Industrial Automation
PSI-MOS-RS232/FO1300 E - FO converters
![](https://www.technologybsa.com/wp-content/uploads/2023/08/copia.png)
![](https://www.technologybsa.com/wp-content/uploads/2023/08/copia.png)
Notes | Utilization restriction EMC note: EMC: class A product, see manufacturer's declaration in the download area Utilization restrictionâ CCCex note: Use in potentially explosive areas is not permitted in China. |
Product properties | Product type: Media converter MTTF: 942 Years (SN29500 standard, temperature25°C, operating cycle21%) 418 Years (SN29500 standard, temperature40°C, operating cycle34.25%) 172 Years (SN29500 standard, temperature40°C, operating cycle100%) MTBF: 549 Years (Telcordia standard, 25°C temperature, 21% operating cycle (5 days a week, 8 hours a day)) 113 Years (Telcordia standard, 40°C temperature, 34.25% operating cycle (5 days a week, 12 hours a day)) |
Electrical properties | Electrical isolation: VCC // V.24 (RS-232) Maximum power dissipation for nominal condition: 2.5 W Test voltage data interface/power supply: 1.5 kVrms (50Hz, 1min.) Supply Supply voltage range: 18 VDC ... 32 VDC Nominal supply voltage: 24 VDC (in acc. with UL) Typical current consumption: 100 mA (24VDC) Max. current consumption: ⤠2 A (For operation in a joining station, via the DIN rail connector) |
Output data | Switching Output name: Relay output Output description: Alarm output Number of outputs: 1 Maximum switching voltage: 60 VDC 42 VAC Limiting continuous current: 1 A |
Connection data | Supply Connection method: COMBICON plug-in screw terminal block Tightening torque: 0.56 Nm ... 0.79 Nm |
Interfaces | Bit distortion, input: ± 35 % (permitted) Bit distortion, output: < 6.25 % Signal: Modbus Transmission channels: 2 (1/1), RxD, TxD, full duplex Data: optical FO No. of channels: 1 Transmit capacity, minimum: -3.4 dBm (50/125üm, multimode fiberglass) -4.7 dBm (62.5/125üm, multimode fiberglass) -5.5 dBm (9/125üm, singlemode fiberglass) Transmission length incl. 3 dB system reserve: 27 km (With F-G 50/125 0.7 dB/km at 1300 nm) 22 km (with F-G 62.5/125 0.8 dB/km at 1300 nm) 45 km (With F-E 9/125 0,4 dB/km at 1300 nm) Transmission protocol: Transparent to protocol for RS-232 interface Connection method: SC duplex Wavelength: 1300 nm Minimum receiver sensitivity: -25.5 dBm (50/125üm, multimode fiberglass) -25.5 dBm (62.5/125üm, multimode fiberglass) -26.5 dBm (9/125üm, singlemode fiberglass) Maximum receiver sensitivity: 0 dBm Transmission medium: Multi-mode fiberglass Single-mode fiberglass Data: V.24 (RS-232) interface in acc. with ITU-T V.28, EIA/TIA-232, DIN66259-1 Serial transmission speed: 9.6Kbps...115.2Kbps Connection method: D-SUB9 plug Transmission length: ⤠15 m Single conductor/terminal point, rigid: 0.2 mm² ... 2.5 mm² Single-wire/terminal point, flexible: 0.2 mm² ... 2.5 mm² Max. AWG conductor cross section, flexible: 14 Min. AWG conductor cross section, flexible: 24 Single-wire/terminal point, rigid AWG max.: 14 Single-wire/terminal point, rigid AWG min.: 24 Transmission medium: Copper File format/coding: UART (11 Bit, NRZ) Data direction switching: Automatic control |
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/91b384dadfc51747a6197f94ade1679e/-S204x204-FJPG Width: 35 mm Height: 99 mm Depth: 105 mm |
Material specifications | Material: PA 6.6-FR |
Cable/line | FO cable Fiber types: 50/125 µm 9/125 µm Fiberglass |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -20°C ... 60°C Ambient temperature (storage/transport): -40°C ... 85°C Altitude: ⤠5000 m (For restrictions, see the manufacturer's declaration for altitude operation) Permissible humidity (operation): 30 % ... 95 % (non-condensing) |
Approvals | CE Certificate: CE-compliant ATEX Identification: ï II 3 G Ex nA nC IIC T4 Gc X Note: Please follow the special installation instructions in the documentation! UL, USA/Canada Identification: 508 Listed 508 Recognized Corrosive gas test Identification: ISA-S71.04-1985 G3 Harsh Group A |
EMC data | Noise immunity: EN 61000-6-2:2005 Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU Noise emission: EN 55011 Electrostatic discharge Standards/regulations: EN61000-4-2 Electrostatic dischargeâ Contact discharge: ± 6 kV Discharge in air: ± 8 kV Comments: Criterion B Electromagnetic HF field Standards/regulations: EN61000-4-3 Electromagnetic HF fieldâ Field intensity: 10 V/m Comments: Criterion A Fast transients (burst) Standards/regulations: EN61000-4-4 Fast transients (burst)â Input: ± 2 kV Signal: ± 2 kV Comments: Criterion B Surge current load (surge) Standards/regulations: EN61000-4-5 Surge current load (surge)â Input: ± 0.5 kV Signal: ± 1 kV Comments: Criterion B Conducted interference Standards/regulations: EN61000-4-6 Conducted interferenceâ Comments: Criterion A Voltage: 10 V Emitted interference Standards/regulations: EN55011 Comments: Class A, industrial applications Criteria Criterion A: Normal operating behavior within the specified limits. Criterion B: Temporary impairment to operational behavior that is corrected by the device itself. |
Standards and regulations | Free from substances that could impair the application of coating: in accordance with VW-AUDI-Seat central standard P-VW 3.10.7 57 65 0 |
Mounting | Mounting type: DIN rail mounting |
ECLASS | ECLASS-11.0: 19170411 ECLASS-12.0: 19170411 ECLASS-13.0: 19170411 |
ETIM | ETIM 9.0: EC001467 |
UNSPSC | UNSPSC 21.0: 43201500 |