Industrial Automation
Notes | Utilization restriction CCCex note: Use in potentially explosive areas is not permitted in China. |
Product properties | Product type: Ethernet extenders MTTF: 506 Years (SN29500 standard, temperature25°C, operating cycle21%) 260 Years (SN29500 standard, temperature40°C, operating cycle34.25%) 110 Years (SN29500 standard, temperature40°C, operating cycle100%) |
System properties | Functionality Basic functions: Ethernet extenders in accordance with ITU-T G.991.2 |
Electrical properties | Electrical isolation: VCC // Ethernet // DSL (A) // DSL (B) // FE Maximum power dissipation for nominal condition: 4.8 W Mains type: Permanent line Test voltage data interface/power supply: 500 VAC (In accordance with EN/IEC 60079-7, observe the limitations in the specific conditions of use.) 1.5 kV AC (50Hz, 1min.) Supply Supply voltage range: 10 VDC ... 60 VDC Nominal supply voltage: 24 VDC ±5% Typical current consumption: 200 mA (24VDC) 90 mA (60VDC) 450 mA (10VDC) Function Status and diagnostic indicators: Display for warning, status and device information |
Output data | Signal Output name: Digital output Number of outputs: 2 Voltage output signal: 10 VDC ... 60 VDC (24VDC, depending on the operating voltage) Current output signal: ⤠500 mA (Short-circuit-proof) |
Connection data | Supply Connection method: Push-in spring connection |
Interfaces | Signal: Ethernet Web server: yes Basic functions: Ethernet extenders in accordance with ITU-T G.991.2 Data: Ethernet interface, 10/100Base-T(X) in accordance with IEEE 802.3 Serial transmission speed: 10/100 Mbps, auto negotiation Connection method: RJ45 jack, shielded 4 ports 10/100BaseT(X), auto negotiation and autocrossing No. of channels: 4 Transmission length: < 100 m (shielded twisted pair) Protocols supported: IPv4, IPv6, TCP/IP, HTTP, HTTPS Auxiliary protocols: ARP, DHCP(Client), PING, SNMP Data: SHDSL interface according to ITU-T G.991.2.bis Serial transmission speed: 4-wire operation: 64 kbps ... 30 Mbps 2-wire operation: 32 kbps ... 15.3 Mbps Connection method: Push-in spring connection No. of channels: 2 (2-wire operation) Transmission length: < 20 km (Depending on data rate and cable cross section) Single conductor/terminal point, rigid: 0.2 mm² ... 1.5 mm² Single-wire/terminal point, flexible: 0.2 mm² ... 2.5 mm² Single-wire/terminal point, rigid AWG max.: 16 Single-wire/terminal point, rigid AWG min.: 24 |
Dimensions | Width: 60 mm Height: 130 mm Depth: 160 mm |
Material specifications | Material: Aluminum / steel sheet DC01 |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -25°C ... 60°C -25°C ... 0°C (Display inactivity can occur, image changes may take several seconds) 55°C ... 60°C (Display contrast can deteriorate) Ambient temperature (storage/transport): -40°C ... 85°C Altitude: ⤠2500 m (For restrictions, see the manufacturer's declaration for altitude operation) Max. permissible relative humidity (operation): < 60 % (At an ambient operating temperature >70°C) Permissible humidity (operation): 10 % ... 95 % (non-condensing) Permissible humidity (storage/transport): 10 % ... 95 % (non-condensing) |
Approvals | CE Certificate: CE-compliant ATEX Identification: ï II 3 G Ex ec IIC T4 Gc Certificate: PxCIF16ATEX2702253X Note: Please follow the special installation instructions in the documentation! UKEX Identification: ï II 3 G Ex ec IIC T4 Gc Certificate: PxCIMA22UKEX2702253X UL, USA/Canada Identification: 508 Listed Corrosive gas test Identification: ISA-S71.04-1985 G3 Harsh Group A |
EMC data | Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU Electrostatic discharge Standards/regulations: EN61000-4-2 Electrostatic dischargeâ Contact discharge: ± 6 kV Discharge in air: ± 8 kV Indirect discharge: ± 6 kV Comments: Criterion B Electromagnetic HF field Standards/regulations: EN61000-4-3 Electromagnetic HF fieldâ Frequency range: 80 MHz ... 3 GHz Field intensity: 10 V/m Comments: Criterion A Fast transients (burst) Standards/regulations: EN61000-4-4 Fast transients (burst)â Input: ± 2 kV Signal: ± 2 kV Comments: Criterion B Surge current load (surge) Standards/regulations: EN61000-4-5 Surge current load (surge)â Input: ± 0.5 kV (Symmetrical, unshielded supply line) ± 1 kV (Asymmetrical, unshielded supply line) Output: ± 1 kV (asymmetrical, unshielded) Signal: ± 1 kV (asymmetrical, shielded Ethernet cable) ± 4 kV (asymmetrical: line to ground, unshielded SHDSL cable) ± 2 kV (symmetrical: line to line, unshielded SHDSL cable) Comments: Criterion B Conducted interference Standards/regulations: EN61000-4-6 Conducted interferenceâ Frequency range: 0.15 MHz ... 80 MHz Comments: Criterion A Voltage: 10 V Emitted interference Standards/regulations: EN55011 Comments: Class A, industrial applications Criteria Criterion A: Normal operating behavior within the specified limits. Criterion B: Temporary impairment to operational behavior that is corrected by the device itself. |
Standards and regulations | Standards/regulations: EN50121-4 |
Mounting | Mounting type: DIN rail: 35 mm Assembly instructions: The product can be snapped onto all 35 mm DIN rails in accordance with EN60715. |
ECLASS | ECLASS-11.0: 19170407 ECLASS-12.0: 19170407 ECLASS-13.0: 19170407 |
ETIM | ETIM 9.0: EC000309 |
UNSPSC | UNSPSC 21.0: 43223100 |
Description other products