Industrial Automation
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/8f70464ada73cf4fa8957d52a1c72d22/-S204x204-FJPG Width: 22.5 mm Height: 99 mm Depth: 114.5 mm |
Notes | Utilization restriction CCCex note: Use in potentially explosive areas is not permitted in China. |
Material specifications | Color: gray |
Interfaces | Data: HART FSK Transmission speed: 1200 bps Connection method: Screw connection No. of channels: 4 |
Product properties | Product type: I/O component MTBF: 359 Years (Siemens model SN29500, temperature 40°C, env. factor 1.5 and stress factor 50%) |
Electrical properties | Test voltage data interface/power supply: 500 VAC Test voltage data interfaces: 500 VAC Supply Supply voltage range: 19.2 VDC ... 30 VDC (supplied from the bus) Typical current consumption: 44 mA (at 24 V DC) |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -40°C ... 70°C -40°F ... 158°F Ambient temperature (storage/transport): -40°C ... 85°C |
Approvals | Conformity/Approvals Conformance: CE-compliant Noxious gas test: ISA-S71.04-1985 G3 Harsh Group A Ex data ATEX: ï II 3 G Ex nA IIC T4 Gc DEMKO 17 ATEX 1749X IECEx: IECEx ULD 17.0020X Ex nA IIC T4 Gc UL, USA / Canada: Class I, Div. 2, Groups A, B, C, D |
Mounting | Mounting type: DIN rail mounting Assembly instructions: on standard DIN rail NS 35 in accordance with EN 60715 Mounting position: any |
ECLASS | ECLASS-11.0: 27242208 ECLASS-12.0: 27242208 ECLASS-13.0: 27242208 |
ETIM | ETIM 9.0: EC001423 |
UNSPSC | UNSPSC 21.0: 32151700 |
Description other products