Industrial Automation
AXL F CNT2 INC2 XC 1F - Special function module


Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/3f783436b27c3846a361ee861b282789/-S204x204-FJPG Width: 53.6 mm Height: 126.1 mm Depth: 54 mm Note on dimensions: The depth applies when a THÃ35-7.5 DIN rail is used (in accordance with ENÃ60715). |
Notes | Utilization restriction EMC note: EMC: class A product, see manufacturer's declaration in the download area |
Interfaces | AxiolineÃFÃlocal bus Number of interfaces: 2 Connection method: Bus base module Transmission speed: 100 Mbps |
System properties | Module ID code (hex): none Input address area: 28 Byte Output address area: 28 Byte Required parameter data: 115 Byte Required configuration data: 7 Byte |
Input data | Digital Input name: Digital inputs Description of the input: EN 61131-2, type 3 Number of inputs: 8 (CNT: G1, G2, Dir1, Dir2; INC: Ref1, Ref2, L1, L2) Connection method: Push-in connection Connection technology: 1-conductor (optional 2, 3-conductor) Input voltage range "0" signal: -3 VÃDC ... 5 VÃDC Input voltage range "1" signal: 11 VÃDC ... 30 VÃDC Nominal input voltage UIN: 24 VÃDC Nominal input current at UIN: 2.5 mA (per channel) Encoder Number of inputs: 2 (A1, /A1, B1, /B1, Z1, /Z1; A2, /A2, B2, /B2, Z2, /Z2) Input name: Incremental encoder inputs Encoder signals: Symmetrical and asymmetrical encoders Cable length: max. 30 m Counter Input name: Counter input for 24 V signals Description of the input: EN 61131-2, type 3 Connection method: Push-in connection Number of inputs: 2 (S1, S2) Input voltage: 24 VÃDC Input voltage range "0" signal: -3 VÃDC ... 5 VÃDC Input voltage range "1" signal: 11 VÃDC ... 30 VÃDC Input frequency: max. 300 kHz (1 channel wired) max. 100 kHz (more than one channel wired or Z signal monitoring via the firmware) Input current: 2.5 mA (per channel) Resolution: 32 bits Permissible cable length: max. 30 m |
Output data | Digital Output name: Digital outputs Connection method: Push-in connection Connection technology: 1-conductor Number of outputs: 2 (Out1, Out2) Protective circuit: Short-circuit protection Overload protection Output voltage: 24 VÃDC Maximum output current per channel: 500 mA Nominal output voltage: 24 VÃDC Nominal load, inductive: max. 12 VA (1.2 H, 48 é, with nominal voltage) Nominal load, lamp: max. 12 W (at nominal voltage) Nominal load, ohmic: max. 12 W (48 é, with nominal voltage) |
Product properties | Type: block modular Product type: I/O component Product family: AxiolineÃF Mounting position: any (no temperature derating) Scope of delivery: including bus base module and AxiolineÃF connectors Insulation characteristics Overvoltage category: II (IEC 60664-1, ENÃ60664-1) Pollution degree: 2 (IEC 60664-1, ENÃ60664-1) |
Electrical properties | Encoder Number: 2 (UE1, UE2) 2 (US1, US2) max. 2 (A, /A, B, /B, (Z, /Z)) max. 2 (A, B, (Z)) Nominal output voltage: 5 VÃDC 24 VÃDC Voltage range: 5 VÃDC ... 5.5 VÃDC 19.2 VÃDC ... 30 VÃDC Current carrying capacity: max. 250 mA typ. 500 mA Protective circuit: Short-circuit protection; electronic Designation: Symmetrical incremental encoders Asymmetrical incremental encoder Type of connection of signals: Push-in connection Encoder supply voltage: 5 VÃDC 24 VÃDC Signal voltage level: Differential signal (signal ââ¬Ã¢ inverted signal)Ãñ0.5ÃV, minimum; ñ6ÃV, maximum Low ââ°¤ 2.5 V, high ââ°¥ 3.5 V (up to 27 V, maximum) Common mode voltage range signal - ground: -10 V ... 