Industrial Automation
AXL F RTD8 XC 1F - Temperature module


Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/3f783436b27c3846a361ee861b282789/-S204x204-FJPG Width: 53.6 mm Height: 126.1 mm Depth: 54 mm Note on dimensions: The depth applies when a THÃ35-7.5 DIN rail is used (in accordance with ENÃ60715). |
Interfaces | AxiolineÃFÃlocal bus Number of interfaces: 2 Connection method: Bus base module Transmission speed: 100 Mbps |
System properties | Module Input address area: 16 Byte Output address area: 16 Byte Required parameter data: 20 Byte Required configuration data: 6 Byte |
Input data | Analog Input name: Analog inputs Description of the input: Inputs for resistive temperature sensors Number of inputs: 8 (for resistance temperature detectors) Connection method: Push-in connection Connection technology: 2-, 3-, 4-conductor (shielded) A/D converter resolution: 24 bit Sensor types (RTD) that can be used: Pt, Ni, KTY, Cu sensors Data formats: IB IL, S7-compatible Measured value representation: 16 bits (15 bits + sign bit) Input filter time: 40 ms 60 ms 100 ms 120 ms (adjustable) Nominal value of the current sources: 1 mA (Pt 100, Ni 100, RLin 500 é; pulse current, the specification is valid during the sampling phase) 210 õA (P t1000, Ni 1000, RLin 5000 é; pulse current, the specification is valid during the sampling phase) Differential non-linearity: typ. 1Ãppm / ñ0.0001Ã% (in all ranges) Integral non-linearity: typ. 30Ãppm / ñ0.003Ã% (Pt 100) typ. 20Ãppm / ñ0.002Ã% (RLin 500Ãé) typ. 200Ãppm / ñ0.02Ã% (RLin 5000Ãé) Linear resistance measuring range: 0 é ... 500 é 0 ké ... 5 ké Protective circuit: Short-circuit protection, overload protection of the inputs Transient protection of inputs Transient protection of sensor supplies |
Product properties | Type: block modular Product type: I/O component Product family: AxiolineÃF Mounting position: any (no temperature derating) Scope of delivery: including bus base module and AxiolineÃF connectors Insulation characteristics Overvoltage category: II (IEC 60664-1, ENÃ60664-1) Pollution degree: 2 (IEC 60664-1, ENÃ60664-1) |
Electrical properties | Potentials Power consumption: typ. 0.94 W (at UBus and UA (up to HWÃ01)) typ. 0.59 W (at UBus and UA (from HWÃ02)) max. 1.5 W (at UBus and UA (up to HWÃ01)) max. 1.03 W (at UBus and UA (from HWÃ02)) Potentials: AxiolineÃF local bus supply (U Supply voltage: 5 VÃDC (via bus base module) Current draw: max. 180 mA (up to HWÃ01) max. 85 mA (from HWÃ02) typ. 115 mA (up to HWÃ01) typ. 60 mA (from HWÃ02) Power consumption: max. 900 mW (up to HWÃ01) max. 425 mW (from HWÃ02) typ. 580 mW (up to HWÃ01) typ. 300 mW (from HWÃ02) Potentials: Supply for analog modules (U Supply voltage: 24 VÃDC Supply voltage range: 19.2 VÃDC ... 30 VÃDC (including all tolerances, including ripple) Current draw: max. 25 mA typ. 15 mA (up to HWÃ01) typ. 12 mA (from HWÃ02) Power consumption: max. 0.6 W Protective circuit: Surge protection; electronic (35 V, 0.5 s) Reverse polarity protection; Polarity protection diode Transient protection; Suppressor diode Electrical isolation/isolation of the voltage ranges Test voltage: 5ÃV supply of the local bus (UBus) / 24ÃV supply (I/Os): 500 VÃAC, 50 Hz, 1 min. Test voltage: 5ÃV supply of the local bus (UBus)/analog inputs: 500 VÃAC, 50 Hz, 1 min. Test voltage: 5ÃV supply of the local bus (UBus) / functional ground: 500 VÃAC, 50 Hz, 1 min. Test voltage: 24 V supply (I/O)/analog inputs: 500 VÃAC, 50 Hz, 1 min. Test voltage: 24ÃV supply (I/O) / functional ground: 500 VÃAC, 50 Hz, 1 min. Test voltage: Analog inputs/functional ground: 500 VÃAC, 50 Hz, 1 min. |
Connection data | Connection technology Connection name: AxiolineÃF connector Note on the connection method: Please observe the information provided on conductor cross sections in the ââ¬Ã AxiolineÃF: system and installationâ⬠user manual. Conductor connection Connection method: Push-in connection Conductor cross section rigid: 0.2 mm² ... 1.5 mm² Conductor cross section flexible: 0.2 mm² ... 1.5 mm² Conductor cross section AWG: 24 ... 16 Stripping length: 8 mm AxiolineÃF connector Connection method: Push-in connection Note on the connection method: Please observe the information provided on conductor cross sections in the ââ¬Ã AxiolineÃF: system and installationâ⬠user manual. Conductor cross section, rigid: 0.2 mm² ... 1.5 mm² Conductor cross section, flexible: 0.2 mm² ... 1.5 mm² Conductor cross section AWG: 24 ... 16 Stripping length: 8 mm |
Environmental and real-life conditions | Ambient conditions Ambient temperature (operation): -25°C ... 60°C (Standard) -40°C ... 70°C (Extended, see section ââ¬Ã Tested successfully: use under extreme ambient conditionsâ⬠in the data sheet.) Degree of protection: IP20 Air pressure (operation): 70 kPa ... 106 kPa (up to 3000Ãm above sea level) Air pressure (storage/transport): 70 kPa ... 106 kPa (up to 3000Ãm above sea level) Ambient temperature (storage/transport): -40°C ... 85°C Permissible humidity (operation): 5 % ... 95 % (non-condensing) Permissible humidity (storage/transport): 5 % ... 95 % (non-condensing) |
Standards and regulations | Protection class: III (IEC 61140, ENÃ61140, VDEÃ0140-1) |
Mounting | Mounting type: DIN rail mounting Mounting position: any (no temperature derating) |