Industrial Automation
Notes | Utilization restriction EMC note: EMC: class A product, see manufacturer's declaration in the download area Utilization restrictionâ CCCex note: Use in potentially explosive areas is not permitted in China. |
Product properties | Product type: Interface converter Application: RS-485 MTTF: 1808 Years (SN29500 standard, temperature25°C, operating cycle21%) 796 Years (SN29500 standard, temperature40°C, operating cycle34.25%) 334 Years (SN29500 standard, temperature40°C, operating cycle100%) Insulation characteristics Pollution degree: 2 |
Electrical properties | Electrical isolation: VCC // RS-485 (A) // RS-485 (B) Maximum power dissipation for nominal condition: 2.16 W Test voltage data interface/power supply: 1.5 kVrms (50Hz, 1min.) Supply Supply voltage range: 18 V AC/DC ... 30 V AC/DC (via pluggable COMBICON screw terminal block) Nominal supply voltage: 24 V AC/DC Typical current consumption: 90 mA (24VDC) Max. current consumption: 100 mA |
Connection data | Supply Single conductor/terminal point, rigid: 0.2 mm² ... 2.5 mm² Single-wire/terminal point, flexible: 0.2 mm² ... 2.5 mm² Conductor cross section, flexible [AWG]: 24 ... 12 Tightening torque: 0.56 Nm ... 0.79 Nm |
Interfaces | Bit distortion: < 1.5 % Bit distortion, input: max. ± 35 % Bit distortion, output: < 3.6 % Bit delay: < 200 ns Signal: Modbus Transmission channels: 2 (1/1), TD, RD, half duplex Data: RS-485 interface, in acc. with EIA/TIA-485, DIN 66259-4/RS-485 2-wire Serial transmission speed: 1.2 / 2.4 / 4.8 / 9.6 / 19.2 / 38.4 / 57.6 / 75 / 93.75 / 115.2 / 136 / 187.5 / 375 / 500 / 1500 kbps Connection method: Pluggable screw connection Transmission length: ⤠1200 m (depends on transmission speed, bus system and cable type) Cascadability: 9 (4,8 ... 93,75 kbps) 8 (115.2 kbps) 7 (136 kbps) 6 (187.5 kbps) 5 (375 ... 1500 kbps) Termination resistor: 390 é 180 é 390 é (Can be connected) Single-wire/terminal point, flexible: 0.2 mm² ... 2.5 mm² Max. AWG conductor cross section, flexible: 12 Min. AWG conductor cross section, flexible: 24 Transmission medium: 2-wire twisted pair, shielded File format/coding: UART (11/10 bit switchable; NRZ) Data direction switching: Automatic control, min. station response time 1 bits Protocols supported: transparent protocol Data: RS-485 interface, in acc. with EIA/TIA-485, DIN 66259-4/RS-485 2-wireâ Serial transmission speed: 1.2 / 2.4 / 4.8 / 9.6 / 19.2 / 38.4 / 57.6 / 75 / 93.75 / 115.2 / 136 / 187.5 / 375 / 500 / 1500 kbps Transmission length: ⤠1200 m (depends on transmission speed, bus system and cable type) Cascadability: 9 (4,8 ... 93,75 kbps) 8 (115.2 kbps) 7 (136 kbps) 6 (187.5 kbps) 5 (375 ... 1500 kbps) Single-wire/terminal point, flexible: 0.2 mm² ... 2.5 mm² Max. AWG conductor cross section, flexible: 12 Min. AWG conductor cross section, flexible: 24 Transmission medium: 2-wire twisted pair, shielded File format/coding: UART (11/10 bit switchable; NRZ) Data direction switching: Automatic control, min. station response time 1 bits Protocols supported: transparent protocol |
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/da57c9364aeb1a47ab3c572a45a056a9/-S204x204-FJPG Width: 22.5 mm Height: 99 mm Depth: 114.5 mm |
Material specifications | Material: PA 6.6-FR |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -40°C ... 70°C Ambient temperature (storage/transport): -40°C ... 85°C Altitude: ⤠5000 m (For restrictions, see the manufacturer's declaration for altitude operation) Permissible humidity (operation): 10 % ... 95 % (non-condensing) |
Approvals | CE Certificate: CE-compliant EAC Identification: EAC ATEX Identification: ï II 3 G Ex nA IIC T4 Gc Certificate: IBExU16ATEXB004 X Note: Please follow the special installation instructions in the documentation! IECEx Identification: Ex nA IIC T4 Gc Certificate: IECEx IBE 15.0034X UL, USA/Canada Identification: 508 Recognized Class I, Div. 2, Groups A, B, C, D Class I, Zone 2, AEx nA IIC T4 Class I, Zone 2, Ex nA IIC T4 Gc X KC approval for South Korea Certificate: KCC-REI-PCK-FL2744429 Corrosive gas test Identification: ISA-S71.04-1985 G3 Harsh Group A Shipbuilding Identification: DNV GL DNV GL data Temperature: B Humidity: A Vibration: A EMC: B Enclosure: Required protection according to the Rules shall be provided upon installation on board |
EMC data | Noise immunity: EN 61000-6-2:2005 Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU Noise emission: EN 61000-6-4 Electrostatic discharge Standards/regulations: EN61000-4-2 Electrostatic dischargeâ Contact discharge: ± 6 kV (Test Level 3) Discharge in air: ± 8 kV (Test Level 3) Indirect discharge: ± 6 kV (Test Level 3) Comments: Criterion B Electromagnetic HF field Standards/regulations: EN61000-4-3 Electromagnetic HF fieldâ Frequency range: 26 MHz ... 3 GHz (Test Level 3) Field intensity: 10 V/m Comments: Criterion A Fast transients (burst) Standards/regulations: EN61000-4-4 Fast transients (burst)â Input: ± 4 kV (Test Level 3) Signal: ± 2 kV (Test Level 3) Comments: Criterion B Surge current load (surge) Standards/regulations: EN61000-4-5 Surge current load (surge)â Input: ± 0.5 kV (DC supply) Signal: ± 2 kV (Data line, asymmetrical) Comments: Criterion B Conducted interference Standards/regulations: EN61000-4-6 Conducted interferenceâ Frequency range: 0.15 MHz ... 80 MHz Comments: Criterion A Voltage: 10 V Emitted interference Standards/regulations: EN55011 Comments: Class A, industrial applications Criteria Criterion A: Normal operating behavior within the specified limits. Criterion B: Temporary impairment to operational behavior that is corrected by the device itself. |
Mounting | Mounting type: DIN rail mounting |
ECLASS | ECLASS-11.0: 27242208 ECLASS-12.0: 27242208 ECLASS-13.0: 27242208 |
ETIM | ETIM 9.0: EC001423 |
UNSPSC | UNSPSC 21.0: 43222600 |
Description other products