Industrial Automation
IL PN BK DI8 DO4 2TX-PAC - Bus coupler


Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/70f9f0a5c5a6dc49a176841af248e138/-S204x204-FJPG Width: 80 mm Height: 119.8 mm Depth: 71.5 mm Note on dimensions: Specfications with connectors |
Notes | Utilization restriction CCCex note: Use in potentially explosive areas is not permitted in China. |
Interfaces | PROFINET Number of interfaces: 2 Connection method: RJ45 jack Note on the connection method: Auto negotiation and autocrossing Transmission speed: 100 Mbps (acc. to PROFINET standard) Transmission physics: Ethernet in RJ45 twisted pair Inline local bus Connection method: Inline data jumper Transmission speed: 500 kbps / 2 Mbps (automatic detection, no combined system) |
System properties | System limits Number of supported devices: max. 63 (per station) Number of local bus devices that can be connected: max. 61 (The on-board I/Os are two devices) Number of devices with parameter channel: max. 16 Number of supported branch terminals with remote bus branch: 0 PROFINET Device function: PROFINET device Update rate: min. 1 ms (depending on the size of the bus system) Module ID code (hex): none Input address area: 8 bit Output address area: 4 bit Register length: 16 bit |
Input data | Digital Input name: Digital inputs Description of the input: EN 61131-2 type 1 Number of inputs: 8 Connection method: Inline connector Connection technology: 3-conductor Input voltage: 24 VÃDC Input voltage range "0" signal: -30 VÃDC ... 5 VÃDC Input voltage range "1" signal: 15 VÃDC ... 30 VÃDC Nominal input voltage UIN: 24 VÃDC Nominal input current at UIN: typ. 3 mA Typical input current per channel: typ. 3 mA Typical response time: approx. 500 õs Filter time: 3 ms Delay at signal change from 0 to 1: 5 ms Delay at signal change from 1 to 0: 5 ms |
Output data | Digital Output name: Digital outputs Connection method: Inline connector Connection technology: 3-conductor Number of outputs: 4 Protective circuit: Short-circuit and overload protection; Freewheeling circuit in the output driver Output voltage: 24 VÃDC -1ÃV (At nominal current) Maximum output current per module: max. 2 A Nominal output voltage: 24 VÃDC Output current when switched off: max. 10 õA (When not loaded, a voltage can be measured even at an output that is not set.) Nominal load, inductive: 12 VA (1.2 H, 48 é) Nominal load, lamp: 12 W Nominal load, ohmic: 12 W Reverse voltage resistance to short pulses: Reverse voltage proof Behavior with overload: Auto restart Behavior with inductive overload: Output can be destroyed Behavior at voltage switch-off: The output follows the power supply without delay Signal delay: typ. 1.2 ms Overcurrent shut-down: min. 0.7 A |
Product properties | Type: modular Product type: I/O component Product family: Inline No. of channels: 12 Diagnostics messages: Short-circuit or overload of the digital outputs yes Sensor supply failure yes Failure of the actuator supply yes Insulation characteristics Overvoltage category: II (IEC 60664-1, ENÃ60664-1) Pollution degree: 2 (IEC 60664-1, ENÃ60664-1) |
Electrical properties | No. of channels: 12 Maximum power dissipation for nominal condition: max. 3.3 W Potentials Power consumption: typ. 3 W (entire device) Protective circuit: Surge protection (segment supply, main supply, bus coupler supply); Suppressor diode, 35 V DC Reverse polarity protection (segment supply, main supply, bus coupler supply); Suppressor diode, 35 V DC Potentials: Bus coupler supply U Supply voltage: 24 VÃDC (via Inline connector) Supply voltage range: 19.2 VÃDC ... 30 VÃDC (including all tolerances, including ripple) Current draw: max. 0.91 A (with max. number of connected I/O terminal blocks) typ. 138 mA Potentials: Communications power (U Supply voltage: 7.5 VÃDC Potentials: Supply of analog modules (U Supply voltage: 24 VÃDC Supply voltage range: 19.2 VÃDC ... 30 VÃDC (including all tolerances, including ripple) Potentials: Main circuit supply (U Supply voltage: 24 VÃDC (via Inline connector) Supply voltage range: 19.2 VÃDC ... 30 VÃDC (including all tolerances, including ripple) Current draw: max. 8 AÃDC min. 3 mA (without connected peripherals) Potentials: Segment circuit supply (U Supply voltage: 24 VÃDC (via Inline connector) Supply voltage range: 19.2 VÃDC ... 30 VÃDC (including all tolerances, including ripple) Current draw: max. 8 AÃDC min. 3 mA (without connected peripherals) Electrical isolation/isolation of the voltage ranges Test voltage: PROFINET interface 1 / PROFINET interface 2: 500 VÃAC, 50 Hz, 1 min. Test voltage: PROFINET interface 1 / communications power (UBK, UL, UANA): 500 VÃAC, 50 Hz, 1 min. Test voltage: PROFINET interface 1 / I/O (UM, US): 500 VÃAC, 50 Hz, 1 min. Test voltage: PROFINET interface 1 / functional ground: 500 VÃAC, 50 Hz, 1 min. Test voltage: PROFINET interface 2 / communications power (UBK, UL, UANA): 500 VÃAC, 50 Hz, 1 min. Test voltage: PROFINET interface 2 / I/O (UM, US): 500 VÃAC, 50 Hz, 1 min. Test voltage: PROFINET interface 2 / functional ground: 500 VÃAC, 50 Hz, 1 min. Test voltage: Communications power (UBK, UL, UANA) / I/O (UM, US): 500 VÃAC, 50 Hz, 1 min. Test voltage: Communications power (UBK, UL, UANA) / functional ground: 500 VÃAC, 50 Hz, 1 min. Test voltage: I/O (UM, US) / functional ground: 500 VÃAC, 50 Hz, 1 min. |
Connection data | Connection technology Connection name: Inline connector Conductor connection Connection method: Spring-cage connection Conductor cross section rigid: 0.08 mm² ... 1.5 mm² Conductor cross section flexible: 0.08 mm² ... 1.5 mm² Conductor cross section AWG: 28 ... 16 Stripping length: 8 mm Inline connector Connection method: Spring-cage connection Conductor cross section, rigid: 0.08 mm² ... 1.5 mm² Conductor cross section, flexible: 0.08 mm² ... 1.5 mm² Conductor cross section AWG: 28 ... 16 Stripping length: 8 mm |
Environmental and real-life conditions | Ambient conditions Ambient temperature (operation): -25°C ... 55°C (observe derating) Degree of protection: IP20 Air pressure (operation): 70 kPa ... 106 kPa (up to 3000Ãm above sea level) Air pressure (storage/transport): 70 kPa ... 106 kPa (up to 3000Ãm above sea level) Ambient temperature (storage/transport): -40°C ... 85°C Permissible humidity (operation): 10 % ... 95 % (non-condensing) Permissible humidity (storage/transport): 10 % ... 95 % (non-condensing) |
Standards and regulations | Protection class: III (IEC 61140, ENÃ61140, VDEÃ0140-1) |
Mounting | Mounting type: DIN rail mounting |
Description other products