Industrial Automation

Mechatronics

Industrial Safety

Panel Components

Sensors and Systems of Vision

Pneumatics

Network Comunications

Automation Cables

Design Software

Access services

Enter your reserved area

Access services

Enter your reserved area

PHOENIX CONTACT 2702654
PHOENIX CONTACT 2702654
PHOENIX CONTACTNot available

AXL F DI8/2 48/60DC 1F - Digital module

AxiolineF, Digital input module, Digital inputs: 8, 48 VDC / 60 VDC, connection technology: 2-conductor, corresponds to standard IEC 61850-3, transmission speed in the local bus:100 Mbps, degree of protection: IP20, including bus base module and AxiolineF connectors
Product Code: 2702654
Partner cod.: 2702654
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Download
Tecnichal data
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/c1416576ed7aaf4e91ee7183ca7f3cde/-S204x204-FJPG
Width: 53.6 mm
Height: 126.1 mm
Depth: 54 mm
Note on dimensions: The depth applies when a THÂ35-7.5 DIN rail is used (in accordance with ENÂ60715).
InterfacesAxiolineÂFÂlocal bus
Number of interfaces: 2
Connection method: Bus base module
Transmission speed: 100 Mbps
System propertiesModule
Input address area: 1 Byte
Output address area: 0 Byte
Required parameter data: 3 Byte
Required configuration data: 6 Byte
Input dataDigital
Input name: Digital inputs
Description of the input: EN 61131-2 type 1
Number of inputs: 8
Connection method: Push-in connection
Connection technology: 2-conductor
Input voltage: 48 V (Nominal voltage)
60 V (Nominal voltage)
max. 100 VÂDC
Input voltage range: -100 VÂDC ... 100 VÂDC
Input voltage range "0" signal: -12 VÂDC ... 12 VÂDC
Input voltage range "1" signal: 32 VÂDC ... 100 VÂDC
Nominal input voltage UIN: 48 VÂDC
60 VÂDC
Nominal input current at UIN: 2.5 mA
Input filter time: < 1 ms
Protective circuit: Polarity reversal protection of the inputs
Product propertiesType: block modular
Product type: I/O component
Product family: AxiolineÂF
Mounting position: any (no temperature derating)
Nominal mounting position: wall mounting on horizontal DIN rail
Scope of delivery: including bus base module and AxiolineÂF connectors
Insulation characteristics
Overvoltage category: III (EN 61010-2-201/IEC 61010-2-201)
Pollution degree: 2
Electrical propertiesPotentials: AxiolineÂF local bus supply (U
Supply voltage: 5 VÂDC (via bus base module)
Current draw: max. 120 mA
Power consumption: max. 600 mW
Electrical isolation/isolation of the voltage ranges
Test voltage: I/Os / logic: 4 kV
5 kV
Test voltage: I/O/functional ground: 4 kV
5 kV
Test voltage: I/O / I/O (adjacent connectors): 2.5 kV
Test voltage: Logic/functional ground: 1 kV
Connection dataConnection technology
Connection name: AxiolineÂF connector
Note on the connection method: Please observe the information provided on conductor cross sections in the âہ“AxiolineÂF: system and installation” user manual.
Conductor connection
Connection method: Push-in connection
Conductor cross section rigid: 0.2 mm² ... 1.5 mm²
Conductor cross section flexible: 0.2 mm² ... 1.5 mm²
Conductor cross section AWG: 24 ... 16
Stripping length: 8 mm
AxiolineÂF connector
Connection method: Push-in connection
Note on the connection method: Please observe the information provided on conductor cross sections in the âہ“AxiolineÂF: system and installation” user manual.
Conductor cross section, rigid: 0.2 mm² ... 1.5 mm²
Conductor cross section, flexible: 0.2 mm² ... 1.5 mm²
Conductor cross section AWG: 24 ... 16
Stripping length: 8 mm
Environmental and real-life conditionsAmbient conditions
Ambient temperature (operation): -25°C ... 60°C
Degree of protection: IP20
Air pressure (operation): 70 kPa ... 106 kPa (up to 3000Âm above sea level)
Air pressure (storage/transport): 70 kPa ... 106 kPa (up to 3000Âm above sea level)
Ambient temperature (storage/transport): -40°C ... 85°C
Permissible humidity (operation): 5 % ... 95 % (non-condensing)
Permissible humidity (storage/transport): 5 % ... 95 % (non-condensing)
MountingMounting type: DIN rail mounting
Mounting position: any (no temperature derating)
Nominal mounting position: wall mounting on horizontal DIN rail
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_01328.pdf

Approvals_01329.pdf

Approvals_01759.pdf

Data_sheet_03362.pdf

Manual_00006.pdf

Manual_00007.pdf

Manufacturer_declaration_00805.pdf

Manufacturer_declaration_05480.pdf

Manufacturer_declaration_05562.pdf

Manufacturer_declaration_05563.pdf

Manufacturer_declaration_14704.pdf

Package_slip_00728.pdf

Product_information_00033.pdf

Product_information_00322.pdf

Technical_drawing_37854.pdf

Various_00004.pdf