13.2 V Input frequency: max. 300 kHz (1 channel wired) max. 100 kHz (more than one channel wired or Z signal monitoring via the firmware) max. 300 kHz (1 channel wired) max. 100 kHz (more than one channel wired or Z signal monitoring via the firmware) Potentials: AxiolineÃF local bus supply (U Supply voltage: 5 VÃDC (via bus base module) Current draw: max. 120 mA typ. 100 mA Power consumption: max. 0.6 W typ. 0.5 W Potentials: Feed-in of supply voltage (U Supply voltage: 24 VÃDC Supply voltage range: 19.2 VÃDC ... 30 VÃDC (including all tolerances, including ripple) Current draw: max. 2.5 A (dependent on the encoder or sensor type used and the load on the digital output.) Power consumption: max. 60 W (of which 1.6ÃW internal losses) Protective circuit: Surge protection; electronic (35 V, 0.5 s) Reverse polarity protection; parallel diode; with external 5ÃA fuse (only for commissioning) Electrical isolation/isolation of the voltage ranges Test voltage: 5ÃV supply of the local bus (UBus) / 24ÃV supply (I/Os): 500 VÃAC, 50 Hz, 1 min. Test voltage: 5ÃV supply of the local bus (UBus) / functional ground: 500 VÃAC, 50 Hz, 1 min. Test voltage: 24ÃV supply (I/O) / functional ground: 500 VÃAC, 50 Hz, 1 min. |
Connection data | Connection technology Connection name: AxiolineÃF connector Note on the connection method: Please observe the information provided on conductor cross sections in the ââ¬Ã AxiolineÃF: system and installationâ⬠user manual. Conductor connection Connection method: Push-in connection Conductor cross section rigid: 0.2 mm² ... 1.5 mm² Conductor cross section flexible: 0.2 mm² ... 1.5 mm² Conductor cross section AWG: 24 ... 16 Stripping length: 8 mm AxiolineÃF connector Connection method: Push-in connection Note on the connection method: Please observe the information provided on conductor cross sections in the ââ¬Ã AxiolineÃF: system and installationâ⬠user manual. Conductor cross section, rigid: 0.2 mm² ... 1.5 mm² Conductor cross section, flexible: 0.2 mm² ... 1.5 mm² Conductor cross section AWG: 24 ... 16 Stripping length: 8 mm |
Environmental and real-life conditions | Ambient conditions Ambient temperature (operation): -25°C ... 60°C (Standard, applications with UL approval, use in zoneÃ2 potentially explosive area) -40°C ... 70°C (Extended, see section ââ¬Ã Tested successfully: use under extreme ambient conditionsâ⬠in the data sheet.) Degree of protection: IP20 Air pressure (operation): 70 kPa ... 106 kPa (up to 3000Ãm above sea level) Air pressure (storage/transport): 70 kPa ... 106 kPa (up to 3000Ãm above sea level) Ambient temperature (storage/transport): -40°C ... 85°C Permissible humidity (operation): 5 % ... 95 % (non-condensing) Permissible humidity (storage/transport): 5 % ... 95 % (non-condensing) |
Standards and regulations | Protection class: III (IEC 61140, ENÃ61140, VDEÃ0140-1) |
Approvals | ATEX Identification: ïà II 3 G Ex ec IIC T4 Gc Certificate: UL 20 ATEX 2441X UKEX Identification: ïà II 3 G Ex ec IIC T4 Gc Certificate: PxCIMA22UKEX2701949X IECEx Identification: Ex ec IIC T4 Gc Certificate: IECEx ULD 20.0026X UL, USA/Canada Identification: cULus Certificate: E238705 UL Ex, USA / Canada Identification: Class I, Zone 2, AEx ec IIC T4 ClassÃI, DivisionÃ2, Groups A, B, C, D, T4 Ex ec IIC T4 Gc X Certificate: E366272 CCCÃ/ÃChina-Ex Identification: Ex ec IIC T4 Gc Certificate: ïì, 2021122309114456 |
Mounting | Mounting type: DIN rail mounting Mounting position: any (no temperature derating) |
Description other products