Industrial Automation

Mechatronics

Industrial Safety

Panel Components

Sensors and Systems of Vision

Pneumatics

Network Comunications

Automation Cables

Design Software

Access services

Enter your reserved area

Access services

Enter your reserved area

PHOENIX CONTACT 2708559
PHOENIX CONTACT 2708559
PHOENIX CONTACTNot available

PSI-MOS-PROFIB/FO1300 E - FO converters

Fiber optic converter with integrated optical diagnostics, alarm contact, for PROFIBUS up to 12 Mbps, termination device with one fiber optic interface (SC-Duplex), 1300 nm, for fiberglass cable
Product Code: 2708559
Partner cod.: 2708559
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Download
Tecnichal data
NotesUtilization restriction
CCCex note: Use in potentially explosive areas is not permitted in China.
Product propertiesProduct type: Media converter
MTTF: 849 Years (SN29500 standard, temperature25°C, operating cycle21%)
392 Years (SN29500 standard, temperature40°C, operating cycle34.25%)
163 Years (SN29500 standard, temperature40°C, operating cycle100%)
MTBF: 406 Years (Telcordia standard, 25°C temperature, 21% operating cycle (5 days a week, 8 hours a day))
92 Years (Telcordia standard, 40°C temperature, 34.25% operating cycle (5 days a week, 12 hours a day))
Electrical propertiesElectrical isolation: VCC // RS-485
Maximum power dissipation for nominal condition: 1.32 W
Test voltage data interface/power supply: 1.5 kVrms (50Hz, 1min.)
Supply
Supply voltage range: 18 VDC ... 32 VDC (via pluggable COMBICON screw terminal block)
Nominal supply voltage: 24 VDC (in acc. with UL)
Typical current consumption: 55 mA (24VDC)
Max. current consumption: 90 mA
≤ 2 A (For operation in a joining station, via the DIN rail connector)
Output dataSwitching
Output name: Relay output
Output description: Alarm output
Number of outputs: 1
Maximum switching voltage: 60 VDC (Resistive Load, General Load)
30 VAC (Resistive load)
42 VAC (peak, resistive load)
Limiting continuous current: 0.46 A
Connection dataSupply
Connection method: COMBICON plug-in screw terminal block
Stripping length: 7 mm
Tightening torque: 0.56 Nm ... 0.79 Nm
InterfacesBit distortion, input: ± 35 % (permitted)
Bit distortion, output: < 6.25 %
Bit delay: < 1 bit (DIP7 = OFF, standard operation)
11 bit (DIP7 =ON, redundancy operation)
Signal: PROFIBUS
Data: optical FO
No. of channels: 1
Transmit capacity, minimum: -3.4 dBm (50/125μm, multimode fiberglass)
-4.7 dBm (62.5/125μm, multimode fiberglass)
-5.5 dBm (9/125μm, singlemode fiberglass)
Transmission length incl. 3 dB system reserve: 25 km (With F-G 50/125 0.7 dB/km at 1300 nm)
22 km (with F-G 62.5/125 0.8 dB/km at 1300 nm)
45 km (With F-E 9/125 0,4 dB/km at 1300 nm)
Transmission protocol: Protocol-transparent to the RS-485 interface
Connection method: SC duplex
Wavelength: 1300 nm
Minimum receiver sensitivity: -25.5 dBm (Multi mode)
-26.5 dBm (Singlemode)
Maximum receiver sensitivity: 0 dBm
Transmission medium: Multi-mode fiberglass
Single-mode fiberglass
Data: PROFIBUS acc. to IEC 61158, RS-485 2-wire, half duplex, automatic control
Serial transmission speed: ≤ 12 Mbps
Connection method: D-SUB-9 female connector
Transmission length: ≤ 1200 m (depending on the data rate, with shielded, twisted pair data cable)
Single conductor/terminal point, rigid: 0.2 mm² ... 2.5 mm²
Single-wire/terminal point, flexible: 0.2 mm² ... 2.5 mm²
