Industrial Automation
Notes | Utilization restriction CCCex note: Use in potentially explosive areas is not permitted in China. |
Product properties | Product type: Media converter MTTF: 849 Years (SN29500 standard, temperature25°C, operating cycle21%) 392 Years (SN29500 standard, temperature40°C, operating cycle34.25%) 163 Years (SN29500 standard, temperature40°C, operating cycle100%) MTBF: 406 Years (Telcordia standard, 25°C temperature, 21% operating cycle (5 days a week, 8 hours a day)) 92 Years (Telcordia standard, 40°C temperature, 34.25% operating cycle (5 days a week, 12 hours a day)) |
Electrical properties | Electrical isolation: VCC // RS-485 Maximum power dissipation for nominal condition: 1.32 W Test voltage data interface/power supply: 1.5 kVrms (50Hz, 1min.) Supply Supply voltage range: 18 VDC ... 32 VDC (via pluggable COMBICON screw terminal block) Nominal supply voltage: 24 VDC (in acc. with UL) Typical current consumption: 55 mA (24VDC) Max. current consumption: 90 mA ⤠2 A (For operation in a joining station, via the DIN rail connector) |
Output data | Switching Output name: Relay output Output description: Alarm output Number of outputs: 1 Maximum switching voltage: 60 VDC (Resistive Load, General Load) 30 VAC (Resistive load) 42 VAC (peak, resistive load) Limiting continuous current: 0.46 A |
Connection data | Supply Connection method: COMBICON plug-in screw terminal block Stripping length: 7 mm Tightening torque: 0.56 Nm ... 0.79 Nm |
Interfaces | Bit distortion, input: ± 35 % (permitted) Bit distortion, output: < 6.25 % Bit delay: < 1 bit (DIP7 = OFF, standard operation) 11 bit (DIP7 =ON, redundancy operation) Signal: PROFIBUS Data: optical FO No. of channels: 1 Transmit capacity, minimum: -3.4 dBm (50/125üm, multimode fiberglass) -4.7 dBm (62.5/125üm, multimode fiberglass) -5.5 dBm (9/125üm, singlemode fiberglass) Transmission length incl. 3 dB system reserve: 25 km (With F-G 50/125 0.7 dB/km at 1300 nm) 22 km (with F-G 62.5/125 0.8 dB/km at 1300 nm) 45 km (With F-E 9/125 0,4 dB/km at 1300 nm) Transmission protocol: Protocol-transparent to the RS-485 interface Connection method: SC duplex Wavelength: 1300 nm Minimum receiver sensitivity: -25.5 dBm (Multi mode) -26.5 dBm (Singlemode) Maximum receiver sensitivity: 0 dBm Transmission medium: Multi-mode fiberglass Single-mode fiberglass Data: PROFIBUS acc. to IEC 61158, RS-485 2-wire, half duplex, automatic control Serial transmission speed: ⤠12 Mbps Connection method: D-SUB-9 female connector Transmission length: ⤠1200 m (depending on the data rate, with shielded, twisted pair data cable) Single conductor/terminal point, rigid: 0.2 mm² ... 2.5 mm² Single-wire/terminal point, flexible: 0.2 mm² ... 2.5 mm² Max. AWG conductor cross section, flexible: 14 Min. AWG conductor cross section, flexible: 24 Single-wire/terminal point, rigid AWG max.: 14 Single-wire/terminal point, rigid AWG min.: 24 Transmission medium: 2-wire twisted pair, shielded File format/coding: UART (11 Bit, NRZ) Data direction switching: Automatic control Output nominal voltage: 5 VDC ±0.25 (50 mA) |
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/91b384dadfc51747a6197f94ade1679e/-S204x204-FJPG Width: 35 mm Height: 105 mm Depth: 106 mm |
Material specifications | Material: PA 6.6-FR |
Cable/line | FO cable Fiber types: 50/125 µm 62.5/125 µm 9/125 µm Fiberglass |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -20°C ... 60°C Ambient temperature (storage/transport): -40°C ... 85°C Altitude: ⤠5000 m (For restrictions, see the manufacturer's declaration for altitude operation) ⤠2000 m (Hazardous locations) Permissible humidity (operation): 30 % ... 95 % (non-condensing) |
Approvals | CE Certificate: CE-compliant ATEX Identification: ï II 3 G Ex ec IIC T4 Gc Certificate: UL 21 ATEX 2550X Note: Please follow the special installation instructions in the documentation! IECEx Identification: Ex ec IIC T4 Gc Certificate: IECEx ULD 21.00013X UL, USA/Canada Identification: Class I, Zone 2, AEx ec IIC T4 Gc Ex ec IIC T4 Gc X Class I, Div. 2, Groups A, B, C, D Corrosive gas test Identification: ISA-S71.04-1985 G3 Harsh Group A |
EMC data | Noise immunity: EN 61000-6-2:2005 Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU Noise emission: EN 55011 Electrostatic discharge Standards/regulations: EN61000-4-2 Electrostatic dischargeâ Contact discharge: ± 6 kV Discharge in air: ± 8 kV Comments: Criterion B Electromagnetic HF field Standards/regulations: EN61000-4-3 Electromagnetic HF fieldâ Field intensity: 10 V/m Comments: Criterion A Fast transients (burst) Standards/regulations: EN61000-4-4 Fast transients (burst)â Input: ± 2 kV Signal: ± 2 kV Comments: Criterion B Surge current load (surge) Standards/regulations: EN61000-4-5 Surge current load (surge)â Input: ± 0.5 kV Signal: ± 1 kV Comments: Criterion B Conducted interference Standards/regulations: EN61000-4-6 Conducted interferenceâ Comments: Criterion A Voltage: 10 V Emitted interference Standards/regulations: EN55011 Comments: Class A, industrial applications Criteria Criterion A: Normal operating behavior within the specified limits. Criterion B: Temporary impairment to operational behavior that is corrected by the device itself. |
Standards and regulations | Free from substances that could impair the application of coating: in accordance with VW-AUDI-Seat central standard P-VW 3.10.7 57 65 0 |
Mounting | Mounting type: DIN rail mounting |
ECLASS | ECLASS-11.0: 19170411 ECLASS-12.0: 19170411 ECLASS-13.0: 19170411 |
ETIM | ETIM 9.0: EC001467 |
UNSPSC | UNSPSC 21.0: 43201500 |
Description other products