FLT 35-260 - Type 1+2 combined lightning current and surge arrester

Type 1 / Class I / B arrester (lightning current arrester) with encapsulated arc chopping spark gap, 1-channel. Housing width: 17.5 mm (1 Div.)
Product Code: 2800110
Partner cod.: 2800110
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Description
Download
Tecnichal data
Product propertiesIEC test classification: I
T1
EN type: T1
IEC power supply system: TN-S
TN-C
TT
Type: DIN rail module, one-piece
Product type: Combination type
Number of positions: 1
Surge protection fault message: none
Insulation characteristics
Overvoltage category: III
Pollution degree: 2
Electrical propertiesNominal frequency fN: 50 Hz (60Hz)
Connection dataConnection method: Screw connection
Screw thread: M5
Tightening torque: 4.5 Nm
Stripping length: 14.5 mm
Conductor cross section flexible min.: 2.5 mm²
Conductor cross section flexible max.: 25 mm²
Conductor cross section, rigid min.: 2.5 mm²
Conductor cross section, rigid max.: 35 mm²
Conductor cross section AWG: 6 ... 2
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/d1f5ed03fd95e24fa3d3e418ea12b00f/-S204x204-FJPG
Width: 17.6 mm
Height: 88.6 mm
Depth: 66.2 mm
Horizontal pitch: 1 Div.
Material specificationsFlammability rating according to UL 94: V-0
CTI value of material: 600
Insulating material: PA 6.6
Material group: I
Housing material: PA 6.6
Mechanical propertiesMechanical data
Open side panel: No
Protective circuitMode of protection: L-PEN
Direction of action: 1L-N/PE
Nominal voltage UN: 230/400VAC (TN)
230/400VAC (TT)
Nominal frequency fN: 50 Hz (60Hz)
Maximum continuous operating voltage UC (L-PEN): 385 VAC
Rated load current IL: 80 A
Residual current IPE: ≤ 0.1 mA
Standby power consumption PC: ≤ 35 mVA
Nominal discharge current In (8/20) µs (L-PEN): 35 kA
Impulse discharge current (10/350) µs (L-PEN), charge: 17.5 As
Impulse discharge current (10/350) µs (L-PEN), specific energy: 306 kJ/Ω
Impulse discharge current (10/350)µs (L-PEN), peak current value Iimp: 35 kA
Follow current quenching capacity Ifi (L-PEN): 3 kA (260 V AC)
1.5 kA (385 V AC)
Short-circuit current rating ISCCR: 3 kA (260 V AC)
1.5 kA (385 V AC)
Voltage protection level Up (L-PEN): ≤ 5 kV
Front of wave sparkover voltage at 6 kV (1.2/50) µs: ≤ 5 kV
TOV behavior at UT (L-PEN): 440 VAC (5s / withstand mode)
440 VAC (120min / withstand mode)
Response time tA (L-PEN): ≤ 100 ns
Max. backup fuse with V-type through wiring: 80 A AC (gG)
Max. backup fuse with branch wiring: 400 A AC (gG)
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20 (only when all terminal points are used)
Ambient temperature (operation): -40°C ... 85°C
Ambient temperature (storage/transport): -40°C ... 85°C
Altitude: ≤ 2000 m (amsl)
Permissible humidity (operation): 5 % ... 95 %
Standards and regulationsAir clearances and creepage distances
Standards/regulations: EN60664-1 / EN61643-11
Standards/specifications: IEC 61643-11
EN61643-11
Note: 2011
2012
MountingMounting type: DIN rail: 35 mm
Technical Specs
ECLASSECLASS-11.0: 27130802
ECLASS-13.0: 27171201
ETIMETIM 9.0: EC000381
UNSPSCUNSPSC 21.0: 39121600
Description
Type 1 / Class I / B arrester (lightning current arrester) with encapsulated arc chopping spark gap, 1-channel. Housing width: 17.5 mm (1 Div.)
Download