Industrial Automation
IB IL 24 LPSDO 8 V3-PAC - Safety module


Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/2182c65be3908e489150116208cdf69e/-S204x204-FJPG Width: 48.8 mm Height: 119.8 mm Depth: 71.5 mm Note on dimensions: Housing dimensions |
Interfaces | Inline local bus Connection method: Inline data jumper Transmission speed: 500 kbps / 2 Mbps (can be switched) |
System properties | SafetyBridge properties Connection to I/O modules: max. 16 (safe digital I/O modules) Logic memory: 60 kByte Module ID code (dec.): 171 ID code (hex): AB Length code (hex): 18 Length code (dec): 24 Process data channel: 48 Byte Input address area: 48 Byte ((Operating mode: SafetyBridge 24Ãwords)) Output address area: 48 Byte ((Operating mode: SafetyBridge 24Ãwords)) Register length: 48 Byte Required parameter data: 1 Byte ((Operating mode: SafetyBridge 24Ãwords)) Required configuration data: 5 Byte ((Operating mode: SafetyBridge 24Ãwords)) |
Output data | Digital Output name: Digital outputs Connection method: Spring-cage connection Connection technology: 2-, 3-, 4-conductor Number of outputs: 4 (for 2-channel assignment) 8 (for 1-channel assignment) 8 Protective circuit: Overload protection, short-circuit protection of outputs Output voltage: 24 VÃDC (US - 1 V) Output current: max. 6 A (Total current of all outputs, -25ðC ... 50ðC) max. 4 A (Total current of all outputs, >50ðC ... 55ðC) Maximum output current per group: 3 A Maximum output current per channel: 2 A Nominal output voltage: 24 VÃDC Nominal load, inductive: see safety data Nominal load, lamp: see safety data Nominal load, ohmic: see safety data Behavior with inductive overload: Output can be destroyed |
Product properties | Type: modular Product type: I/O component Product family: Inline Application: Functional safety Diagnostics messages: Short-circuit or overload of the digital outputs Error message in diagnostics code (bus) and display by means of the LED on the motor |
Electrical properties | Maximum power dissipation for nominal condition: 150 W Potentials: Communications power (U Supply voltage: 7.5 VÃDC (see safety data) Current draw: max. 230 mA (see safety data) Potentials: Main circuit supply (U Supply voltage: 24 VÃDC (see safety data) Supply voltage range: 19.2 VÃDC ... 30 VÃDC (including all tolerances, including ripple) Current draw: max. 6.03 A typ. 30 mA (all outputs set including actuator current) Potentials: Segment circuit supply (U Supply voltage: 24 V (see safety data) Supply: Module electronics Supply voltage: 24 VÃDC (via voltage jumper) Supply voltage range: 19.2 VÃDC ... 30 VÃDC Electrical isolation/isolation of the voltage ranges Test voltage: 5 V supply, incoming remote bus/7.5 V supply (bus logics): 500 VÃAC, 50 Hz, 1 min. Test voltage: 5 V supply, outgoing remote bus/7.5 V supply (bus logics): 500 VÃAC, 50 Hz, 1 min. Test voltage: 7.5 V supply (bus logics)/24 V supply (I/O): 500 VÃAC, 50 Hz, 1 min. Test voltage: 24ÃV supply (I/O) / functional ground: 500 VÃAC, 50 Hz, 1 min. |
Connection data | Connection technology Connection name: Inline connector pluggable: yes Conductor connection Connection method: Spring-cage connection Conductor cross section rigid: 0.2 mm² ... 1.5 mm² Conductor cross section flexible: 0.2 mm² ... 1.5 mm² Conductor cross section AWG: 24 ... 16 Inline connector Connection method: Spring-cage connection Conductor cross section, rigid: 0.2 mm² ... 1.5 mm² Conductor cross section, flexible: 0.2 mm² ... 1.5 mm² Conductor cross section AWG: 24 ... 16 |
Environmental and real-life conditions | Ambient conditions Ambient temperature (operation): -25°C ... 55°C Degree of protection: IP20 Air pressure (operation): 80 kPa ... 108 kPa (up to 2000Ãm above sea level) Air pressure (storage/transport): 66 kPa ... 108 kPa (up to 3500Ãm above sea level) Ambient temperature (storage/transport): -25°C ... 70°C Permissible humidity (operation): 10 % ... 85 % (Take suitable measures against increased air humidity within the permitted temperature range.) Permissible humidity (storage/transport): 10 % ... 85 % (Take suitable measures against increased air humidity within the permitted temperature range.) |
Standards and regulations | Protection class: III (IEC 61140, ENÃ61140, VDEÃ0140-1) |
Mounting | Mounting type: DIN rail mounting |
Description other products