Industrial Automation
AXL F IF CAN 1H - Communication module


Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/172c7c5767999646b422d3edebda44f8/-S204x204-FJPG Width: 35 mm Height: 126.1 mm Depth: 54 mm Note on dimensions: The depth applies when a THÃ35-7.5 DIN rail is used (in accordance with ENÃ60715). |
Interfaces | AxiolineÃFÃlocal bus Number of interfaces: 2 Connection method: Bus base module Transmission speed: 100 Mbps CAN bus Connection method: Push-in connection Transmission speed range: 10 kbps ... 1 Mbps (Default: 20Ãkbps) Transmission physics: CAN bus according to standard ISOÃ11898-2 (high-speed CAN) No. of channels: 1 |
System properties | Module Process data channel: 64 Byte Input address area: 64 Byte Output address area: 64 Byte Required parameter data: 1 Byte Required configuration data: 7 Byte |
Product properties | Type: block modular Product type: I/O component Product family: AxiolineÃF Mounting position: any (no temperature derating) Insulation characteristics Overvoltage category: II (IEC 60664-1, ENÃ60664-1) Pollution degree: 2 (IEC 60664-1, ENÃ60664-1) |
Electrical properties | Potentials: AxiolineÃF local bus supply (U Supply voltage: 5 VÃDC (via bus base module) Current draw: max. 150 mA Power consumption: max. 0.75 W Potentials: Feed-in of supply voltage (U Supply voltage: 24 VÃDC Supply voltage range: 19.2 VÃDC ... 30 VÃDC including all tolerances, including ripple Current draw: max. 25 mA Power consumption: max. 0.6 W Electrical isolation/isolation of the voltage ranges Test voltage: 5ÃV supply of the local bus (UBus) / 24ÃV supply (I/Os): 500 VÃAC, 50 Hz, 1 min. Test voltage: 5ÃV supply of the local bus (UBus) / CAN I/Os: 500 VÃAC, 50 Hz, 1 min. Test voltage: 24 V supply (I/O) / CAN I/O: 500 VÃAC, 50 Hz, 1 min. Test voltage: 5ÃV supply of the local bus (UBus) / functional ground: 500 VÃAC, 50 Hz, 1 min. Test voltage: 24ÃV supply (I/O) / functional ground: 500 VÃAC, 50 Hz, 1 min. |
Connection data | Connection technology Connection name: AxiolineÃF connector Note on the connection method: Please observe the information provided on conductor cross sections in the ââ¬Ã AxiolineÃF: system and installationâ⬠user manual. Conductor connection Connection method: Push-in connection Conductor cross section rigid: 0.2 mm² ... 1.5 mm² Conductor cross section flexible: 0.2 mm² ... 1.5 mm² Conductor cross section AWG: 24 ... 16 Stripping length: 8 mm AxiolineÃF connector Connection method: Push-in connection Note on the connection method: Please observe the information provided on conductor cross sections in the ââ¬Ã AxiolineÃF: system and installationâ⬠user manual. Conductor cross section, rigid: 0.2 mm² ... 1.5 mm² Conductor cross section, flexible: 0.2 mm² ... 1.5 mm² Conductor cross section AWG: 24 ... 16 Stripping length: 8 mm |
Environmental and real-life conditions | Ambient conditions Ambient temperature (operation): -25°C ... 60°C Degree of protection: IP20 Air pressure (operation): 70 kPa ... 106 kPa (up to 3000Ãm above sea level) Air pressure (storage/transport): 70 kPa ... 106 kPa (up to 3000Ãm above sea level) Ambient temperature (storage/transport): -40°C ... 85°C Permissible humidity (operation): 5 % ... 95 % (non-condensing) Permissible humidity (storage/transport): 5 % ... 95 % (non-condensing) |
Standards and regulations | Protection class: III (IEC 61140, ENÃ61140, VDEÃ0140-1) |
Mounting | Mounting type: DIN rail mounting Mounting position: any (no temperature derating) |