Max. AWG conductor cross section, flexible: 14
Min. AWG conductor cross section, flexible: 24
Single-wire/terminal point, rigid AWG max.: 14
Single-wire/terminal point, rigid AWG min.: 24
Transmission medium: 2-wire twisted pair, shielded
File format/coding: UART (11 Bit, NRZ)
Data direction switching: Automatic control
Output nominal voltage: 5 VDC ±0.25 (50 mA)
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/91b384dadfc51747a6197f94ade1679e/-S204x204-FJPG
Width: 35 mm
Height: 105 mm
Depth: 106 mm
Material specificationsMaterial: PA 6.6-FR
Cable/lineFO cable
Fiber types: 50/125 µm
62.5/125 µm
9/125 µm
Fiberglass
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -20°C ... 60°C
Ambient temperature (storage/transport): -40°C ... 85°C
Altitude: ≤ 5000 m (For restrictions, see the manufacturer's declaration for altitude operation)
≤ 2000 m (Hazardous locations)
Permissible humidity (operation): 30 % ... 95 % (non-condensing)
ApprovalsCE
Certificate: CE-compliant
ATEX
Identification:  II 3 G Ex ec IIC T4 Gc
Certificate: UL 21 ATEX 2550X
Note: Please follow the special installation instructions in the documentation!
IECEx
Identification: Ex ec IIC T4 Gc
Certificate: IECEx ULD 21.00013X
UL, USA/Canada
Identification: Class I, Zone 2, AEx ec IIC T4 Gc
Ex ec IIC T4 Gc X
Class I, Div. 2, Groups A, B, C, D
Corrosive gas test
Identification: ISA-S71.04-1985 G3 Harsh Group A
EMC dataNoise immunity: EN 61000-6-2:2005
Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU
Noise emission: EN 55011
Electrostatic discharge
Standards/regulations: EN61000-4-2
Electrostatic discharge​
Contact discharge: ± 6 kV
Discharge in air: ± 8 kV
Comments: Criterion B
Electromagnetic HF field
Standards/regulations: EN61000-4-3
Electromagnetic HF field​
Field intensity: 10 V/m
Comments: Criterion A
Fast transients (burst)
Standards/regulations: EN61000-4-4
Fast transients (burst)​
Input: ± 2 kV
Signal: ± 2 kV
Comments: Criterion B
Surge current load (surge)
Standards/regulations: EN61000-4-5
Surge current load (surge)​
Input: ± 0.5 kV
Signal: ± 1 kV
Comments: Criterion B
Conducted interference
Standards/regulations: EN61000-4-6
Conducted interference​
Comments: Criterion A
Voltage: 10 V
Emitted interference
Standards/regulations: EN55011
Comments: Class A, industrial applications
Criteria
Criterion A: Normal operating behavior within the specified limits.
Criterion B: Temporary impairment to operational behavior that is corrected by the device itself.
Standards and regulationsFree from substances that could impair the application of coating: in accordance with VW-AUDI-Seat central standard P-VW 3.10.7 57 65 0
MountingMounting type: DIN rail mounting
Technical Specs
ECLASSECLASS-11.0: 19170411
ECLASS-12.0: 19170411
ECLASS-13.0: 19170411
ETIMETIM 9.0: EC001467
UNSPSCUNSPSC 21.0: 43201500
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Application_note_00152.pdf

Application_note_00155.pdf

Application_note_00159.pdf

Application_note_00156.pdf

Approvals_00056.pdf

Approvals_00057.pdf

Approvals_00842.pdf

Approvals_00843.pdf

Approvals_01763.pdf

Approvals_01790.pdf

Data_sheet_03077.pdf

Data_sheet_03406.pdf

Manufacturer_declaration_00485.pdf

Manufacturer_declaration_01521.pdf

Manufacturer_declaration_05546.pdf

Manufacturer_declaration_14826.pdf

Manufacturer_declaration_17707.pdf

Package_slip_01830.pdf

Technical_drawing_38029.pdf