supported: Instruction list (IL) Symbolic flowchart (SFC) Ladder diagram (LD) Function block diagram (FBD) Structured text (ST) System requirements Engineering tool: PC Worx PC Worx Express Configuration tool: Config+ Version 1.01 or later Diagnostics tool: DIAG+ Runtime system: eCLR Application interface: OPC |
Electrical properties | Transmission medium: Copper Real-time clock Realtime clock: Yes Description realtime clock: integrated (rechargeable battery buffered) Potentials: 24 V supply U Supply voltage: 24 VÃDC -15Ã% / +20Ã% (in accordance with ENÃ61131-2) Supply voltage range: 19.2 VÃDC ... 30 VÃDC Current draw: 80 mA (without connected I/O terminal blocks) Potentials: 7.5 V communications power U Supply voltage: 7.5 VÃDC ñ5Ã% Potentials: 24ÃV analog supply U Supply voltage: 24 VÃDC -15Ã% / +20Ã% Supply voltage range: 19.2 VÃDC ... 30 VÃDC (including all tolerances, including ripple) Potentials: 24 V main supply U Supply voltage: 24 VÃDC -15Ã% / +20Ã% (in accordance with ENÃ61131-2) Supply voltage range: 19.2 VÃDC ... 30 VÃDC (including all tolerances, including ripple) Current draw: max. 8 AÃDC 6 mA (without sensors) Potentials: 24 V segment supply U Supply voltage: 24 VÃDC -15Ã% / +20Ã% (in accordance with ENÃ61131-2) Supply voltage range: 19.2 VÃDC ... 30 VÃDC (including all tolerances, including ripple) Current draw: max. 8 AÃDC 10 mA (without actuators) |
Input data | Digital Input name: Digital inputs Description of the input: EN 61131-2 type 1 NPN/PNP Number of inputs: 8 Cable length: max. 30 m Connection method: Inline potential distributor Connection technology: 2-, 3-, 4-conductor Input voltage range: -0.5 V ... 30 V Input voltage range "0" signal: -0.5 V ... 5 V Input voltage range "1" signal: 15 V ... 30 V Nominal input current at UIN: typ. 7 mA max. 15 mA Input filter time: typ. 5 ms (Signal change 0ïâ®1) typ. 5 ms () |
Output data | Digital Output name: Digital outputs Connection method: Spring-cage connection Connection technology: 2-, 3-, 4-conductor Number of outputs: 4 Maximum output current per channel: 500 mA Maximum output current per module / terminal block: 2 A Nominal load, lamp: 12 W Nominal load, ohmic: 12 W Behavior with inductive overload: Output can be destroyed |
Connection data | Inline connector Connection method: Spring-cage connection Conductor cross section, rigid: 0.08 mm² ... 1.5 mm² Conductor cross section, flexible: 0.08 mm² ... 1.5 mm² Conductor cross section AWG: 28 ... 16 |
Interfaces | Web server: yes null Bus system: RJ45 Number of interfaces: 2 Connection method: RJ45 jack Transmission speed: 10/100 Mbps No. of channels: 2 INTERBUS local bus (master) Number of interfaces: 1 Connection method: Inline data jumper Transmission speed: 500 kBaud / 2 MBaud (can be switched) Parameterization/operation/diagnostics Bus system: RS-232 Number of interfaces: 1 Connection method: 6-pos. MINI DIN socket (PS/2) Transmission speed: max. 115.2 kbps Transmission physics: Copper No. of channels: 1 |
Dimensions | Width: 80 mm Height: 119.8 mm Depth: 71.5 mm |
Material specifications | Color: green |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -25°C ... 55°C Ambient temperature (storage/transport): -25°C ... 85°C Permissible humidity (operation): 10 % ... 95 % (according to DINÃENÃ61131-2) Permissible humidity (storage/transport): 10 % ... 95 % (according to DINÃENÃ61131-2) Shock: 25g, Criterion 1, according to IEC 60068-2-27 Vibration (operation): 5g Air pressure (operation): 70 kPa ... 106 kPa (up to 3000Ãm above sea level) Air pressure (storage/transport): 70 kPa ... 106 kPa (up to 3000Ãm above sea level) Resistance to gases that may endanger the functions, in acc. with DIN 40046-36, DIN 40046-37: Sulfur dioxide (SO2) 10 ñ0.3 ppm (test duration: 10 days), hydrogen sulfide (H2S) 1 ñ0.3 ppm (test duration: 4 days), both at 25°C and with 75% humidity |
EMC data | Conformance with EMC directives: Immunity test in accordance with ENÃ61000-6-2/IEC 61000-6-2 Electrostatic discharge (ESD)ENÃ61000-4-2/IEC 61000-4-2 Criterion B, 6 kV contact discharge, 8 kV air discharge Immunity test in accordance with ENÃ61000-6-2/IEC 61000-6-2 Electromagnetic fieldsENÃ61000-4-3/IEC 61000-4-3 Criterion A, Field intensity: 10 V/m Immunity test in accordance with ENÃ61000-6-2/IEC 61000-6-2 Fast transients (burst)ENÃ61000-4-4/IEC 61000-4-4 Criterion A, all interfaces 1 kVCriterion B, all interfaces 2 kV Immunity test in accordance with ENÃ61000-6-2/IEC 61000-6-2 Transient overvoltage (surge)ENÃ61000-4-5/IEC 61000-4-5 Criterion B, supply lines DC: 0.5 kV/0.5 kV (symmetrical/asymmetrical), fieldbus cable shield 1 kV Immunity test in accordance with ENÃ61000-6-2/IEC 61000-6-2 Conducted interferenceENÃ61000-4-6/IEC 61000-4-6 Criterion A, Test voltage 10 V Noise emission test in accordance with ENÃ61000-6-4/IEC 61000-6-4 ENÃ55011 ClassÃA Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU |
Mounting | Mounting type: DIN rail mounting |