PHOENIX CONTACT 2800190
PHOENIX CONTACTNot available

VAL-MS-T1/T2 335/12.5 ST - Type 1/2 surge protection plug

L-N replacement plug for VAL-MS-T1/T2 335/12.5 plug-in lighting/surge arrester.
Product Code: 2800190
Partner cod.: 2800190
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Download
Tecnichal data
Product propertiesIEC test classification: I / II
T1 / T2
EN type: T1 / T2
IEC power supply system: TN-C
TN-S
TT
Type: DIN rail module, two-section, divisible
Product type: Replacement plug
Product family: VALVETRAB MS
Number of positions: 1
Surge protection fault message: optical
Insulation characteristics
Overvoltage category: III
Pollution degree: 2
Electrical propertiesNominal frequency fN: 50 Hz (60Hz)
Connection dataConnection method: pluggable
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/244085b8304de74e95f3135ca62ba23a/-S204x204-FJPG
Width: 17.7 mm
Height: 47 mm
Depth: 67.3 mm
Horizontal pitch: 1 Div.
Material specificationsFlammability rating according to UL 94: V-0
CTI value of material: 600
Insulating material: PA 6.6/PBT
Material group: I
Housing material: PA 6.6
PBT
Protective circuitMode of protection: L-N
L-PEN
Direction of action: L-N / L-PEN
Nominal voltage UN: 240/415VAC (TN-C, TN-S)
240/415VAC (TT)
Nominal frequency fN: 50 Hz (60Hz)
Maximum continuous voltage UC: 335 VAC
Residual current IPE: ≤ 800 µA
Standby power consumption PC: ≤ 270 mVA
Nominal discharge current In (8/20) µs: 12.5 kA
Maximum discharge current Imax (8/20) µs: 50 kA
Impulse discharge current (10/350)µs, charge: 6.25 As
Impulse discharge current (10/350)µs, specific energy: 39 kJ/Ω
Impulse discharge current (10/350)µs, peak value limp: 12.5 kA
Short-circuit current rating ISCCR: 25 kA
Voltage protection level Up: ≤ 1.2 kV
≤ 1.6 kV (30 kA - 8/20 µs)
Residual voltage Ures: ≤ 1.2 kV (at In)
≤ 1.1 kV (at 10 kA)
≤ 1 kV (at 5 kA)
≤ 0.9 kV (at 3kA)
TOV behavior at UT: 415 VAC (5s / withstand mode)
457 VAC (120min / safe failure mode)
Response time tA: ≤ 25 ns
Max. backup fuse with branch wiring: 160 A (gG)
Additional technical data
Maximum discharge current Imax (8/20) µs: 65 kA
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -40°C ... 80°C
Ambient temperature (storage/transport): -40°C ... 80°C
Altitude: ≤ 2000 m (amsl)
Permissible humidity (operation): 5 % ... 95 %
Shock (operation): 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation): 7.5g (10 ... 500 Hz / 2.5 h / X, Y, Z)
ApprovalsUL specifications
Maximum continuous operating voltage MCOV (L-N): 335 VAC
Nominal discharge current In (L-N): 20 kA
Mode of protection: L-N
Nominal voltage: 240VAC
Power distribution system: Single phase
Nominal frequency: 50/60 Hz
Measured limiting voltage MLV (L-N): 2630 V
SPD Type: 4CA
Standards and regulationsStandards/specifications: IEC 61643-11
Note: 2011
EN 61643-11
Standards/specifications: EN61643-11
Note: 2012
MountingMounting type: on base element
Technical Specs
ECLASSECLASS-11.0: 27130890
ECLASS-13.0: 27171292
ETIMETIM 9.0: EC002496
UNSPSCUNSPSC 21.0: 39121600
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_00200.pdf

Approvals_00246.pdf

Approvals_00291.pdf

Approvals_01874.pdf

Approvals_01937.pdf

Flyer_00002.pdf

Flyer_00001.pdf

Manufacturer_declaration_00573.pdf

Manufacturer_declaration_01991.pdf

Package_slip_00540.pdf

Technical_drawing_38345.pdf