Industrial Automation
AXL F SSDOR4/2 1F - Safety module


Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/9bf47cad1f9a594387de8d805d9e0343/-S204x204-FJPG Width: 53.6 mm Height: 126.1 mm Depth: 54 mm Note on dimensions: Housing dimensions |
Interfaces | AxiolineÃFÃlocal bus Connection method: Bus base module |
System properties | Module Input address area: 8 Byte Output address area: 8 Byte Required parameter data: 1 Byte Required configuration data: 7 Byte |
Input data | Digital Input name: Signal inputs Number of inputs: 2 Input voltage: Power supply from clock outputs UT1 and UT2 Nominal input current at UIN: typ. 3.2 mA |
Output data | Digital Output name: Outputs OUT24V_0Ãand OUT24V_1 Number of outputs: 2 Nominal output voltage: Power supply from U0 or U1 Relay Number of outputs: 4 (floating) Contact switching type: N/O contact Switching voltage: min. 12 V AC/DC max. 30 V AC/DC Switching current: min. 3 mA max. 6 A (30ÃVÃDC) Switching capacity: min. 60 mW Limiting continuous current: 6 A Mechanical service life: 10x 106 cycles Output fuse: 6 A gL/gG (See ââ¬Ã Application examplesâ⬠section) |
Product properties | Type: modular Product type: I/O component Product family: AxiolineÃF Mounting position: any Application: Functional safety Operating mode: SafetyBridge Insulation characteristics Overvoltage category: II (IEC 60664-1) Pollution degree: 2 (IEC 60664-1) |
Electrical properties | Transmission medium: Copper Potentials Protection: max. 500 mA slow-blow (for UI) max. 6 A gL/gG () Protective circuit: Polarity reversal protection of the supply voltage; parallel protection against polarity reversal for a limited period of time Surge voltage detection; at 31ÃV Undervoltage detection; at 17ÃV Surge protection of the supply voltage; electronic (35 V, 0.5 s) Potentials: AxiolineÃF local bus supply (U Supply voltage: 5 VÃDC (via bus base module) Current draw: max. 163 mA (at UBus 5ÃVÃDC) typ. 93 mA (at UBus 5ÃVÃDC) Potentials: Supply voltage U Supply voltage: 24 VÃDC Supply voltage range: 19.2 VÃDC ... 30.2 VÃDC (including all tolerances, including ripple) Current draw: max. 30 mA typ. 10 mA (Power supply from UI with 30ÃVÃDC, all inputs set) Potentials: Feed-in U Supply voltage: 24 VÃDC Supply voltage range: 19.2 VÃDC ... 30 VÃDC (including all tolerances, including ripple) Current draw: max. 6 A typ. 1.6 mA (Power supply from U0 with 30ÃV DC, all inputs set without load) |
Connection data | Connection technology Connection name: I/O Note on the connection method: Note the specification in the section Conductor cross sections, and stripping and insertion lengths. Conductor connection Connection method: Push-in connection Conductor cross section rigid: 0.5 mm² ... 1.5 mm² Conductor cross section flexible: 0.5 mm² ... 1.5 mm² Conductor cross section AWG: 20 ... 16 Stripping length: 8 mm I/O Connection method: Push-in connection Note on the connection method: Note the specification in the section Conductor cross sections, and stripping and insertion lengths. Conductor cross section, rigid: 0.5 mm² ... 1.5 mm² Conductor cross section, flexible: 0.5 mm² ... 1.5 mm² Conductor cross section AWG: 20 ... 16 Stripping length: 8 mm |
Environmental and real-life conditions | Ambient conditions Ambient temperature (operation): -35°C ... 60°C Degree of protection: IP20 Degree of protection at installation location: min. IP54 Air pressure (operation): 70 kPa ... 108 kPa Air pressure (storage/transport): 66 kPa ... 108 kPa Ambient temperature (storage/transport): -40°C ... 85°C |
Standards and regulations | Protection class: III (IEC 61140-1) Air clearances and creepage distances Air clearances and creepage distances: IEC 60664-1 |
Mounting | Mounting type: DIN rail mounting Mounting position: any |